Plan Review Details - Permit 11080670
Plan Review Stops For Permit 11080670
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2011-08-31 Cont ID  
Sent By shill Date 2011-08-31 Time 14:43 Rev Time 0.00
Received By shill Date 2011-08-31 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-25 Cont ID  
Sent By wjolin Date 2011-08-25 Time 14:51 Rev Time 0.00
Received By wjolin Date 2011-08-25 Time 13:56 Sent To M
Notes
2011-08-25 14:34:214050 NORTH FLAGLER DRIVE
 PERMIT #11080670
 MASTER #11080115
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SUBMIT COPY OF SIGNED CONTRACT INDICATING THE TOTAL
 COST (MATERIALS PLUS LABOR).
  
 INSPECTOR'S NOTE:
 1) A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG
 THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A
 MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE
 DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR
 AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC
 904.11.1.
  
 2) DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE
 SURFACE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-31 Cont ID  
Sent By hmoser Date 2011-08-31 Time 12:03 Rev Time 0.00
Received By hmoser Date 2011-08-25 Time 14:51 Sent To  
Notes
2011-08-25 09:41:07SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-31 Cont ID  
Sent By hmoser Date 2011-08-31 Time 12:03 Rev Time 0.00
Received By hmoser Date 2011-08-31 Time 11:02 Sent To  
Notes
2011-08-31 11:20:39REFER TO SECTION 904.11.1 MANUAL SYSTEM OPERATION.
 2007 FBC.