Plan Review Details - Permit 11080396
Plan Review Stops For Permit 11080396
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-17 Cont ID  
Sent By jgomez Date 2011-08-17 Time 13:05 Rev Time 0.00
Received By jgomez Date 2011-08-17 Time 13:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-15 Cont ID  
Sent By jgomez Date 2011-08-15 Time 11:32 Rev Time 0.00
Received By jgomez Date 2011-08-15 Time 11:13 Sent To  
Notes
2011-08-15 11:36:30RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 09-0224.01 SUBMITTED. RAS 117 CALCULATIONS REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. 1609 FBC 2007.
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT ACCORDING TO 2009
 REVISIONS THIS BUILDING IS LOCATED ON EXPOSURE "C".
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-17 Cont ID  
Sent By jgomez Date 2011-08-17 Time 13:05 Rev Time 0.00
Received By jgomez Date 2011-08-17 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-15 Cont ID  
Sent By jgomez Date 2011-08-15 Time 11:13 Rev Time 0.00
Received By jgomez Date 2011-08-15 Time 11:13 Sent To  
Notes
***NONE***