Plan Review Details - Permit 11080860
Plan Review Stops For Permit 11080860
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-19 Cont ID  
Sent By jwitmer Date 2011-10-19 Time 11:15 Rev Time 1.00
Received By jwitmer Date 2011-10-12 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-09-13 Cont ID  
Sent By jwitmer Date 2011-09-13 Time 14:13 Rev Time 0.77
Received By jwitmer Date 2011-09-12 Time 15:54 Sent To  
Notes
2011-09-13 14:35:06BUILDING PLAN REVIEW
 PERMIT: 11080860
 ADD: 2100 45TH ST # A-2A
 CONT: COVENANT CONSTRUCTION
 TEL: (561)255-1855
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-000 CODE CLASSIFICATION INDICATES THIS
 BUILDING TO BE A TYPE T UNPROTECTED/ NON-SPINKLERED.
 PLEASE REVIEW TABLE 601 FOR TYPE I CONSTRUCTION THERE
 IS EITHER A TYPE I-A OR TYPE TYPE I-B BOTH OF WHICH
 HAVE FIRE RATING ON THEIR STRUCTURAL MEMBERS, PLEASE
 REVIEW FIRE RATING IN HOURS OF STRUCTURAL COMPONENTS
 AND MEMBERS.
  
 2) PLEASE REVIEW DOOR 4, 5 7 & 9 AND THIER REQUIRED
 CLEAR WIDTH, SHEET A-500 DOOR SCHEDULE INDICATE THESE
 DOORS TO BE A 2'-8" DOOR. PLEASE REVIEW 2007/ 09 FBC-B
 1008.1.1 AND REQUIRED CLEAR WIDTH. THE MINIMUM WIDTH OF
 EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT
 LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF NOT
 LESS THAN 32 INCHES (813 MM). CLEAR OPENINGS OF
 DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN
 90 DEGREES (1.57 RAD). WHERE THIS SECTION REQUIRES A
 MINIMUM CLEAR WIDTH OF 32 INCHES (813 MM) AND A DOOR
 OPENING INCLUDES TWO DOOR LEAVES WITHOUT A MULLION, ONE
 LEAF SHALL PROVIDE A CLEAR OPENING WIDTH OF 32 INCHES
 (813 MM).
  
 3) DOOR # 16 SWINGS INTO THE CLEAR FLOOR SPACE OF THE
 DRINKING FOUNTAIN. 11-4.15.5 CLEARANCES.
  
 (1) A-100 WALL- AND POST-MOUNTED CANTILEVERED UNITS
 SHALL HAVE A CLEAR KNEE SPACE BETWEEN THE BOTTOM OF THE
 APRON AND THE FLOOR OR GROUND AT LEAST 27 INCHES (685
 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 17 INCHES TO 19
 INCHES (430 MM TO 485 MM) DEEP [SEE FIGURE 27(A) AND
 FIGURE 27(B)]. SUCH UNITS SHALL ALSO HAVE A MINIMUM
 CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) TO ALLOW A PERSON IN A WHEELCHAIR TO APPROACH
 THE UNIT FACING FORWARD.
  
 4) A-100 PLEASE SEE DOORS 19 & 20 FOR THEIR MANEUVERING
 CLEARENCES AT DOORS. 11-4.13.6 MANEUVERING CLEARANCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN FIGURE 25. THE FLOOR OR GROUND AREA WITHIN THE
 REQUIRED CLEARANCES SHALL BE LEVEL AND CLEAR.
  
