Plan Review Details - Permit 11090046
Plan Review Stops For Permit 11090046
Review Stop ENG ENGINEERING CSD
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2012-10-25 Cont ID  
Sent By   Date 2012-10-25 Time   Rev Time 1.00
Received By   Date 2012-09-18 Time   Sent To I
Notes
2012-10-25 14:57:12PLEASE INCORPORATE PLANNING'S COMMENTS SO THAT WE MAY
 REVIEW CHANGES.
  
 #1 DRAINAGE: PROVIDE PERVIOUS AND IMPERVIOUS AREA
 CALCULATION FOR SITE.
  
 (STORMWATER RUNOFF FOR DEVELOPMENT WITHIN DEVELOPED
 AREA MUST MEET THE FOLLOWING LEVEL OF SERVICE
 STANDARDS: (A) WATER QUANTITY: POST-DEVELOPMENT RUN-OFF
 SHALL NOT EXCEED PRE-DEVELOPMENT RUNOFF RATES FOR THE
 ENTIRE DEVELOPMENT. (B) WATER QUALITY: THE TREATMENT OF
 POST-DEVELOPMENT RUNOFF FROM THE SITE MUST ENSURE THAT
 RECEIVING WATER QUALITY CRITERIA ESTABLISHED IN CHAPTER
 17-302, SECTION 17-302.500, F.A.C. ARE MAINTAINED.)
 THE CITY OF WPB REQUIRES THAT APPLICANT ABIDE BY SOUTH
 FLORIDA WATER MANAGEMENT DRAINAGE CRITERIA AS FOLLOWS:
  
 #2 APPLICANTS TREAT FIRST INCH OF RUNOFF WATER OR 2 1/2
 TIMES THE IMPERVIOUS AREA (EXCLUDING BUILDING AREA),
 WHICHEVER IS GREATER.
  
 (THIS CRITERIA ALSO COMPLIES WITH PERFORMANCE STANDARDS
 ESTABLISHED IN CHAPTER 17-25, F.A.C., WITH TREATMENT OF
 THE FIRST INCH OF RUN-OFF ONSITE TO MEET WATER QUALITY
 STANDARDS REQUIRED BY CH. 17-302, SECTION 17-302.500,
 F.A.C. STORMWATER DISCHARGE FACILITIES MUST BE DESIGNED
 SO AS NOT TO DEGRADE THE RECEIVING WATER BODY BELOW THE
 MINIMUM CONDITIONS NECESSARY TO ASSURE THE SUITABILITY
 OF WATER FOR THE DESIGNATED USE AS ESTABLISHED IN
 CHAPTER 17-302, F.A.C.)
  
 [email protected]
 (561) 494-1085

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2012-04-20 Cont ID  
Sent By mgonzale Date 2012-04-20 Time   Rev Time 1.00
Received By mgonzale Date 2012-04-20 Time   Sent To  
Notes
2012-04-20 09:46:02COMMENTS:
  
 #1 RAINFALL DEPTHS LESS THAN SFWMD'S MAPS
  
 #2 DRAINAGE CALCULATIONS DO NOT INCLUDE THE ENTIRE
 SITE.
  
 #3 HOW IS RUNOFF DIRECTED TO CATCH BASINS OR DRY
 RETENTION AREAS?
  
 #4 WILL PERVIOUS AREAS BE GRASSED OR REMAIN ROCKED
 AREAS? (ROCKED AREAS ARE NOT CONSIDERED PERVIOUS.
  
 #5 IF ANY SPECIFIC QUESTIONS RELATED TO STORMWATER
 PLEASE REFER THEM TO:
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 PHONE: 494-1040 EXT: 1120
 FAX: 494-1116
 E-MAIL: [email protected]
  
 ******************************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-09-27 Cont ID  
Sent By mgonzale Date 2011-09-27 Time   Rev Time 1.00
Received By mgonzale Date 2011-09-27 Time   Sent To  
Notes
2011-09-27 09:16:11COMMENTS
  
 #1 SURVEY SUBMITTED DOES NOT SHOW THE WORK AREA.
  
 #2 PLEASE SHOW CROSS SECTION OF PROPOSED PAVEMENT
 SHOWING CONCRETE BASE AND PAVEMENT.
  
 #3 STATE PERVIOUS AND IMPERVIOUS CALCULATION OF THE
 SITE INCLUDING IMPROVEMENTS SOT THAT THE CITY CAN
 UPDATE STORMWATER ACCOUNT.
 (2001 SURVEY SUBMITTED IS NOT CURRENT)
  
 #4 PLEASE SHOW HOW STORM CATCH BASINS CONNECT.
  
 #5 THE REQUIRED WATER QUALITY TREATMENT VOLUME FOR WET
 DETENTION IS THE GREATER OF 1 INCH OVER THE ENTIRE
 RIGHT OF WAY OR 2.5 INCHES OVER THE IMPERVIOUS AREA.
 CONSULT WITH YOUR CIVIL ENGINEER.
  
 **************************************
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2013-01-09 Time 15:07 Sent To  
Notes
2013-01-09 15:08:01SENT TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-26 Cont ID  
Sent By lmartine Date 2012-10-26 Time 09:04 Rev Time 0.00
Received By lmartine Date 2012-10-18 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-26 Cont ID  
Sent By lmartine Date 2012-04-20 Time 16:45 Rev Time 0.00
Received By lmartine Date 2012-04-05 Time 10:33 Sent To  
Notes
2012-04-05 10:33:54TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-30 Cont ID  
Sent By shill Date 2011-09-30 Time 09:20 Rev Time 0.00
Received By shill Date 2011-09-07 Time 09:13 Sent To  
Notes
2011-09-07 09:13:34TO ZONING
  

Review Stop Z ZONING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date 2013-01-11 Time   Sent To  
Notes
2013-01-11 09:41:41GAVE TO E.S. - MD

Review Stop Z ZONING
Rev No 3 Status F Date 2012-10-12 Cont ID  
Sent By eschneid Date 2012-10-12 Time 11:01 Rev Time 1.00
Received By eschneid Date 2012-09-26 Time 13:54 Sent To ENG
Notes
2012-09-26 14:23:39FAILED
  
 1) REPEAT COMMENT - THE SCOPE OF WORK SHOWN ON THE
 ENGINEERING PLANS SHOW THE ENTIRE SITE WILL BE
 OVERLAYED WITH ASPHALT. THIS REQUIRES THAT THE PARKING
 AND LOADING AREAS BE BROUGHT INTO CONFORMITY WITH THE
 CITY'S LANDSCAPE REGULATIONS. THIS INCLUDES PERIMETER
 LANDSCAPE AS WELL AS TERMINAL ISLANDS IN THE PARKING
 AREA. PLEASE NOTE THAT THE SITE IS REQUIRED TO HAVE A
 MINIMUM OF 15 PERCENT LANDSCAPE AREA, EXCLUDING THE DRY
 DETENTION AREA, NOT THE 12 PERCENT AS SHOWN. NOTE: THE
 CONTRACTOR/ENGINEER HAS STATED TO STAFF THAT THE
 PARKING LOT WILL NOT BE OVERLAYED WITH ASPHALT AND THAT
 THE ONLY THE AREA EAST OF THE EXISTING PARKING WILL BE
 IMPROVED. IF THIS IS THE CASE, THE PLANS SHALL CLEARLY
 REFLECT THE SCOPE OF WORK AND THE PARKING AREA
 LANDSCAPE DOES NOT NEED TO BE BROUGHT IN CONFORMANCE
 WITH THE EXISTING CODE. THE AREA SURROUNDING THE NEWLY
 ASPHALTED AREA DOES NEED TO COMPLY WITH THE LANDSCAPE
 CODE.
  
 2) REPEAT COMMENT - A LANDSCAPE PERMIT, WHICH INCLUDES
 A LANDSCAPE PLAN SIGNED AND SEALED BY A FLORIDA
 REGISTERED LANDSCAPE ARCHITECT, AND MEETING THE
 PROVISIONS OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, SHALL BE SUBMITTED TO THE CITY'S BUILDING
 DIVISION. THE LANDSCAPE PLAN SHALL MATCH THE CIVIL PLAN
 LAYOUT. ZONING WILL NOT APPROVE THIS PERMIT UNTIL BOTH
 PLANS HAVE BEEN REVIEWED AND COMPLY WITH CODE. THE
 LANDSCAPE PLAN SUBMITTED WITH THIS PERMIT DOES NOT
 MATCH THE SITE DATA ON THE ENGINEERING PLANS. NOTE: THE
 LANDSCAPE PLANS WILL BE FULLY REVIEWED AS PART OF THE
 LANDSCAPE PERMIT.
  
 3) REPEAT COMMENT: NEITHER THE SURVEY OR THE
 ENGINEERING PLANS CLEARLY INDICATE THE AREAS THAT ARE
 CURRENTLY LANDSCAPED (OR NOT COVERED IN PAVING/SHELL
 ROCK/ETC. THIS COMMENT WILL NOT APPLY IF THE SCOPE OF
 WORK IS REDUCED TO ONLY PAVING THE AREA EAST OF THE
 EXISTING PARKING LOT.
  
