Plan Review Details - Permit 11080604
Plan Review Stops For Permit 11080604
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-10-27 Cont ID  
Sent By jwitmer Date 2011-10-27 Time 14:26 Rev Time 0.77
Received By jwitmer Date 2011-10-27 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-09-13 Cont ID  
Sent By jwitmer Date 2011-09-13 Time 14:43 Rev Time 0.55
Received By jwitmer Date 2011-09-13 Time 14:39 Sent To  
Notes
2011-09-13 14:55:59BUILDING PLAN REVIEW
 PERMIT: 11080604
 ADD: 3501 ELECTRONIC WAY
 CONT: UNITED GENERAL CONTRACTORS
 TEL: (954)914-1103
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2007/09 FBC-B 413.1 GENERAL. HIGH-PILED STOCK OR
 RACK STORAGE IN ANY OCCUPANCY GROUP SHALL COMPLY WITH
 THE FLORIDA FIRE PREVENTION CODE.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-09-13 Cont ID  
Sent By rlecky Date 2011-09-13 Time 08:48 Rev Time 0.00
Received By rlecky Date 2011-09-13 Time 07:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-10-26 Cont ID  
Sent By wjolin Date 2011-10-26 Time 14:24 Rev Time 0.00
Received By wjolin Date 2011-10-26 Time 14:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-09-06 Cont ID  
Sent By wjolin Date 2011-09-06 Time 15:29 Rev Time 0.00
Received By wjolin Date 2011-09-06 Time 12:49 Sent To  
Notes
2011-09-06 15:29:463501 ELECTRONICS WAY - PHASE 2
 PERMIT #11080604
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE TYPE OF RACK TO BE USED PER NFPA 13
 DEFINITIONS (DOUBLE-ROW RACK, MULTIPLE ROW RACK ETC.).
  
 INDICATE IF ANY SOLID SHELVING IS INTENDED TO BE USED
 WITH THE RACK STORAGE.
  
 PER NFPA 13 SECTION 12.1.13.2 STANDARD RESPONSE
 SPRINKLERS WITH A NOMINAL K-FACTOR OF 8.0 OR LARGER
 SHALL BE USED FOR SPRINKLER DENSITIES BETWEEN 0.20 AND
 0.34 GPM/SQ.FT.
  
 PER NFPA 13 SECTION 12.3.1.14.1 A NOMINAL 6-INCH
 TRANSVERSE FLUE SPACE IS REQUIRED BETWEEN LOADS AND
 RACK UPRIGHTS.
  
 PER NFPA 13 SECTION 12.3.4.1.3 THE DISTANCE BETWEEN
 AISLES SHALL BE AT LEAST 4-FEET.
  
 FIRE ALARM PLANS NOT SIGNED/SEALED BY ENGINEER.
  
 NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-10-27 Cont ID  
Sent By jwitmer Date 2011-10-27 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2011-10-20 Time 14:18 Sent To  
Notes
2011-10-20 14:22:06C--4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-20 Cont ID  
Sent By lmartine Date 2011-09-13 Time 14:17 Rev Time 0.00
Received By lmartine Date 2011-08-23 Time 11:57 Sent To  
Notes
2011-08-23 12:00:14INCOMING SENT TO C-4 BOX. JW
  
  