 5) ADDITIONAL INFORMATION REQUIRED, 106.1.2 PLANS
 INDICATE TWO LABORATORIES, PLEASE PROVIDE WHAT TYPE OF
 ACTIVITIES WILL TAKE PLACE IN THESE ROOMS, WILL EXTRA
 VENTILATION BE REQUIRED, EXHAUST HOODS? MEDIGAL GAS?
 HOT WATER?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-16 Cont ID  
Sent By rlecky Date 2011-09-16 Time 11:32 Rev Time 0.00
Received By rlecky Date 2011-09-16 Time 10:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-09-06 Cont ID  
Sent By wjolin Date 2011-09-06 Time 10:16 Rev Time 0.00
Received By wjolin Date 2011-09-06 Time 09:46 Sent To  
Notes
2011-09-06 10:16:222100 45TH STREET, SUITE A-2A
 PERMIT #11080860
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE EMERGENCY LIGHTING FOR RESOURCE #105.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 STROKE. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 NOTE: SHEET M-1 NOT SEALED BY ENGINEER.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-19 Cont ID  
Sent By jwitmer Date 2011-10-19 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2011-10-06 Time 12:05 Sent To  
Notes
2011-10-06 12:05:52B--19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-21 Cont ID  
Sent By hmoser Date 2011-09-21 Time 14:25 Rev Time 0.00
Received By hmoser Date 2011-08-31 Time 16:26 Sent To  
Notes
2011-08-31 16:27:20SENT TO B19 SHELF FOR REVIEW BY ALL TRADES. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-10-19 Cont ID  
Sent By jwitmer Date 2011-10-19 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2011-10-19 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-09-21 Cont ID  
Sent By hmoser Date 2011-09-21 Time 14:24 Rev Time 0.00
Received By hmoser Date 2011-09-21 Time 13:00 Sent To  
Notes
2011-09-21 14:24:37PLAN DENIED
 PER SECTION 471.003 (2) B (H) FLORIDA STATUTES
 THE DESIGNER OF THIS AIRCONDITIONING PLAN IS NOT SIGNED
 ON THE APPLICATION
 THERE FORE SHE OR HE CAN NOT DESIGN THE AIRCONDITIONING
 SYSTEM
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-10-12 Cont ID  
Sent By lwagner Date 2011-10-12 Time 08:57 Rev Time 0.00
Received By lwagner Date 2011-10-12 Time 08:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-09-14 Cont ID  
Sent By lwagner Date 2011-09-14 Time 11:10 Rev Time 0.00
Received By lwagner Date 2011-09-07 Time 10:12 Sent To  
Notes
2011-09-09 09:49:26FBC 2007 PLUMBING REVIEW #1.
 DENIED:
  
 1. KITCHEN SINK - HOT WATER REQUIRED 607.1 WHERE
 REQUIRED. IN OCCUPIED STRUCTURES, HOT WATER SHALL BE
 SUPPLIED TO ALL PLUMBING FIXTURES AND EQUIPMENT
 UTILIZED FOR BATHING, WASHING, CULINARY PURPOSES,
 CLEANSING, LAUNDRY OR BUILDING MAINTENANCE.
  
 2. SANITARY FOR KITCHEN SINK IS SHOWN CONNECTING TO THE
 RESTROOM WET VENT SYSTEM - SHALL BE CONNECTED
 DOWNSTREAM OF WET VENT.
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-10-17 Cont ID  
Sent By jroach Date 2011-10-17 Time 14:00 Rev Time 0.00
Received By jroach Date 2011-10-17 Time 14:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-09-07 Cont ID  
Sent By jroach Date 2011-09-07 Time 19:58 Rev Time 0.00
Received By jroach Date 2011-09-07 Time 19:58 Sent To  
Notes
2011-09-07 19:59:53ZONING PLAN REVIEW
  
 PERMIT NO.: 11080860
 ADDRESS: 2100 45TH STREET
 CONTRACTOR/CONTACT: AMANDA SHIELDS
 TELEPHONE NO.: 561.255.1855
 SCOPE OF REVIEW: BUILDOUT
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) AS PART OF THE CONVERSION OF THIS SPACE FROM A
 DRIVE-THROUGH TO AN ENCLOSED RETAIL BAY, IT WAS
 REQUIRED THAT THE LANDSCAPING THROUGHOUT THE SITE BE
 UPGRADED TO COMPLY WITH THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS). THIS WORK WAS NEVER
 COMPLETED AND DID NOT PASS FINAL INSPECTION. NO PERMITS
 FOR THE BUILD-OUT OF THIS SPACE WILL BE ISSUED UNTIL
 THIS OUTSTANDING ISSUE HAS BEEN RESOLVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved