| Plan Review Stops For Permit 11080552 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-09-06 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-08-19 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2011-08-22 07:24:24 | SENT TO MECHANICAL BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2011-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-09-06 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-09-06 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2011-09-06 09:48:17 | OK TO ISSUE W/PROVISO PER HM | | | PLANS FILED WITH MASTER 11060763 (INCLUDES ELECTRICAL | | | AND OTHER DETAILS) | | | | | | | | | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | SHOW COMPLIANCE WITH FBC MECHANICAL 403 | | | | | | LETTER SUBMITTED APPEARS TO PROVIDE ASHRAE 62 | | | CALCULATIONS. FOR RETAIL SPACE, OUTDOOR AIR IS TO BE | | | DETERMINED BASED ON OCCUPANCY LEVEL AND FLOOR AREA | | | (ONLY FLOOR AREA WAS USED). | | | | | | LETTER SUBMITTED IS NOT SIGNED AND SEALED, FS471. | | | PLEASE INCORPORATE OUTDOOR AIR CALCULATIONS INTO THE | | | PLAN. | | | | | | PLAN IS TO SHOW HOW OUTDOOR AIR WILL BE SUPPLIED (WHICH | | | UNITS, CFM PER UNIT). | | | | | | INCORPORATE WIND DESIGN CRITERIA INTO THE PLAN. | | | | | | | | | | | | |
|
|
|