Plan Review Details - Permit 11080627
Plan Review Stops For Permit 11080627
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-09 Cont ID  
Sent By wjolin Date 2011-09-09 Time 09:51 Rev Time 0.00
Received By wjolin Date 2011-09-09 Time 09:38 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-25 Cont ID  
Sent By wjolin Date 2011-08-25 Time 13:40 Rev Time 0.00
Received By wjolin Date 2011-08-25 Time 13:17 Sent To M
Notes
2011-08-25 13:40:511 NORTH CLEMATIS STREET - SUITE #320
 PERMIT #11080627
 MASTER #11060068
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ACTUAL MEASUREMENT BETWEEN THREE SEPARATE
 SPRINKLERS EXCEEDS 15'-0".
  
 VERIFY THE THREE ROOMS TO THE EAST HAVE PROPER
 SPRINKLER COVERAGE AS THE EXISTING SPRINKLERS ARE
 LOCATED MORE THAN 9'-0" FROM WALLS. THESE ROOMS ARE
 LABELED AS "NO CHANGE AFFECTING SPRINKLERS IN THIS
 ROOM."
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-31 Cont ID  
Sent By hmoser Date 2011-08-31 Time 13:40 Rev Time 0.00
Received By hmoser Date 2011-08-23 Time 13:54 Sent To  
Notes
2011-08-23 13:54:36TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-09-14 Cont ID  
Sent By hmoser Date 2011-09-14 Time 10:21 Rev Time 0.00
Received By hmoser Date 2011-09-14 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-08-31 Cont ID  
Sent By hmoser Date 2011-08-31 Time 13:35 Rev Time 0.00
Received By hmoser Date 2011-08-31 Time 13:35 Sent To  
Notes
2011-08-31 13:40:04PLEASE PROVIDE A COPIE OF THE SIGNED CONTRACT
 TO VERIFY THE VALUE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved