Plan Review Details - Permit 11080112
Plan Review Stops For Permit 11080112
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-08-17 Cont ID  
Sent By jwitmer Date 2011-08-17 Time 12:18 Rev Time 0.55
Received By jwitmer Date 2011-08-17 Time 12:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-08-15 Cont ID  
Sent By rlecky Date 2011-08-15 Time 10:55 Rev Time 0.00
Received By rlecky Date 2011-08-15 Time 10:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-10 Cont ID  
Sent By wjolin Date 2011-08-10 Time 09:35 Rev Time 0.00
Received By wjolin Date 2011-08-10 Time 08:49 Sent To  
Notes
2011-08-10 09:13:582471 OKEECHOBEE BOULEVARD - SUITE HM
 PERMIT #11080112
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: THIS PERMIT IS FOR PREPARATION OF SHELL SPACE
 ONLY. SEPARATE PLANS AND PERMIT ARE NEEDED FOR THE
 TENANT BEFORE OCCUPANCY WILL BE ALLOWED.
  
  
 *****PROVISO*****
  
 NO ADDRESS PROVIDED IN TITLEBLOCK.
  
 FIRE-RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE/SMOKE BARRIER?PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE
 SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE - NFPA
 101.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-23 Cont ID  
Sent By hmoser Date 2011-08-23 Time 15:29 Rev Time 0.00
Received By hmoser Date 2011-08-05 Time 13:18 Sent To  
Notes
2011-08-05 13:18:51SENT TO B19 SHELF FOR ALL TRADES REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-23 Cont ID  
Sent By hmoser Date 2011-08-23 Time 15:29 Rev Time 0.00
Received By hmoser Date 2011-08-23 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-08-10 Cont ID  
Sent By lwagner Date 2011-08-10 Time 12:10 Rev Time 0.00
Received By lwagner Date 2011-08-10 Time 11:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2011-08-18 Cont ID  
Sent By lfranco Date 2011-08-18 Time 15:41 Rev Time 0.50
Received By lfranco Date 2011-08-18 Time 15:41 Sent To  
Notes
2011-08-18 15:43:52PLANNING AND ZONING: *** PASSED, ZONING REVIEW NOT
 REQUIRED: INTERIOR WORK ONLY AND THE VALUE OF PROPOSED
 WORK DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. ****
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved