Plan Review Details - Permit 11080463
Plan Review Stops For Permit 11080463
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-01 Cont ID  
Sent By jwitmer Date 2011-09-01 Time 15:31 Rev Time 0.55
Received By jwitmer Date 2011-09-01 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-19 Cont ID  
Sent By jwitmer Date 2011-08-19 Time 08:53 Rev Time 0.77
Received By jwitmer Date 2011-08-19 Time 08:53 Sent To  
Notes
2011-08-19 08:56:46BUILDING PLAN REVIEW
 PERMIT: 11080463
 ADD: 1500 N FLORIDA MANGO SUITE142
 CONT: MALASKY HOMES, INC.
 TEL: (561)471-8600
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 PERMIT: 11040647 1500 N FLORIDA MANGO SUITE 1,2 8B & 9B
 (FILE NET)
 INTERIOR DEMO OF WALLS, RAISE CEILING, NEW HVAC
 RE-PLUMB KITCHEN & ELECTRICAL OUTLETS.
 TYPE II-B
 SPRINKLERED
  
 SHEET A-1 LIFE SAFETY PLAN.
  
  
  
  
 1) 413.1 GENERAL. HIGH-PILED STOCK OR RACK STORAGE IN
 ANY OCCUPANCY GROUP SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 2) F] 903.2.6.1 HIGH-PILED STORAGE. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH
 THE FLORIDA FIRE PREVENTION CODE IN ALL BUILDINGS OF
 GROUP M WHERE STORAGE OF MERCHANDISE IS IN HIGH-PILED
 OR RACK STORAGE ARRAYS.
  
 3) 2208.1 STORAGE RACKS. THE DESIGN, TESTING AND
 UTILIZATION OF INDUSTRIAL STEEL STORAGE RACKS SHALL BE
 IN ACCORDANCE WITH THE RMI SPECIFICATION FOR THE
 DESIGN, TESTING AND UTILIZATION OF INDUSTRIAL STEEL
 STORAGE RACKS. RACKS IN THE SCOPE OF THIS SPECIFICATION
 INCLUDE INDUSTRIAL PALLET RACKS, MOVABLE SHELF RACKS
 AND STACKER RACKS, AND DOES NOT APPLY TO OTHER TYPES OF
 RACKS, SUCH AS DRIVE-IN AND DRIVE-THROUGH RACKS,
 CANTILEVER RACKS, PORTABLE RACKS OR RACK BUILDINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-01 Cont ID  
Sent By wjolin Date 2011-09-01 Time 14:14 Rev Time 0.00
Received By wjolin Date 2011-09-01 Time 14:10 Sent To B
Notes
2011-09-01 14:13:471500 NORTH FLORIDA MANGO ROAD
 PERMIT #11080463
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: SUPPLEMENTAL HIGH-PILED RACK STORAGE INFORMATION
 SUBMITTED BY DAVID HILTON OF INTERLINE BRANDS ON
 08/31/11.
  
 FIRE SPRINKLER SYSTEM WILL MOST LIKELY NEED TO BE
 MODIFIED TO PROPERLY PROTECT THE HIGH-PILED RACK
 STORAGE. SEPARATE PLANS AND PERMIT WILL BE NEEDED FOR
 THE SPRINKLER SYSTEM MODIFICATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-18 Cont ID  
Sent By wjolin Date 2011-08-18 Time 15:22 Rev Time 0.00
Received By wjolin Date 2011-08-18 Time 15:03 Sent To  
Notes
2011-08-18 15:22:511500 NORTH FLORIDA MANGO ROAD
 PERMIT #11080463
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2006.
  
 SEVERAL DRAWING LAYERS APPEAR TO BE TURNED OFF ON THE
 LIFE SAFETY PLAN AS NO DOORS, WALLS ETC. ARE SHOWN ON
 THIS PLAN.
  
 GENERAL STORAGE SHALL ADHERE TO REQUIREMENTS OF CHAPTER
 34 OF THE FLORIDA FIRE PREVENTION CODE (NFPA 1).
  
 INDICATE THE COMMODITY CLASSIFICATIONS OF THE MATERIALS
 BEING STORED. INDICATE THE TYPE OF PALLETS TO BE USED
 FOR STORAGE. INDICATE THE CEILING/STRUCTURE HEIGHT.
  
 PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE
 NEAREST FIRE HYDRANTS AND FIRE SPRINKLER RISER.
  
 SHOW LOCATIONS OF PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-01 Cont ID  
Sent By jwitmer Date 2011-09-01 Time 15:31 Rev Time 0.00
Received By jwitmer Date 2011-08-17 Time 15:46 Sent To  
Notes
2011-08-17 15:47:17***************EXPEDITED*****************
 GAVE TO WESLEY