Plan Review Details - Permit 11090032
Plan Review Stops For Permit 11090032
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-09-29 Cont ID  
Sent By rmcdouga Date 2011-09-29 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2011-09-27 Time 09:49 Sent To  
Notes
2011-09-27 11:15:522007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED LESS THAN 600 FEET FROM THE
 INLAND WATERWAY. THEREFORE, IT IS EXPOSURE CATEGORY C.
 ACCORDING TO FBC R301.2.1.4.3, THE ROOF SHEATHING
 UPLIFT, AS WELL AS, THE ROOF TO WALL UPLIFT LOADS ARE
 REQUIRED TO BE INCREASED BY 20 PERCENT. CORRECTIONS TO
 THE EXPOSURE AND WIND LOADS ON SHEETS S-2 AND S-6 ARE
 REQUIRED
  
 2) THE OPENING PRESSURES ON SHEET A-3, WHICH ARE BASED
 ON EXPOSURE B NEED TO BE INCREASED TO REFLECT EXPOSURE
 C. FBC R301.2.1
  
 3) PROVIDE DETAILS (SIZE/LOCATIONS) FOR THE ROOF
 SCUPPERS AND OVERFLOW SCUPPERS WITH CALCULATIONS. FBC
 R903.4 AND R903.4.1 SEE ALSO FBC P 1106 AND 1107
  
 4) SPECIFY THE SQUARE FEET OF LIVING AREA THAT IS BEING
 ADDED TO THE EXISTING STRUCTURE ON THE PLANS. CITY
 AMENDMENTS 106.1.2
  
 5) THE ROOF PLAN ON SHEET S-2 HAS CONFLICTING
 INFORMATION. BOTH 2 X 12 AND 2 X 8 RAFTERS ARE
 SPECIFIED AT THE VERANDA. PLEASE CORRECT.
  
 6) SHOW COMPLIANCE WITH FBC R312 FOR THE VERANDA GUARD
 RAILS.
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE COVERED BREEZEWAY
 THAT ATTACHES THE RESIDENCE WITH THE GARAGE. FBC R
 301.1
  
 8) SHOW COMPLIANCE WITH FBC R408 FOR CRAWL SPACE
 VENTILATION AND ACCESS.
  
 9) SHOW COMPLIANCE WITH FBC R806 FOR ATTIC VENTILATION.
  
 10) BOTH OF THE SECTION DRAWINGS ON SHEET S-2 ARE
 LABELED A-A. THE TOP ONE SHOULD BE LABELED B-B. PLEASE
 CORRECT.
  
 11) THE TWO DRAWINGS ON THE TRUSS LAYOUT FROM THE TRUSS
 COMPANY NEED TO BE IDENTIFIED (LABELED). THERE DOES NOT
 APPEAR TO BE A ROOF LAYOUT OR ROOF TRUSS DRAWINGS FOR
 THE ADDITION. IT APPEARS THAT ONE OF THE DRAWINGS ON
 THE LAYOUT IS FOR FLOOR TRUSSES AND THE F01 TRUSS
 DRAWINGS APPEAR TO BE FLOOR TRUSSES BASED ON THE LOADS
 GIVEN. THE STRUCTURAL PLANS SPECIFY 2 X 12 JOISTS FOR
 BOTH FLOORS OF THE ADDITION. PLEASE CORRECT.
  
 12) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE ENERGY
 CALCULATION FORMS. (1) THE ENERGY COMPLIANCE FORM IS
 REQUIRED TO BE SIGNED BY THE OWNER OR HIS AGENT. (2)
 SPECIFY THE INSULATION R-VALUE FOR THE THE ADDITION,
 WHICH IS A CRAWL SPACE NOT A SLAB ON GRADE. (3) THE
 PLANS SPECIFY R-19 ATTIC INSULATION AND THE ENERGY FORM
 LISTS R-30. (4) SPECIFY THE INSULATION FOR THE FLOOR
 BELOW THE VERANDA. (5) THE 2 X 8 EXTERIOR WOOD WERE NOT
 SHOWN ON THE FORM. (6) THE CEILING FANS ARE NOT
 SPECIFIED ON THE PLANS. IN ORDER TO RECEIVE THE CEILING
 FAN CREDIT, ONE 36" FAN IS REQUIRED IN THE BEDROOM AND
 TWO 48" FANS ARE REQUIRED IN THE LIVING ROOM. (6)
 CREDIT CAN NOT BE TAKEN FOR BOTH CEILING FANS AND CROSS
 VENTILATION PER 2007 ENERGY GLITCH AMENDMENTS C4.2.1.1.
  
 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 106.3.3
  
 14) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILES. IF AN ADHESIVE WILL BE USED
 SUBMIT THE PRODUCT APPROVALS FOR IT. FBC R905.3.7 AND
 DCA RULE 9N-3
  
 15) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS. DCA RULE 9N-3
  
 16) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 SINGLE HUNG BATHROOM WINDOW . DCA RULE 9N-3
  
 17) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS THAT WILL BE USED ON THE FLAT ROOF.
 PROVIDE RAS 117 CALCULATIONS FOR ENHANCED FASTENING.
 DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-09-29 Cont ID  
Sent By rlecky Date 2011-09-14 Time 17:46 Rev Time 0.00
Received By rlecky Date 2011-09-14 Time 17:46 Sent To  
Notes
2011-09-29 17:47:2011090032
 255 CORDOVA RD
 ADDITION TO SFD
  
 PLEASE PROVIDE A PANEL SCHEDULE FOR EACH ELECTRIC
 PANEL. SHOW THE LOCATION OF EACH PANEL AND ELECTRIC
 METER ON THE PLAN. NEC 215.5
 INDICATE THE FEEDER AND CONDUIT SIZE FOR THE SUB PANEL.
 NEC 215.5
 ALL CIRCUITS IN THE GARAGE MUST ORIGINATE FROM A SUB
 PANEL LOCATED WITHIN THE GARAGE. NEC 250.32
 GROUNDING AND BONDING OF THE SUB PANEL IN THE GARAGE
 SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR AND A
 GROUNDING ELECTRODE. NEC 250.32 (A) AND (B)
 EVERY ADDITION TO AN EXISTING BUILDING WITH A FIRE
 PLACE OR GAS FIRED APPLIANCES SHALL HAVE A CARBON
 MONOXIDE DETECTOR WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES. FBC R313.4
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2011-09-16 Cont ID  
Sent By jpapa Date 2011-09-16 Time 09:52 Rev Time 0.00
Received By jpapa Date 2011-09-16 Time 09:52 Sent To  
Notes
2011-09-16 09:55:33FAILED.
  
 1. THE PROPOSED SECOND FLOOR BALCONY (VERANDA)
 ELEVATIONS SHALL BE REVISED TO REFLECT THE DESIGN
 APPROVED BYT THE HISTORIC PRESERVATION BOARD, PER HPB
 11-25.
  
 FOR MORE INFORMATION, PLEASE CONTACT JILLIAN PAPA,
 HISTORIC PRESERVATION PLANNER AT 561-822-1454.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-09-30 Time 16:11 Rev Time 0.00
Received By shill Date 2011-09-09 Time 11:03 Sent To  
Notes
2011-09-09 11:04:00R--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-09-26 Cont ID  
Sent By rmcdouga Date 2011-09-26 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2011-09-26 Time 09:45 Sent To  
Notes
2011-09-26 09:46:22IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-09-26 Cont ID  
Sent By rmcdouga Date 2011-09-26 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2011-09-26 Time 09:45 Sent To  
Notes
2011-09-27 09:48:262007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS. FBC R M1401.3
  
 2) SPECIFY THE SIZE OF ALL DUCTWORK, INCLUDING THE
 FLEX, ON THE PLANS.
  
 3) THE LICENSE NUMBER AND SIGNATURE OF THE QUALIFIER
 FOR WHALEN AIR IS REQUIRED ON THE MECHANICAL PLANS. FS
 47.OO3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-09-26 Cont ID  
Sent By rmcdouga Date 2011-09-26 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2011-09-26 Time 09:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-09-16 Cont ID  
Sent By jpapa Date 2011-09-16 Time 09:55 Rev Time 0.00
Received By jpapa Date 2011-09-16 Time 09:55 Sent To  
Notes
2011-09-16 10:45:08FAILED.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 2. PURSUANT TO SECTION 94-482 OF THE ZLDR: REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE
 SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT
 BUILDING FACADE). THIS MAY BE REQUIRED AS A SEPARATE
 PERMIT (CHECK WITH CONSTRUCTION SERVICES STAFF).
  
 3. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITIONS TO ALL PROPERTY LINES TO INSURE COMPLIANCE
 WITH THE DEVELOPMENT STANDARDS SET FORTH IN SECTION
 94-82 OF THE ZLDRS.
  
 4. PURSUANT TO SEC. 94-83, THE MAXIMUM OVERALL HEIGHT
 IS 30 FEET.
  
 PLEASE DEMONSTRATE COMPLIANCE WITH THIS STANDARD BY
 MEARUING THE 'OVERALL HEIGHT' ACCORDING TO THE
 FOLLOWING DEFINITION [SEC. 94-79 OF THE ZLDRS]: "
 OVERALL HEIGHT IS MEASURED AS THE VERTICAL DISTANCE IN
 FEET FROM FINISHED GRADE TO THE HIGHEST POINT OF THE
 ROOF FOR FLAT ROOFS; TO THE DECK LINE FOR MANSARD
 ROOFS; AND TO THE AVERAGE HEIGHT BETWEEN EAVES AND THE
 RIDGE FOR GABLE, HIP AND GAMBREL ROOFS. WHERE FINISHED
 GRADE IS MORE THAN TWO FEET ABOVE NATURAL GRADE,
 OVERALL HEIGHT SHALL BE MEASURED FROM TWO FEET ABOVE
 NATURAL GRADE. FINISHED GRADE SHALL NOT EXCEED REQUIRED
 MINIMUM FLOOD REGULATIONS. SEE SECTION 94-306 FOR
 LIMITED HEIGHT EXCEPTIONS."
  
 FOR MORE INFORMATION, FEEL FREE TO CONTACT JILLIAN
 PAPA, HISTORIC PRESERVATION PLANNER AT 561-822-1454.
  
  
  
  