Plan Review Details - Permit 11080666
Plan Review Stops For Permit 11080666
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-11-18 Cont ID  
Sent By shill Date 2011-11-18 Time 11:48 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-10-26 Cont ID  
Sent By shill Date 2011-10-26 Time 11:08 Rev Time 0.00
Received By shill Date 2011-10-26 Time 11:08 Sent To  
Notes
2011-10-26 11:13:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 2ND REVIEW, PLEASE SEE REFERENCED CODE SECTION. PROVIDE
 DIMENSIONS OF ALL GLAZING. THIS DOES NOT INCLUDE OPAQUE
 DOORS.
  
 2. CONFIRM WINDOW SIZES. WINDOW SIZES SHOULD BE W X H,
 WHICH IS THE INDUSTRY STANDARD FOR WINDOW AND DOOR
 OPENINGS. IF THE WINDOW IS 37" HIGH, EGRESS OPENING
 WILL BE LESS THAN 15". REVISE FLOOR PLAN IF NECESSARY.
 ALSO REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS, FBC
 R310, FBC EB 604.1. INCLUDE INFORMATION REGARDING THE
 EXISTING WINDOWS IF NECESSARY.
  
 CONTRACTOR SUBMITTED SKETCHES WHICH CONFIRMED THAT
 OPENINGS ARE 37" HIGH. PLEASE ADDRESS THE REMAINDER OF
 THE COMMENT; PROVIDE A FLOOR PLAN TO SHOW ROOM
 DESIGNATIONS FOR PROPOSED WINDOWS AND TYPE OF EXISTING
 WINDOWS.
  
 3. TWO COMPLETE SETS OF PLANS REQUIRED FOR PERMIT
 ISSUANCE. FAILURE TO PROVIDE TWO SETS MAY RESULT IN
 COPY/ADMIN FEES.
  
 4. PERMIT VALUE IS TO INCLUDE LABOR AND MATERIALS,
 FBC108.3.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-29 Cont ID  
Sent By shill Date 2011-08-29 Time 12:19 Rev Time 0.00
Received By shill Date 2011-08-29 Time 12:19 Sent To  
Notes
2011-08-29 12:24:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 2. CONFIRM WINDOW SIZES. WINDOW SIZES SHOULD BE W X H,
 WHICH IS THE INDUSTRY STANDARD FOR WINDOW AND DOOR
 OPENINGS. IF THE WINDOW IS 37" HIGH, EGRESS OPENING
 WILL BE LESS THAN 15". REVISE FLOOR PLAN IF NECESSARY.
 ALSO REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS, FBC
 R310, FBC EB 604.1. INCLUDE INFORMATION REGARDING THE
 EXISTING WINDOWS IF NECESSARY.
  
 3. TWO COMPLETE SETS OF PLANS REQUIRED FOR PERMIT
 ISSUANCE. FAILURE TO PROVIDE TWO SETS MAY RESULT IN
 COPY/ADMIN FEES.
  
 4. PERMIT VALUE IS TO INCLUDE LABOR AND MATERIALS,
 FBC108.3.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-11-18 Cont ID  
Sent By shill Date 2011-11-18 Time 11:48 Rev Time 0.00
Received By shill Date 2011-11-09 Time 11:09 Sent To  
Notes
2011-11-09 11:09:16TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-26 Cont ID  
Sent By shill Date 2011-10-26 Time 11:14 Rev Time 0.00
Received By shill Date 2011-10-18 Time 15:46 Sent To  
Notes
2011-10-18 15:46:53TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-29 Cont ID  
Sent By shill Date 2011-08-29 Time 12:24 Rev Time 0.00
Received By shill Date 2011-08-25 Time 10:04 Sent To  
Notes
2011-08-25 10:04:30SENT TO BUILDING UNDER $5000 SHELF FOR REVIEW. JG.