Plan Review Details - Permit 11080722
Plan Review Stops For Permit 11080722
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-08-31 Cont ID  
Sent By jwitmer Date 2011-08-31 Time 14:54 Rev Time 0.77
Received By jwitmer Date 2011-08-31 Time 14:31 Sent To  
Notes
2011-08-31 14:54:08BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 KITCHENETTE: IF THE KITCHENETTE IS ACTUALLY USED AS A
 BREAK ROOM THEN COMPLIANCE WITH 2007/ 09 FBC-B 11-4.24
 IS REQUIRED.
 11-4.24 SINKS.
 11-4.24.1 GENERAL. SINKS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24.
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) ABOVE
 THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE. KNEE CLEARANCE THAT IS AT
 LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE,
 AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS.
 11-4.24.4 DEPTH. EACH SINK SHALL BE A MAXIMUM OF 61/2
 INCHES (165 MM) DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK (SEE FIGURE 32).
 11-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND
 DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT.
 THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION
 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-08-31 Cont ID  
Sent By rlecky Date 2011-08-31 Time 14:20 Rev Time 0.00
Received By rlecky Date 2011-08-31 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-26 Cont ID  
Sent By wjolin Date 2011-08-26 Time 14:49 Rev Time 0.00
Received By wjolin Date 2011-08-26 Time 14:18 Sent To  
Notes
2011-08-26 14:49:16560 OKEECHOBEE BOULEVARD
 PERMIT #11080722
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE EXIT SIGN IN OPEN WORK AREA SPACE.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-01 Cont ID  
Sent By rbrown Date 2011-09-01 Time 15:54 Rev Time 0.00
Received By rbrown Date 2011-08-26 Time 08:46 Sent To  
Notes
2011-08-26 08:46:16C13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-31 Cont ID  
Sent By hmoser Date 2011-08-31 Time 15:53 Rev Time 0.00
Received By hmoser Date 2011-08-31 Time 15:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-08-31 Cont ID  
Sent By rbrown Date 2011-08-31 Time 15:24 Rev Time 0.00
Received By rbrown Date 2011-08-31 Time 11:12 Sent To  
Notes
2011-08-31 15:24:41PLANS REVIEWED AND STAMPED BY LARRY WAGNER

Review Stop Z ZONING
Rev No 2 Status P Date 2011-09-01 Cont ID  
Sent By rbrown Date 2011-09-01 Time 15:55 Rev Time 0.00
Received By rbrown Date 2011-09-01 Time 15:54 Sent To  
Notes
2011-09-01 15:57:37PASSED WITH PROVISO PER ERIC SCHNEIDER. GROUND LEVEL
 A/C EQUIPMENT LOCATION NOT APPROVED AS CURRENTLY SHOWN
 ON THE PLANS. SEE CONDITIONAL APPROVAL DOCUMENT SIGNED
 BY OWNER AND CONTRACTOR. REVISED PLANS REQUIRED PRIOR
 TO INSPECTION.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-08-31 Cont ID  
Sent By eschneid Date 2011-08-31 Time 16:44 Rev Time 1.50
Received By eschneid Date 2011-08-31 Time 16:44 Sent To  
Notes
2011-08-31 16:50:44FAILED
  
 1) THE CITY COMMISSION APPROVED THE SITE AND LANDSCAPE
 PLANS FOR THE BUILDING AT 560 OKEECHOBEE BOULEVARD WITH
 THE APPROVAL OF RESOLUTION NO. 359-05. THE CITY
 COMMISSION APPROVAL DID NOT INCLUDE GROUND MOUNTED A/C
 EQUIPMENT. THE A/C UNITS WERE APPROVED ON THE ROOF AND
 SCREENED BY THE PARAPETS.
  
 2) THE RELOCATION OF THE A/C EQUIPMENT FROM THE ROOFTOP
 TO GROUND LEVEL REQUIRES THE APPROVAL OF A MINOR
 PLANNED DEVELOPMENT AMENDMENT TO REVISE THE SITE AND
 THE LANDSCAPE PLANS. PLEASE NOTE THAT ZONING STAFF IS
 NOT IN FAVOR OF LOCATING A/C EQUIPMENT, EVEN WITH
 SCREENING, FRONTING ON OKEECHOBEE BOULEVARD, THE MAIN
 VEHICULAR ENTRANCE INTO WEST PALM BEACH. PLEASE
 CONSIDER INSTALLING THE NEW A/C EQUIPMENT ON THE ROOF
 WITH THE EXISTING SCREENED UNITS.
  
 3) IF THE RELOCATION OF THE A/C UNITS ON THE GROUND IS
 PURSUED, THEN THE A/C UNITS SHALL BE SCREENED FROM
 PUBLIC VIEW THROUGH ANY COMBINATION OF LANDSCAPING,
 WALLS AND EQUIPMENT LOCATION PER THE CITYPLACE
 DEVELOPMENT OF REGIONAL IMPACT REQUIREMENTS. ELEVATIONS
 SHOWING THE SCREENING OF THE FULL HEIGHT OF THE A/C
 EQUIPMENT AT INSTALLATION SHALL BE PROVIDED WITH BOTH
 THE MINOR PD AMENDMENT APPLICATION AND THE BUILDING
 PERMIT.
  
 4) A RECENT SURVEY, LESS THAN ONE YEAR OLD, SHALL BE
 PROVIDED SHOWING THE ACCURATE LOCATION OF THE PROPOSED
 A/C EQUIPMENT, INCLUDING ITS SETBACK FROM THE
 OKEECHOBEE BOULEVARD RIGHT-OF-WAY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  