Plan Review Details - Permit 11080435
Plan Review Stops For Permit 11080435
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-08-29 Cont ID  
Sent By jwitmer Date 2011-08-22 Time 10:07 Rev Time 0.00
Received By jwitmer Date 2011-08-19 Time 12:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-22 Cont ID  
Sent By wjolin Date 2011-08-22 Time 10:47 Rev Time 0.00
Received By wjolin Date 2011-08-22 Time 10:06 Sent To  
Notes
2011-08-22 10:47:461 NORTH CLEMATIS STREET - SUITE #200
 PERMIT #11080435
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-1.0: IN ADDITION TO THE FIRE ALARM AND FIRE
 SPRINKLER, THE MAG LOCK DOORS SHALL UNLOCK UPON LOSS OF
 POWER CONTROLLING THE LOCKS OR LOCKING MECHANISM.
  
 SHEET LS-1.0: THE ELEVATOR LOBBY MAG LOCK SIGNAGE
 SHOULD READ PULL UNTIL ALARM SOUNDS - DOOR CAN BE
 OPENED IN 15 SECONDS. LETTERS SHALL BE AT LEAST 1-INCH
 IN HEIGHT AND 1/8-INCH STROKE. ONCE THE DOOR LOCK HAS
 BEEN RELEASED BY THE APPLICATION OF FORCE TO THE
 RELEASEING DEVICE, RELOCKING SHALL BE BY MANUAL MEANS
 ONLY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-09-06 Cont ID  
Sent By jwitmer Date 2011-09-06 Time 13:14 Rev Time 0.00
Received By jwitmer Date 2011-08-16 Time 15:10 Sent To  
Notes
2011-08-16 15:10:50DIGITAL REVIEW ROUTED TO RR.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-09-06 Cont ID  
Sent By rregueir Date 2011-09-06 Time 13:26 Rev Time 0.00
Received By rregueir Date 2011-09-06 Time 13:23 Sent To  
Notes
***NONE***