Plan Review Details - Permit 11080715
Plan Review Stops For Permit 11080715
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-09-09 Cont ID  
Sent By rmcdouga Date 2011-09-09 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2011-09-09 Time 10:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-09 Cont ID  
Sent By rmcdouga Date 2011-09-09 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2011-09-09 Time 10:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2011-09-09 Cont ID  
Sent By rmcdouga Date 2011-09-09 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2011-09-09 Time 10:52 Sent To  
Notes
2011-09-09 10:53:03SEPARATE PERMIT, APPLICATION AND PLAN REVIEW IS
 REQUIRED FOR GAS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-10-07 Cont ID  
Sent By rmcdouga Date 2011-10-07 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2011-10-05 Time 16:51 Sent To  
Notes
2011-10-05 16:52:08SENT TO R MC DOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-09-30 Cont ID  
Sent By rmcdouga Date 2011-09-30 Time 11:57 Rev Time 0.00
Received By rmcdouga Date 2011-09-15 Time 10:43 Sent To  
Notes
2011-09-15 10:44:17INCOMING SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-09 Cont ID  
Sent By rmcdouga Date 2011-09-09 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2011-08-25 Time 14:35 Sent To  
Notes
2011-08-25 14:35:27TO ZONING
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-10-07 Cont ID  
Sent By rmcdouga Date 2011-10-07 Time 09:51 Rev Time 0.00
Received By rmcdouga Date 2011-10-07 Time 08:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-09-30 Cont ID  
Sent By rmcdouga Date 2011-09-30 Time 11:43 Rev Time 0.00
Received By rmcdouga Date 2011-09-30 Time 11:43 Sent To  
Notes
2011-09-30 11:57:252007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE MAXIMUM FLOW RATES FOR THE VARIABLE SPEED PUMPS
 WAS NOT USED IN THE TDH CALCULATIONS AS STATED IN THE
 FIRST REVIEW COMMENT #1.
  
 2) THE MAXIMUM WATER VELOCITY OF 6 FEET PER SECOND IN
 THE 2.5" BRANCH SUCTION PIPING AND THE 8 FEET PER
 SECOND IN THE 2.5" MAIN SUCTION PIPING IS EXCEEDED WHEN
 USING THE MAXIMUM FLOW RATE OF 145 GPM FOR THE VARIABLE
 SPEED PUMPS THAT WERE SPECIFIED. ANSI/APSP-7 SECTION
 4.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-09-09 Cont ID  
Sent By rmcdouga Date 2011-09-09 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2011-09-09 Time 10:53 Sent To  
Notes
2011-09-09 11:55:562007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
 FBC R4101 & ANSI/APSP 7
  
 1) THE PLANS SPECIFY TWO VARIABLE SPEED PUMPS WHICH
 REQUIRE THE MAXIMUM FLOW RATE OF THE PUMP TO BE USED IN
 CALCULATIONS. SEE NOTE NUMBER 1 ON TDH CALCULATION WORK
 SHEET.
  
 2) SPECIFY THE MANUFACTURER, MODEL NUMBER AND HORSE
 POWER OF EACH PUMP. SUBMIT 2 COPIES OF THE
 SPECIFICATIONS FOR EACH OF THE THREE POOL PUMPS
 INCLUDING THE PUMP CURVES.
  
 3) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR EACH OF THE SYSTEMS OR DESIGN THE
 SYSTEMS FOR THE MAXIMUM FLOW RATE OF THE PUMP.
  
 4) SUBMIT A PIPING DIAGRAM THAT SPECIFIES ALL PIPE
 SIZES IN EACH SYSTEM.
  
 5) THE FIRST SHEET OF PLANS SHOWS FIVE SETS OF MAIN
 DRAINS FOR A TOTAL OF 10. THE PIPING DIAGRAM SHOWS FOUR
 SETS OF MAIN DRAINS FOR A TOTAL OF 8. PLEASE CLARIFY.
  
 6) THE VALUE FOR THE SCOPE OF WORK APPEARS TO BE LOW.
 PLEASE SUBMIT A COPY OF THE SIGNED CONTRACT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2011-09-29 Cont ID  
Sent By lfranco Date 2011-09-29 Time 13:58 Rev Time 0.00
Received By lfranco Date 2011-09-16 Time 13:03 Sent To  
Notes
2011-09-29 14:04:53PLANNING AND ZONING: *** POOL PERMIT PASSED: A FENCE
 POOL BARRIER WAS SUBMITTED AND APPROVED. INSTALL FENCE
 AROUND PROPERTY LINE & FENCE TO SERVE AS POOL BARRIER -
 PERMIT NUMBER 11090169 *****
  
  
  
  
 9/26/11 JORGE P/U PERMIT A
 9/26/11 CALLED CONTRACTOR PERMIT READY FOR ISSUE W/ FEE
 137.50 FILE UNDER "J" SMALL BIN AR
 9/23/11- APPROVED ROUTED TO MISC #2- AV
2011-09-16 13:03:50GIVEN TO LINDA FRANCO

Review Stop Z ZONING
Rev No 1 Status F Date 2011-09-01 Cont ID  
Sent By lfranco Date 2011-09-01 Time 18:11 Rev Time 0.50
Received By lfranco Date 2011-08-29 Time 16:54 Sent To  
Notes
2011-09-01 18:59:41PLANNING AND ZONING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW: PLEASE REFERENCE
 THE POOL PERMIT IN THE FENCE PERMIT FOR EASIER
 PROCESSING OF BOTH PERMITS.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B) AND
 (C):
 B. EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE. AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  