Plan Review Details - Permit 11080576
Plan Review Stops For Permit 11080576
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-08 Cont ID  
Sent By lmartine Date 2011-09-08 Time 12:19 Rev Time 0.00
Received By lmartine Date 2011-09-08 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-22 Cont ID  
Sent By jgomez Date 2011-08-22 Time 09:25 Rev Time 0.00
Received By jgomez Date 2011-08-22 Time 09:16 Sent To  
Notes
2011-08-22 09:42:37RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- IDENTIFY WHICH APPROVED ASSEMBLY FROM FLORIDA
 PRODUCT APPROVAL FL 5680-R3 SUBMITTED IS GOING TO BE
 USED TO CHECK COMPLIANCE WITH THE DESIGN PRESSURES OF
 SEC. 1609 FBC.
  
 2- FLORIDA PRODUCT APPROVAL FL 5680-R3 SUBMITTED
 REQUIRES SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS TO MEET
 THE DESIGN PRESSURES OF SEC. 1609 FBC. PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS (2 COPIES).
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION WAS
 UPDATED. PERMIT FEE BALANCE IS $285.15.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-22 Cont ID  
Sent By jgomez Date 2011-08-22 Time 09:17 Rev Time 0.00
Received By jgomez Date 2011-08-22 Time 09:17 Sent To  
Notes
***NONE***