Plan Review Details - Permit 11070709
Plan Review Stops For Permit 11070709
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By jwitmer Date 2011-09-07 Time 14:22 Rev Time 1.00
Received By jwitmer Date 2011-09-07 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-11 Cont ID  
Sent By jwitmer Date 2011-08-11 Time 09:53 Rev Time 2.22
Received By jwitmer Date 2011-08-10 Time 11:00 Sent To  
Notes
2011-08-11 10:31:09BUILDING PLAN REVIEW
 PERMIT: 11070709
 ADD:7900 S DIXIE
 CONT: MONTEIRO DEVELOPMENT
 TEL: (561)346-6916
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLEASE REVIEW SITE PLAN THE ACCESSIBLE RAMP LOCATED
 ACROSS FROM THE ACCESSIBLE PARKING SPACES. REVIEW
 SECTION: 2007 FBC-B 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM
 OF EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE. BOTTOM LANDING IS INDICATED AS 5FOOT
 WIDE.
  
 1B) AT THE ACCESSIBLE PARKINGSPACES THE ACCESS AISLE
 DOES INDICATE THE USE OF DETECTABLE SURFACES BUT FROM
 THE BUILDING AT THE BOTTOM OF THE RAMP LANDING NO
 DETECTABLE WARNING
 SURFACES ARE INDICATED. 11-4.29.2.
  
 2A) SHEET A3 INDICATES TTHE USE OF ROOF SCUPPERS AND
 SECONDARY OVER FLOW SCUPPRES BUT NO SIZE IS PROVIDED.
 1504.3.2 & 1504.3.3..
  
 2B) THE UPPER ROOF DOES DUMP THE RAIN WATER ONTO THE
 LOWER ROOF SECTION PLEASE PROVIDE THE TOTAL AREA OF
 BOTH ROOFS IN ROOFING CALCULATION FOR THE LOWER ROOF
 PORTION.1504.3.3
  
 2C) THE RAIN LEADERS ARE NO CLEAR AS TO WHERE THEY STOP
 TO DRAIN ABOVE AND OVER THE SIDE WALK, OR BELOW THE
 SIDE WALK ENDING WHERE? 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 3) SHEET A2 DOES INDICATE A NEW COOLER AND EXTERIOR
 FREEZER. COOLERS AND FREEZERS ARE NOT COVERED UNDER
 THIS PERMIT REQUIRING SEPERATE PERMITS PLANS REVIEWS
 AND ASSOCIATED FEES.
 COOLERS AND FREEZERS WILL NEED TO COMPLY WITH 2007
 FBC-B 2603.4.1.2 & 2603.4.1.3. PLEASE BE AWARE THAT
 EXTERIOR FREEZERS AND OR COOLERS WILL ALSO NEED TO
 PROVIDE PRODUCT APPROVALS INDICATING COMPLIANCE WITH
 140 MPH WIND ZONE. RULE 9N-3(31)(G).
  
 4) SHEET P1 INDICATES ROOF TOP REMOTE CONDENSING UNITS
 ATTACHED TO 4X4 WOOD SLEEPRES, PLEASE REVIEW 2007 FBC-B
 SECTION 1509.7 AND TABLE 1509.7.
  
 5) THE PRODUCT APPROVALS SUBMITTED FOR REVIEW (WINDOWS
 & DOORS) ONLY ONE SEET OF APPROVALS WERE SUBMITTED, THE
 BUILDING DEPARTMENT REQUIRES TWO SETS ONE FOR THE FIELD
 AND ONE FOR RECORD RETENTION. 106.3.1.
  
