| 2011-08-30 16:12:13 | BUILDING PLAN REVIEW |
| | PERMIT: 11080665 |
| | ADD: 1450 CENTREPARK BLVD 150 |
| | CONT: ANDERSON-MOORE CONSTRUCTION CORP. |
| | TEL: (561)662-1819 |
| | |
| | 2007 FLORIDA BUILDING CODE-BUILDING W/ 2009 FBC |
| | SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS CHAPTER 1 |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1450 CENTREPARK #165 11080820- NO FEE PERMIT FOR DEMO |
| | OF TENANT SEPERATION WALL AND NEW TENANT SEPERATION |
| | WALL, (DRYWALL SCREW INSPECTION) ONLY. |
| | COMMENTS FOR BOTH PERMITS 11080665 SUITE # 150 AND |
| | 11080820 SUITE # 165 WILL APPEAR UNDER THIS REVIEW. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY SHEET A8 INDICATES FOR BOTH SUITES |
| | THE COMMON PATH OF TRAVEL IS EXCEEDED. 2007 FBC-B |
| | 1014.3 EXCEPTION# 1 DOES ALLOW FOR A 100 FOOT COMMON |
| | PATH OF TRAVEL FOR SPRINKLERED BUILDINGS. FOR BOTH |
| | SUITES THIS COMMON PATH OF TRAVEL IS EXCEEDED. |
| | |
| | 2) SHEET A8 THE LIFE SAFETY PLAN INDICATES WITHIN SUITE |
| | # 150 SINCE THE COMMON PATH OF TRAVEL IS EXCEEDED, IT |
| | WOULD APPEAR THAT A SECOND EXIT DOOR WOULD NEED TO BE |
| | INCORPORATED INTO THE PLAN LAYOUT MEETING THE |
| | REQUIREMENT OF 1015.2.1 EXCEPTION #3. THE SECONDARY |
| | EXIT DOOR CURRENTLY DOE NOT MEET THIS REQUIREMENT. |
| | |
| | 3) DISCREPANCY IN PLANS PLEASE REVIEW SHEETS A4 VERSES |
| | A8 PRINTING ROOM # 116. SHEET A4 INDICATES A DOOR INTO |
| | THE EXIT ACCESS CORRIDOR, DOOR # 021 WHICH DOES NOT |
| | APPEAR ON SHEET A8. |
| | |
| | 4) SHEET A8 INDICATES A SEPERATE TENANT SPACE ROOM |
| | NUMBER 115 LABELED COURIER, THESE TENANT SEPERATION |
| | WALLS ARE NOT INDICATED AS TENANT SEPERATION WALLS. |
| | 2007/09 FBC-B 708.1(7). |
| | |
| | 5) A4 & A8 BOTH INDICATE A NETWORK ROOM # 107, THIS |
| | ROOM MAY REQUIRE A 1 HOUR RATING PER NFPA 645.4(5) IF |
| | CONSIDERED A IT ROOM? |
| | |
| | 6) A8 STORAGE ROOM # 117IS OVER 100SQ. FT. AND WILL |
| | NEED TO COMPLY WITH 2007/09 FBC-B FOR THE WALL TO BE |
| | ABLE TO RESIST THE PASSAGE OF SMOKE SEE TABLE 508.2. |
| | WHERE TABLE 508.2 PERMITS AN AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE |
| | INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE |
| | REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF |
| | RESISTING THE PASSAGE OF SMOKE. THE PARTITIONS SHALL |
| | EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING ASSEMBLY OR |
| | FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY ABOVE OR TO |
| | THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, OR SUB |
| | DECK ABOVE. DOORS SHALL BE SELF- OR AUTOMATIC CLOSING |
| | UPON DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| | 715.4.7.3. DOORS SHALL NOT HAVE AIR TRANSFER OPENINGS |
| | AND SHALL NOT BE UNDERCUT IN EXCESS OF THE CLEARANCE |
| | PERMITTED IN ACCORDANCE WITH NFPA 80. |
| | |
| | 7) 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |