| Plan Review Stops For Permit 11080035 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2011-09-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-09-06 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-09-06 |
Time |
11:19 |
Sent To |
FIRE |
|
| Notes |
| 2011-09-06 11:21:19 | NOTE: SEPERATE PERMIT REQUIRED FOR RESIDENTIAL SMOKE | | | AND CARBON MONOXIDE DETECTORS. FBC R313 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2011-09-06 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-09-06 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-09-06 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2011-09-06 10:44:15 | PENDING NEW PLAN WITH RESPONSE TO FIRE DEPARTMENT | | | COMMENTS. RESIDENTIAL SMOKE AND CARBON MONOXIDE ALARMS | | | WILL REQUIRE A SEPERATE PERMIT IF NOT INCLUDED WITH | | | THIS APPLICATION. | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2011-08-04 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-08-04 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-08-04 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2011-08-04 11:49:35 | CARBON MONOXIDE ALARM REQUIRED OUT SIDE EACH SLEEPING | | | AREA. FBC R313 | | | THIS PERMIT APPEARS TO BE SUPPORTING A BUSINESS | | | ACTIVITY " ELITE CARE FACILITY" REQUIRING A CERTIFICATE | | | OF USE. ALL BUSINESSES MUST BE REGISTERED WITH WPB. | | | CODE OF ORDNANCES CHAPTER 22 SEC. 22.32 | | | CHANGE OF OCCUPANCY PERMIT REQUIRED FOR BUSINSESS USE | | | IN A RESIDENTIAL OCCUPANCY. FBC 105.1 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2011-09-08 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-09-08 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-09-08 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2011-08-30 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-08-30 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-08-30 |
Time |
11:09 |
Sent To |
E |
|
| Notes |
| 2011-08-30 11:24:57 | 3840 HAMILTON KEY | | | PERMIT #11080035 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE PERMIT APPLICATION INDICATES THIS WILL BE A CLASS A | | | ADDRESSABLE SYSTEM; HOWEVER, THE EQUIPMENT PRODUCT DATA | | | INDICATES THIS WILL BE A CONVENTIONAL NON-ADDRESSABLE | | | SYSTEM. | | | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBER TO EACH | | | FIRE ALARM DEVICE ON THE SYSTEM. | | | | | | DRAWINGS DO NOT REQUIRE ENGINEER?S SIGN/SEAL, BUT DO | | | REQUIRE A NAME AND SIGNATURE FROM THE PERSON | | | RESPONSIBLE FOR THE DESIGN. | | | | | | NO NOTIFICATION APPLIANCES LOCATED IN FAMILY ROOM. | | | | | | MINI-HORN DEVICE NOT INDICATED IN SYMBOLS LEGEND. | | | | | | VISUAL NOTIFICATION DOES NOT APPEAR TO BE PROVIDED IN | | | BEDROOMS #1, #2 OR #3. | | | | | | WIRE SIZE NOT INDICATED ON PLANS. | | | | | | BATTERY CALCULATIONS DO NOT INDICATE WHAT SIZE BATTERY | | | WILL BE PROVIDED. | | | | | | NOTE 1: FIRE SPRINKLER FLOW SWITCH AND TAMPER SWITCH | | | LOCATIONS TO BE DETERMINED; ADD DEVICES TO FIRE ALARM | | | SCOPE WHEN AVAILABLE. | | | | | | NOTE 2: SEPARATE PERMITS WILL BE REQUIRED FOR THE FIRE | | | SPRINKLER SYSTEM AND THE SMOKE ALARMS/CARBON MONOXIDE | | | DETECTORS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2011-08-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
ddaniels |
Date |
2011-08-03 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2011-08-03 10:05:55 | 08/03/2011 PLANS REVIEWED BY FIRE **DENIED** | | | | | | 1. NOT ENOUGH INFORMATION ON PLANS | | | 2. SHOW TYPE OF OCCUPANCY | | | 3. SHOW SCOPE OF WORK | | | 4. LEGEND NEEDS TO MATCH PLANS | | | | | | DERRICK DANIELS, BATTALION CHIEF | | | FIRE PLANS REVIEW | | | 561 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-09-08 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-09-08 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-08-30 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2011-08-30 10:38:50 | INCOMING SENT TO FIRE BOX. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-08-04 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-08-04 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-08-02 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2011-08-02 14:40:06 | TO FIRE BOX |
|
|