Plan Review Details - Permit 11080552
Plan Review Stops For Permit 11080552
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-06 Cont ID  
Sent By shill Date 2011-09-06 Time 09:39 Rev Time 0.00
Received By shill Date 2011-08-19 Time 07:24 Sent To  
Notes
2011-08-22 07:24:24SENT TO MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-09-06 Cont ID  
Sent By shill Date 2011-09-06 Time 09:47 Rev Time 0.00
Received By shill Date 2011-09-06 Time 09:39 Sent To  
Notes
2011-09-06 09:48:17OK TO ISSUE W/PROVISO PER HM
 PLANS FILED WITH MASTER 11060763 (INCLUDES ELECTRICAL
 AND OTHER DETAILS)
  
  
 ****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SHOW COMPLIANCE WITH FBC MECHANICAL 403
  
 LETTER SUBMITTED APPEARS TO PROVIDE ASHRAE 62
 CALCULATIONS. FOR RETAIL SPACE, OUTDOOR AIR IS TO BE
 DETERMINED BASED ON OCCUPANCY LEVEL AND FLOOR AREA
 (ONLY FLOOR AREA WAS USED).
  
 LETTER SUBMITTED IS NOT SIGNED AND SEALED, FS471.
 PLEASE INCORPORATE OUTDOOR AIR CALCULATIONS INTO THE
 PLAN.
  
 PLAN IS TO SHOW HOW OUTDOOR AIR WILL BE SUPPLIED (WHICH
 UNITS, CFM PER UNIT).
  
 INCORPORATE WIND DESIGN CRITERIA INTO THE PLAN.
  
  
  
  