Plan Review Details - Permit 11080654
Plan Review Stops For Permit 11080654
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2011-09-13 Cont ID  
Sent By jwitmer Date 2011-09-13 Time 15:08 Rev Time 0.00
Received By jwitmer Date 2011-09-13 Time 15:07 Sent To  
Notes
2011-09-13 15:08:17ENGINEERING TO REVIEW. JW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2011-11-01 Cont ID  
Sent By mgonzale Date 2011-11-01 Time   Rev Time 0.25
Received By mgonzale Date 2011-11-01 Time   Sent To  
Notes
2011-10-28 13:55:18PASSED WITH PROVISO
 PLAN IS ACCEPTABLE FOR GARBAGE PICK-UP.
 DUMPSTER MUST BE SCREENED WITH FANCE AND LANDSCAPE.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET,
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2011-10-12 Cont ID  
Sent By mgonzale Date 2011-10-12 Time   Rev Time 0.50
Received By mgonzale Date 2011-10-12 Time   Sent To  
Notes
2011-10-12 07:24:16MINIMUM STANDARD FOR DUMPSTER SHOULD BE MET.
 PLEASE REFER TO CITY OF WPB DUMPSTER DETAIL.
 YOU WILL NEED TO NOTE THE LANDSCAPE SCREENING.
  
 "WALLS MUST LANDSCAPED WITH HEDGE MATERIAL
 PLANTED AT 2 FOOT INTERVALS"
  
 SEE
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/PDF/STANDARDS/GC-8
 .PDF
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-10-17 Cont ID  
Sent By wjolin Date 2011-10-17 Time 13:57 Rev Time 0.00
Received By wjolin Date 2011-10-17 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-26 Cont ID  
Sent By wjolin Date 2011-08-26 Time 14:13 Rev Time 0.00
Received By wjolin Date 2011-08-26 Time 14:09 Sent To  
Notes
2011-08-26 14:13:303319 SOUTH DIXIE HIGHWAY
 PERMIT #11080654
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET C-2 INDICATES A NEW REAR PARKING SPACE AND A
 6-INCH CURB; THIS WILL IMPEDE ON THE REQUIRED
 UNOBSTRUCTED WIDTH OF 20'-0" FOR FIRE DEPARTMENT
 APPARATUS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-22 Cont ID  
Sent By shill Date 2011-11-01 Time 10:34 Rev Time 0.00
Received By shill Date 2011-10-12 Time 12:53 Sent To  
Notes
2011-10-12 12:53:27C--7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-12 Cont ID  
Sent By lmartine Date 2011-10-12 Time 12:52 Rev Time 0.00
Received By lmartine Date 2011-08-25 Time 11:18 Sent To  
Notes
2011-08-25 11:18:46SENT TO C7 SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2011-11-01 Cont ID  
Sent By eschneid Date 2011-11-01 Time 11:31 Rev Time 0.25
Received By eschneid Date 2011-11-01 Time 11:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-09-05 Cont ID  
Sent By eschneid Date 2011-09-05 Time 12:56 Rev Time 0.25
Received By eschneid Date 2011-09-05 Time 12:56 Sent To  
Notes
2011-09-05 12:58:55FAILED
  
 1) CHAIN LINK AND SLATS IS NOT PERMITTED FOR A DUMPSTER
 ENCLOSURE GATE.
  
 2) STEVE RIVIERA, OF ABC, IN AN E-MAIL DATED AUGUST 24,
 2011, STATED THAT REVISED GATE PLANS WILL BE SUBMITTED.
 THEY WILL BE REVIEWED AT TIME OF SUBMITTAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.