Plan Review Details - Permit 11080524
Plan Review Stops For Permit 11080524
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By rmcdouga Date 2011-09-07 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2011-09-07 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-25 Cont ID  
Sent By rmcdouga Date 2011-08-25 Time 08:56 Rev Time 0.00
Received By rmcdouga Date 2011-08-25 Time 07:51 Sent To  
Notes
2011-08-25 09:09:482007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY FOR THIS STRUCTURE IS "C" PER
 FBC R301.2.1.4.2. PLEASE INCREASE THE OPENING PRESSURES
 TO CORRESPOND WITH EXPOSURE CATEGORY C.
  
 2) THE ALLOWABLE PRESSURES ON THE SHUTTER INSTALLATION
 SCHEDULE ARE INCORRECT FOR THE ANCHORS, SPACING AND
 OTHER CRITERIA LISTED IN THE PRODUCT APPROVAL. THE
 ALLOWABLE PRESSURES DEPEND ON THE SUBSTRATE, MOUNT
 TYPE, SPAN, EDGE DISTANCE, ANCHOR TYPE AND ANCHOR
 SPACING. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-09-07 Cont ID  
Sent By rmcdouga Date 2011-09-07 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2011-08-29 Time 13:00 Sent To  
Notes
2011-08-29 13:01:01INCOMING SENT TO R. MCDOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-25 Cont ID  
Sent By rmcdouga Date 2011-08-25 Time 08:56 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2011-08-18 13:13:32MISC 1
  