Plan Review Details - Permit 11080380
Plan Review Stops For Permit 11080380
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-09-01 Cont ID  
Sent By wjolin Date 2011-09-01 Time 10:06 Rev Time 0.00
Received By wjolin Date 2011-09-01 Time 09:34 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-08-29 Cont ID  
Sent By wjolin Date 2011-08-29 Time 12:08 Rev Time 0.00
Received By wjolin Date 2011-08-29 Time 11:58 Sent To M
Notes
2011-08-29 12:08:45120 SOUTH OLIVE AVENUE - SUITE #102
 PERMIT #11080380
 MASTER #11070603
 REVIEW #2 COMMENTS - FIRE DEPARTMENT
  
 SUITE NUMBER IN TITLEBLOCK DOES NOT MATCH THE PERMIT
 APPLICATION.
  
 HUMIDOR SPRINKLER AND TWO SPRINKLERS TO NORTH OF
 HUMIDOR ARE PROTECTING MORE THAN 130 SQUARE FEET.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-17 Cont ID  
Sent By wjolin Date 2011-08-17 Time 10:51 Rev Time 0.00
Received By wjolin Date 2011-08-17 Time 10:18 Sent To M
Notes
2011-08-17 10:51:15120 SOUTH OLIVE AVENUE - SUITE #102
 PERMIT #11080380
 MASTER #11070603
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE SUITE NUMBER IN TITLEBLOCK ADDRESS.
  
 GENERAL NOTE 1 INDICATES THE DESIGN WILL CONFORM TO
 NFPA 13R NOT NFPA 13.
  
 GENERAL NOTE 3 INDICATES ORDINARY HAZARD SPACING;
 HOWEVER, SPRINKLER COVERAGES EXCEED 130 SQUARE FEET.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-09-06 Cont ID  
Sent By hmoser Date 2011-09-06 Time 10:23 Rev Time 0.00
Received By hmoser Date 2011-08-31 Time 16:17 Sent To  
Notes
2011-08-31 16:17:52SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-31 Cont ID  
Sent By jgomez Date 2011-08-31 Time 16:15 Rev Time 0.00
Received By jgomez Date 2011-08-26 Time 15:02 Sent To  
Notes
2011-08-31 16:16:358/31/11 FIRE REVIEW DONE ON 8/29/11. JG.
2011-08-26 15:03:00TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-23 Cont ID  
Sent By hmoser Date 2011-08-23 Time 07:10 Rev Time 0.00
Received By hmoser Date 2011-08-15 Time 07:18 Sent To  
Notes
2011-08-15 07:18:56SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-09-06 Cont ID  
Sent By hmoser Date 2011-09-06 Time 10:23 Rev Time 0.00
Received By hmoser Date 2011-09-06 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-08-23 Cont ID  
Sent By hmoser Date 2011-08-23 Time 07:10 Rev Time 0.00
Received By hmoser Date 2011-08-23 Time 06:50 Sent To  
Notes
2011-08-23 07:02:19PLANS DENIED
 PROVIDE SUITE NUMBER ON TITLE BLOCK
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]