Plan Review Details - Permit 11080117
Plan Review Stops For Permit 11080117
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By jwitmer Date 2011-09-07 Time 11:50 Rev Time 1.33
Received By jwitmer Date 2011-09-07 Time 11:50 Sent To  
Notes
2011-09-07 11:51:43REVISION DATED: 8/17/11 15 SHEETS & 5 PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-08-17 Cont ID  
Sent By jwitmer Date 2011-08-17 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2011-08-17 Time 08:18 Sent To  
Notes
2011-08-17 09:28:06BUILDING PLAN REVIEW
 PERMIT: 11080117
 ADD: 3990 N FLAGLER
 CONT: BENCHMARK III CORP.
 TEL: (561)722-5095
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1)THIS PROVISO WAS ATTACHED TO THE FOUNDATION PERMIT.
 INSPECTOR IS TO REVIEW AAND BRING IN A SIGNED SEALED
 SOILS REPORT AT TIME OF FOUNDATION INSPECTION. THIS
 PLAN IS FOR A NEW BUILDING PLEASE PROVIDE SOILS REPORT
 FOR THE SAFE MINIMUM SOIL BEARING VALUES. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN
 THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS
 OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 2) THIS PROVISO WAS ATTACHED TO THE FOUNDATION PERMIT.
 THE NEW FOUNDATION PLANS DO SHOW WHAT FINISH SLAB
 ELEVATION 100 IS REFRENECED TOO IN NGVD. THIS BUILDING
 IS IN A A- 5 FLOOD ZONE. THE BASE FLOOD ELEVATION FOR
 FINISH FLOOR IS 7.5 NGVD. SHEET AS-101 INDICATES A
 FINISH FLOOR ELEVATION OF 100.00' BUT THERE IS NO
 REFERENCE TO WHAT 100.00' IS EQUAL TO?
  
 3A)FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 EXTERIOR DOORS GLAZED OR SOLID SINGLE AND DOUBLE
 WINDOWS W/ LARGE MISSILE IMPACT
 WALL LOUVERS
 ROOFING ASSEMBLIES, STANDING SEAM METAL ROOF, PLEASE
 NOTE PLANS INDICATE THE USE OF A SELF-ADHERED MEMBRANE,
 MUST COMPLY WITH PRODUCT APPROVAL IF A NAILABLE
 SUBSHEET IS
 REQUIRED.
  
 3B) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) NO TRUSS ENGINEERING PACKAGE HAS BEEN SUBMITTED,
 CONTRACTOR IS WORKING AT OWN RISK, SINCE THE MAGNITUDE
 OF GRAVITY, UPLIFT OR LATERAL LOADS HAS NOT BEEN
 PROVIDED BY TRUSS ENGINEER, THE DESIGNER OF RECORD IS
 TO REVIEW & STAMP ENGINEERING BEFORE TRUSS ENGINEERING
 IS SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-09-06 Cont ID  
Sent By rlecky Date 2011-09-06 Time 12:03 Rev Time 0.00
Received By rlecky Date 2011-09-06 Time 12:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2011-08-30 Cont ID  
Sent By rlecky Date 2011-08-23 Time 11:27 Rev Time 0.00
Received By lmartine Date 2011-08-22 Time 09:44 Sent To  
Notes
2011-08-30 16:53:58PER DOUG, BY-PASS AND ASSIGN NEW STOP AFTER ISSUEING
 STRUCTURE ONLY.
2011-08-23 11:29:14NEW MAINTENANCE BUILDING #11080117
 3990 N. FLAGLER DR.
  
 GENERAL PURPOSE RECEPTACLES LOCATED OUTDOORS, IN
 BATHROOMS AND ALL MAINTENANCE AREAS REQUIRE GFCI
 PROTECTION. NEC 210.8
 PLEASE PROVIDE THE FEEDER SIZES FOR PANEL BOARDS MC AND
 MD. INDICATE ON THE SITE ELECTRICAL PLAN WHERE PANEL
 BOARDS MC AND MD ARE LOCATED. NEC 215.5
 FEEDER TO TRANSFORMER MB IS APPEARS TO BE UNDERSIZED.
 NEC T. 310.16
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-08 Cont ID  
Sent By wjolin Date 2011-09-08 Time 13:40 Rev Time 0.00
Received By wjolin Date 2011-09-08 Time 13:32 Sent To  
Notes
2011-09-08 13:40:533990 NORTH FLAGLER DRIVE - MAINTENANCE BUILDING
 PERMIT #11080117
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: CIVIL SITE DRAWINGS WILL BE SUBMITTED AS SEPARATE
 PACKAGE.
  
 *****PROVISO*****
  
 IDLE PALLETS SHALL BE STORED OUTSIDE OR IN A SEPARATE
 BUILDING DESIGNED FOR PALLET STORAGE. INDOOR STORAGE OF
 PALLETS IS PERMITTED IF THE BUILDING IS PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. OUTDOOR PALLETS SHALL BE
 LOCATED AT LEAST 20 FEET FROM BUILDINGS.
  
