| Plan Review Stops For Permit 11080433 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2011-08-17 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-08-17 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-08-17 |
Time |
11:33 |
Sent To |
M |
|
| Notes |
| 2011-08-17 13:31:57 | 622 NORTH FLAGLER DRIVE - UNIT #802 | | | PERMIT #11080433 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | PROVIDE SPRINKLER PROTECTION FOR WALK-IN CLOSET #2868 | | | (SOUTH BEDROOM). | | | | | | NOTE: "GENERAL NOTES" ON PLAN INDICATE THIS IS AN NFPA | | | 13-RESIDENTIAL SYSTEM. THE SYSTEM SHOULD BE DESIGNED TO | | | NFPA 13 WITH THE USE OF RESIDENTIAL SPRINKLERS IN | | | DWELLING UNITS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|