| Plan Review Stops For Permit 11090049 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-09-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-09-06 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-09-06 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2011-09-06 14:56:19 | 951 28TH ST. | | | 11090049 | | | ADD A 3 PHASE 240 VOLT ELECTRIC SERVICE | | | | | | PROVIDE DETAILS OR PICTURE OF ALL EXISTING SERVICES ON | | | THE BUILDING. NEC 215.15 | | | ALL SERVICE DISCONNECTS MUST BE GROUPED IN ONE | | | LOCATION. NEC 230.72 | | | VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT | | | THE AVAILABLE FAULT CURRENT. NEC 110.9 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|