 STORAGE MORE THAN 12 FEET IN HEIGHT OR STORAGE LOCATED
 WITHIN THE ATTIC SPACE REQUIRES THE BUILDING TO BE
 PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-12 Cont ID  
Sent By wjolin Date 2011-08-12 Time 13:23 Rev Time 0.00
Received By wjolin Date 2011-08-12 Time 13:03 Sent To  
Notes
2011-08-12 13:23:353990 NORTH FLAGLER DRIVE - MAINTENANCE BUILDING
 PERMIT #11080117
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: CIVIL SITE DRAWINGS WILL BE SUBMITTED AS SEPARATE
 PACKAGE.
  
 *****PROVISO*****
  
 NO ADDRESS PROVIDED IN TITLEBLOCK.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 PROVIDE EQUIPMENT AND STORAGE LAYOUT PLAN. INDICATE
 WHAT MATERIALS WILL BE STORED, THE APPROXIMATE
 QUANTITIES AND HOW THE MATERIALS WILL BE STORED (PILED,
 RACK, PALLET ETC.). INDICATE IF ANY FLAMMABLE OR
 COMBUSTIBLE LIQUIDS OR GASES WILL BE STORED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2011-09-06 Time 11:23 Sent To  
Notes
2011-09-06 11:23:07C29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-30 Cont ID  
Sent By hmoser Date 2011-08-30 Time 16:46 Rev Time 0.00
Received By hmoser Date 2011-08-04 Time 15:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-08-30 Cont ID  
Sent By jwitmer Date 2011-08-30 Time 16:21 Rev Time 0.00
Received By jwitmer Date 2011-08-30 Time 16:21 Sent To  
Notes
2011-08-30 16:22:51IMPACT FEE PLAN REVIEW # 2011-15450
 AMOUNT: $ 15,199.85

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-08-17 Cont ID  
Sent By jwitmer Date 2011-08-17 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2011-08-17 Time 08:08 Sent To  
Notes
2011-08-17 08:08:58BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-30 Cont ID  
Sent By hmoser Date 2011-08-30 Time 16:46 Rev Time 0.00
Received By hmoser Date 2011-08-30 Time 16:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2011-09-07 Cont ID  
Sent By lwagner Date 2011-09-07 Time 13:48 Rev Time 0.00
Received By lwagner Date 2011-09-07 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-09-07 Cont ID  
Sent By lwagner Date 2011-09-07 Time 09:28 Rev Time 0.00
Received By lwagner Date 2011-09-07 Time 09:28 Sent To  
Notes
2011-09-07 09:26:48FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. PLUMBING PLANS DO NOT SHOW THE REQUIRED DRINKING
 FOUNTAIN AND SERVICE SINK. SEE APPROVED FOUNDATION
 PLANS.
 FBC 403.1 (4)& (8)
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2011-08-30 Cont ID  
Sent By lwagner Date 2011-08-22 Time 12:38 Rev Time 0.00
Received By lmartine Date 2011-08-30 Time 16:50 Sent To  
Notes
2011-08-30 16:52:03PER DOUG, BY-PASS AND ASSIGN NEW STOP AFTER ISSUING
 STRUCTURE ONLY.
2011-08-22 12:38:05FBC PLUMBING REVIEW #1
 DENIED:
  
 1. PLUMBING PLANS DO NOT SHOW THE REQUIRED DRINKING
 FOUNTAIN AND SERVICE SINK.
 FBC 403.1 (4)& (8)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-08-26 Cont ID  
Sent By jroach Date 2011-08-26 Time 13:43 Rev Time 0.00
Received By jroach Date 2011-08-26 Time 13:43 Sent To  
Notes
2011-08-26 13:44:10ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.26.2011
 PERMIT NO.: 11080117
 ADDRESS: 3990 NORTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: JEFFREY L. SLADE
 TELEPHONE NO.: 954.764.6550
 SCOPE OF REVIEW: NEW MAINTENANCE BUILDING.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THIS PLAN REVIEW IS PASSED ONLY FOR AN AT RISK
 PERMIT. ALL DEVELOPMENT IS SUBJECT TO THE APPROVAL OF
 RESOLUTION NO. 191-11 BY THE CITY COMMISSION OF THE
 CITY OF WEST PALM BEACH. FAILURE TO OBTAIN SUCH
 APPROVAL WILL REQUIRE THAT ALL DEVELOPMENT CONSTRUCTED
 UNDER THIS PERMIT SHALL BE REMOVED AND THE SITE
 RETURNED TO ITS ?PRE-PERMIT STATE?.
  
 2. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 SEPARATE PERMITS SHALL BE OBTAINED FOR ALL SITE-RELATED
 WORK, INCLUDING LANDSCAPING, PAVEMENT, ETC.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM