Plan Review Details - Permit 11080527
| Plan Review Stops For Permit 11080527 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2011-09-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-09-06 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-09-06 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-08-19 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-08-19 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-08-19 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2011-08-19 14:39:14 | PENDING RESPONSE TO PBC FIRE COMMENTS. | | | | | | SECTION 907. 1.1 OF THE FLORIDA BUILDING CODE ( FBC). | | | WIRE SIZES, BATTERY CALCULATIONS AND VISIBLE ALARM. | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2011-08-29 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-08-29 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-08-29 |
Time |
12:11 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2011-08-19 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-08-19 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-08-19 |
Time |
13:53 |
Sent To |
E |
|
| Notes |
| 2011-08-19 14:08:35 | 1411 NORTH FLAGLER DRIVE - SUITE #9200 | | | PERMIT #11080527 | | | MASTER #11050760 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLAN ADDRESS DOES NOT MATCH THE APPLICATION ADDRESS. | | | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBER TO EACH | | | FIRE ALARM DEVICE ON THE SYSTEM. | | | | | | NO BATTERY CALCULATIONS SUBMITTED. | | | | | | NO STROBE DEVICES PROVIDED IN PATIENT BLOOD DRAW ROOMS. | | | | | | NO WIRE SIZE INDICATED ON THE PLANS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-09-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-09-06 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-08-26 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2011-08-26 15:08:39 | TO FIRE | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-08-19 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-08-19 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-08-18 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2011-08-18 15:22:00 | TO FIRE | | | |
|
|
|