 4) REPEAT COMMENT: THE AREAS CONTAINING OUTDOOR STORAGE
 SHALL BE SCREENED IN ACCORDANCE WITH THE SECTION
 94-444(C) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. THE PLANS DO NOT DEMONSTRATE SCREENING OF
 THE OUTDOOR STORAGE.
  
 5) REPEAT COMMENT - THE PARKING DETAIL DOES NOT MATCH
 WEST PALM BEACH REQUIREMENTS.
  
 6) REPEAT COMMENT - THE RIGHT-OF-WAY ADJACENT TO THE
 SITE SHALL BE SODDED AND IRRIGATED AND MAINTAINED.
 NOTE: THIS SHALL BE CLEARLY SHOWN ON THE LANDSCAPE
 PLAN.
  
 7) LANDSCAPED AREAS SHALL BE PROTECTED FROM VEHICULAR
 ENCROACHMENT BY TYPE D CURB OR EQUIVALENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2012-04-13 Cont ID  
Sent By eschneid Date 2012-04-13 Time 11:42 Rev Time 1.50
Received By eschneid Date 2012-04-05 Time 15:33 Sent To ENG
Notes
2012-04-13 12:41:20FAILED
  
 1) THE SCOPE OF WORK SHOWN ON THE ENGINEERING PLANS
 SHOW THE ENTIRE SITE WILL BE OVERLAYED WITH ASPHALT.
 THIS REQUIRES THAT THE PARKING AND LOADING AREAS BE
 BROUGHT INTO CONFORMITY WITH THE CITY'S LANDSCAPE
 REGULATIONS. THIS INCLUDES PERIMETER LANDSCAPE AS WELL
 AS TERMINAL ISLANDS IN THE PARKING AREA. PLEASE NOTE
 THAT THE SITE IS REQUIRED TO HAVE A MINIMUM OF 15
 PERCENT LANDSCAPE AREA, EXCLUDING THE DRY DETENTION
 AREA, NOT THE 12 PERCENT AS SHOWN.
  
 2) A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN
 SIGNED AND SEALED BY A FLORIDA REGISTERED LANDSCAPE
 ARCHITECT, AND MEETING THE PROVISIONS OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, SHALL BE SUBMITTED TO THE
 CITY'S BUILDING DIVISION. THE LANDSCAPE PLAN SHALL
 MATCH THE CIVIL PLAN LAYOUT. ZONING WILL NOT APPROVE
 THIS PERMIT UNTIL BOTH PLANS HAVE BEEN REVIEWED AND
 COMPLY WITH CODE.
  
 3) NEITHER THE SURVEY OR THE ENGINEERING PLANS CLEARLY
 INDICATE THE AREAS THAT ARE CURRENTLY LANDSCAPED (OR
 NOT COVERED IN PAVING/SHELL ROCK/ETC.
  
 4) THE AREAS CONTAINING OUTDOOR STORAGE SHALL BE
 SCREENED IN ACCORDANCE WITH THE SECTION 94-444(C) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 5) THE PARKING DETAIL DOES NOT MATCH WEST PALM BEACH
 REQUIREMENTS.
  
 6) THE RIGHT-OF-WAY ADJACENT TO THE SITE SHALL BE
 SODDED AND IRRIGATED AND MAINTAINED.
  
 7) ) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 SUBMITTAL OF PLANS SHOWING THE ADDITION OF LANDSCAPE.
  
 8) A PRE-MEETING MAY BE BENEFICIAL TO DISCUSS THE
 LANDSCAPE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
2012-04-05 15:33:56GIVEN TO ES

Review Stop Z ZONING
Rev No 1 Status F Date 2011-09-15 Cont ID  
Sent By eschneid Date 2011-09-15 Time 14:55 Rev Time 0.25
Received By eschneid Date 2011-09-08 Time 11:29 Sent To ENG
Notes
2011-09-15 15:00:34FAILED
  
 1) THE SURVEY PROVIDED WITH THE APPLICATION DOES NOT
 MATCH THE AERIAL. PROVIDE A RECENT SURVEY, LESS THAN
 ONE YEAR OLD.
  
 2) SHOW THE PROPOSED AREA OF WORK ON TWO COPIES OF THE
 UPDATED SURVEY OR SITE PLANS.
  
 3) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON THE
 RESUBMITTED ITEMS SHOWING THE AREA OF WORK.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.


Account Summary | Usage Policy | Privacy Policy