Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-16 Cont ID  
Sent By wjolin Date 2011-08-16 Time 15:32 Rev Time 0.00
Received By wjolin Date 2011-08-16 Time 14:09 Sent To E
Notes
2011-08-16 15:32:121661 WORTHINGTON ROAD - SUITE #100
 PERMIT #11080425
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 VERIFY "PUSH TO EXIT" BUTTON UNLOCKS THE DOOR
 IMMEDIATELY AND DOES NOT DELAY 30 SECONDS BEFORE
 UNLOCKING THE DOOR AS INDICATED IN THE ACCESS LEGEND.
  
 CORRIDOR #101/HR #106 INDICATES A CARD READER ON BOTH
 SIDES OF THE DOOR. CARD READER SHALL NOT BE REQUIRED TO
 EXIT THIS ROOM.
  
 THE "PUSH TO EXIT" BUTTONS SHALL BE LOCATED WITH
 60-INCHES OF THE DOORS; VERIFY THIS DISTANCE IS
 POSSIBLE FOR RECEPTION #100 WHERE THE BUTTON APPEARS TO
 BE LOCATED ON A GLASS CURTAIN WALL.
  
 VERIFY MAG LOCKS DISENGAGE UPON POWER FAILURE AND WITH
 ACTIVATION OF FIRE ALARM SYSTEM AND FIRE SPRINKLER
 SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  