| 2011-09-03 13:32:21 | REVIEW FAILED, SEE COMMENTS FROM JIM WITMER, |
| 2011-08-09 13:25:40 | BUILDING PLAN REVIEW |
| | PERMIT: 11080126 |
| | ADD: 5400 GEORGIA AVE |
| | CONT: BLAKEMAN & ASSOCIATES |
| | TEL: (561)214-0201 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) QANITIES OF CHLORINE (2) 3000 GALLON STORAGE TANKS |
| | EXCEEDS THAT FOUND IN 2007/09 FBC-B TABLE 307.1(1) FOR |
| | . THIS BRINGS UP THE QUESTION AS TO WHAT TYPE CLASS |
| | OXIDIZER CHLORINE IS CATERIGAIZED. |
| | RETREIVING MSDS SHEETS IT IS NOTED THAT CHORINE GAS IS |
| | A STRONG FIRE PROMOTER. WHEN CONSULTING WITH THE WPB |
| | FIRE DEPAARTMENT THEY CLASSIFY CHLORINE AS A CLASS III |
| | OXIDIZER. |
| | |
| | 2) PLEASE REVIEW 2007/09 FBC-B TABLE 414.2.5(1) FOR |
| | OUTDOOR STORAGE IN CONTROL AREAS FOR CLASS III OXIDIZER |
| | ALLOWS 115 GALLONS. |
| | |
| | 3) 414.6 OUTDOOR STORAGE, DISPENSING AND USE. THE |
| | OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS |
| | MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE |
| | PREVENTION CODE . |
| | |
| | 4) [F] 414.6.1 WEATHER PROTECTION. WHERE WEATHER |
| | PROTECTION IS PROVIDED FOR SHELTERING OUTDOOR HAZARDOUS |
| | MATERIAL STORAGE OR USE AREAS, SUCH AREAS SHALL BE |
| | CONSIDERED OUTDOOR STORAGE OR USE WHEN THE WEATHER |
| | PROTECTION STRUCTURE COMPLIES WITH SECTIONS 414.6.1.1 |
| | THROUGH 414.6.1.3. NOTE THE MSDS SHEETS DO INDICATE TO |
| | KEEP THIS CHEMICAL OUT OF SUNLIGHT, PLEASE PROVIDE |
| | DOCUMENTATION ON THE TANK THAT WILL HOLD THE CHLORINE. |
| | |
| | [F] 414.6.1.1 WALLS. WALLS SHALL NOT OBSTRUCT MORE THAN |
| | ONE SIDE OF THE STRUCTURE. |
| | |
| | EXCEPTION: WALLS SHALL BE PERMITTED TO OBSTRUCT |
| | PORTIONS OF MULTIPLE SIDES OF THE STRUCTURE, PROVIDED |
| | THAT THE OBSTRUCTED AREA DOES NOT EXCEED 25 PERCENT OF |
| | THE STRUCTURE'S PERIMETER. |
| | |
| | 5) [F] 414.6.1.2 SEPARATION DISTANCE. THE DISTANCE FROM |
| | THE STRUCTURE TO BUILDINGS, LOT LINES, PUBLIC WAYS OR |
| | MEANS OF EGRESS TO A PUBLIC WAY SHALL NOT BE LESS THAN |
| | THE DISTANCE REQUIRED FOR AN OUTSIDE HAZARDOUS MATERIAL |
| | STORAGE OR USE AREA WITHOUT WEATHER PROTECTION. |
| | THE STRUCTURE IS REQUIRED TO BE LOCATED WITH RESPECT TO |
| | LOT LINES, PUBLIC WAYS, OR THE MEANS OF EGRESS TO THE |
| | PUBLIC WAY S OR THE MEANS OF EGRESS TO THE PUBLIC WAY |
| | AS REQUIRED FOR THE SPECIFIC HAZARDOUS MATERIAL |
| | PROVISIONS IN THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | [ |
| | 6) [F] 414.7 EMERGENCY ALARMS. EMERGENCY ALARMS FOR THE |
| | DETECTION AND NOTIFICATION OF AN EMERGENCY CONDITION IN |
| | GROUP H OCCUPANCIES SHALL BE PROVIDED AS SET FORTH |
| | HEREIN. |
| | |
| | [F] 414.7.1 STORAGE. AN APPROVED MANUAL EMERGENCY ALARM |
| | SYSTEM SHALL BE PROVIDED IN BUILDINGS, ROOMS OR AREAS |
| | USED FOR STORAGE OF HAZARDOUS MATERIALS. EMERGENCY |
| | ALARM-INITIATING DEVICES SHALL BE INSTALLED OUTSIDE OF |
| | EACH INTERIOR EXIT OR EXIT ACCESS DOOR OF STORAGE |
| | BUILDINGS, ROOMS OR AREAS. ACTIVATION OF AN EMERGENCY |
| | ALARM-INITIATING DEVICE SHALL SOUND A LOCAL ALARM TO |
| | ALERT OCCUPANTS OF AN EMERGENCY SITUATION INVOLVING |
| | HAZARDOUS MATERIALS. |
| | |
| | [F] 414.7.3 SUPERVISION. EMERGENCY ALARM SYSTEMS SHALL |
| | BE SUPERVISED BY AN APPROVED CENTRAL, PROPRIETARY OR |
| | REMOTE STATION SERVICE OR SHALL INITIATE AN AUDIBLE AND |
| | VISUAL SIGNAL AT A CONSTANTLY ATTENDED ON-SITE |
| | LOCATION. |
| | |
| | 7) 415.7 GROUPS H-3 AND H-4. GROUPS H-3 AND H-4 SHALL |
| | BE CONSTRUCTED IN ACCORDANCE WITH THE APPLICABLE |
| | PROVISIONS OF THIS CODE AND THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |