Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-09 Cont ID  
Sent By wjolin Date 2011-08-09 Time 13:11 Rev Time 0.00
Received By wjolin Date 2011-08-09 Time 12:44 Sent To  
Notes
2011-08-09 13:11:104310 BROADWAY
 PERMIT #11080025
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE
 EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM
 OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE
 SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL
 CLEARLY IDENTIFY THE HAZARD PROTECTED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  