2011-08-29 11:56:05222 LAKEVIEW AVENUE - SUITE #810
 PERMIT #11080760
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE IF THIS SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE SPRINKLER
 DISTANCE BELOW THE CEILING DECK.
  
 OCCUPANCY HAZARD NOT INDICATED ON PLANS. IF THIS IS A
 LIGHT HAZARD OCCUPANCY, THE SPRINKLERS SHOULD BE OF THE
 QUICK-RESPONSE TYPE. IF THIS IS AN ORDINARY HAZARD
 OCCUPANCY, SPRINKLER SPACING EXCEEDS 130 SQUARE FEET
 PER SPRINKLER.
  
 INDICATE THE MAXIMUM WORKING PRESSURE FOR THE EIGHTH
 FLOOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-09-12 Cont ID  
Sent By ddaniels Date 2011-09-12 Time 09:14 Rev Time 0.00
Received By ddaniels Date 2011-09-09 Time 17:58 Sent To  
Notes
2011-09-09 17:58:26IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-06 Cont ID  
Sent By hmoser Date 2011-09-06 Time 10:53 Rev Time 0.00
Received By hmoser Date 2011-08-26 Time 14:38 Sent To  
Notes
2011-08-26 14:38:59SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-09-06 Cont ID  
Sent By hmoser Date 2011-09-06 Time 10:53 Rev Time 0.00
Received By hmoser Date 2011-09-06 Time 10:53 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved