Plan Review Details - Permit 11090049
Plan Review Stops For Permit 11090049
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-09-06 Cont ID  
Sent By rlecky Date 2011-09-06 Time 14:45 Rev Time 0.00
Received By rlecky Date 2011-09-06 Time 14:34 Sent To  
Notes
2011-09-06 14:56:19951 28TH ST.
 11090049
 ADD A 3 PHASE 240 VOLT ELECTRIC SERVICE
  
 PROVIDE DETAILS OR PICTURE OF ALL EXISTING SERVICES ON
 THE BUILDING. NEC 215.15
 ALL SERVICE DISCONNECTS MUST BE GROUPED IN ONE
 LOCATION. NEC 230.72
 VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT
 THE AVAILABLE FAULT CURRENT. NEC 110.9
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-06 Cont ID  
Sent By rlecky Date 2011-09-06 Time 14:45 Rev Time 0.00
Received By rlecky Date 2011-09-06 Time 14:34 Sent To  
Notes
***NONE***