Plan Review Details - Permit 11090038
Plan Review Stops For Permit 11090038
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-09 Cont ID  
Sent By rmcdouga Date 2011-09-09 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2011-09-09 Time 09:55 Sent To  
Notes
2011-09-09 09:56:50SUBMITTED CORRECTED SURVEY BEFORE PERMIT WAS ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-09-08 Cont ID  
Sent By rmcdouga Date 2011-09-08 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2011-09-08 Time 07:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-08 Cont ID  
Sent By rmcdouga Date 2011-09-08 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2011-09-08 Time 07:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2011-09-08 Cont ID  
Sent By rmcdouga Date 2011-09-08 Time 07:58 Rev Time 0.00
Received By rmcdouga Date 2011-09-08 Time 07:58 Sent To  
Notes
2011-09-08 08:00:30A SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR THE GAS PERMIT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-09-08 Cont ID  
Sent By rmcdouga Date 2011-09-08 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2011-09-08 Time 11:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-09-08 Cont ID  
Sent By rmcdouga Date 2011-09-08 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2011-09-08 Time 08:00 Sent To  
Notes
2011-09-08 09:14:512007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 INCLUDING THE PUMP CURVE FOR THE 2 HP PUMP THAT WILL BE
 INSTALLED.
  
 2) THE PLANS SPECIFY A TDH OF 60 FEET. SUBMIT 2 COPIES
 OF TOTAL DYNAMIC HEAD (TDH) CALCULATIONS FOR THE SYSTEM
 OR DESIGN THE SYSTEM FOR THE MAXIMUM FLOW RATE OF THE
 PUMP.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-09-09 Cont ID  
Sent By jroach Date 2011-09-09 Time 09:31 Rev Time 0.00
Received By jroach Date 2011-09-09 Time 09:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-09-07 Cont ID  
Sent By jroach Date 2011-09-07 Time 18:52 Rev Time 0.00
Received By jroach Date 2011-09-06 Time 10:06 Sent To B
Notes
2011-09-06 10:06:36TO JOHN ROACH