 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIE OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 6A) ROOFING ASSEMBLIES
 6B) PREMANUFACTURED A/C ROOF TOP STANDS
 6C) EXTERIOR FREEZERS-UNDER SEPERATE PERMIT
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-08-15 Cont ID  
Sent By rlecky Date 2011-08-15 Time 10:23 Rev Time 0.00
Received By rlecky Date 2011-08-15 Time 10:07 Sent To  
Notes
2011-08-15 10:24:06STAMPED ONE SET. ZONING HAVE THE OTHER SET. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2011-08-04 Cont ID  
Sent By wjolin Date 2011-08-04 Time 14:32 Rev Time 0.00
Received By wjolin Date 2011-08-04 Time 14:04 Sent To  
Notes
2011-08-04 14:31:537900 SOUTH DIXIE HIGHWAY
 PERMIT #11070709
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-09-07 Cont ID  
Sent By jwitmer Date 2011-09-07 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2011-08-26 Time 13:58 Sent To  
Notes
2011-08-26 13:59:48C5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-23 Cont ID  
Sent By lmartine Date 2011-08-23 Time 10:00 Rev Time 0.00
Received By lmartine Date 2011-07-28 Time 11:18 Sent To  
Notes
2011-07-28 11:18:36SENT TO C5 SHELF FOR ALL TRADES REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2011-09-06 Cont ID  
Sent By hmoser Date 2011-09-06 Time 12:19 Rev Time 0.00
Received By hmoser Date 2011-09-06 Time 12:19 Sent To  
Notes
2011-09-06 12:23:27SEPARATE PERMITS REQUIRED FOR WALK IN FREEZER AND
 COOLER.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-08-31 Cont ID  
Sent By hmoser Date 2011-08-31 Time 17:03 Rev Time 0.00
Received By hmoser Date 2011-08-31 Time 17:03 Sent To  
Notes
2011-08-31 17:07:50PLANS DENIED
 FREEZER WIND LOAD CALCULATIONS DO NOT MEAT 140 MPH.
 PLANS MUST BE STAMPED BY A ENGINEER.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-08-22 Cont ID  
Sent By hmoser Date 2011-08-22 Time 07:32 Rev Time 0.00
Received By hmoser Date 2011-08-16 Time 12:49 Sent To  
Notes
2011-08-22 07:32:06PLANS DENIED
 PROVIDE MODEL NUMBER OF 10 TON RTU ON EQUIPMENT
 SCHEDULE.
 PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO ROOF
 TIE DOWN,
 AND THE UNIT TO CURB TIE DOWN.PER SECTION 301.12 WIND
 RESISTANCE. FBC(M) 2007
 PROVIDE A DETAIL ON THE CONDENSER STANDS TO ROOF TIE
 DOWN, AND
 UNIT TO STAND TIE DOWN.PER SECTION 301.12 WIND
 RESISTANCE FBC (M) 2007
 PROVIDE A DETAIL ON THE PLANS FOR THE CONDENSATE
 DISPOSAL FOR THE RTU , COOLER AND FREEZER.
 PER SECTION 307.2 CONDENSATE DISPOSAL.FBC (M) 2007
 ON PAGE P-1 HAS THE DETAIL FOR THE REMOTE CONDENSER AND
 REFRIGERANT LINES .
 PLEASE MOVE TO THE MECHANICAL PAGES.
 PROVIDE SUBTITLES FOR COOLER AND FREEZER. SECTION
 106.3.3 2007 FBC.
 PROVIDE WIND LOAD CALCULATIONS FOR WALK IN FREEZER
 301.12 FBC (M) 2007
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-08-31 Cont ID  
Sent By lwagner Date 2011-08-31 Time 11:02 Rev Time 0.00
Received By lwagner Date 2011-08-31 Time 10:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-08-17 Cont ID  
Sent By lwagner Date 2011-08-17 Time 09:08 Rev Time 0.00
Received By lwagner Date 2011-08-05 Time 14:03 Sent To  
Notes
2011-08-05 15:50:53FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 SHEET AM2 :
 1. GREASE INTERCEPTOR REQUIRED
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR
 AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS,
 SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS.
 FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS,
 PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK
 STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE
 DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS
 WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED.
  
 2. PLEASE ADVISE AS TO THE PURPOSE OF THE BOWL SINK IN
 THE FRONT AREA AND THE FLOOR DRAIN IN THE BACK OPEN
 AREA. IF THEY RECEIVE FATS, OILS, OR GREASE THEY ARE
 REQUIRED TO BE CONNECTED TO A GREASE INTERCEPTOR.
  
 3. THE F8 DRAIN SHOWN ON P-1 FOR THE 2C ICE BIN IS NOT
 SHOWN CONNECTED TO THE DRAINAGE ON THE ISO. OR FLAT
 SANITARY DRAWING.
  
 SHEET P-1
  
 4. WATER SUPPLY FOR 3E1 IS NOT SHOWN ON SHEET AM2
  
 NOTE
 1. 608.16.1 BEVERAGE DISPENSERS. THE WATER SUPPLY
 CONNECTION TO BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022, CSA B64.3.1 OR BY AN AIR GAP. THE BACKFLOW
 PREVENTER DEVICE AND THE PIPING DOWNSTREAM THEREFROM
 SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS.
  
 2. SHEET A1 SHOWS AN OLD GREASE TRAP . THIS WILL BE
 REQUIRED TO BE PROPERLY ABANDONED OR INSPECTED FOR
 USABILITY IF USED WITH THE NEW OCCUPANCY.

Review Stop Z ZONING
Rev No 2 Status P Date 2011-09-05 Cont ID  
Sent By eschneid Date 2011-09-05 Time 09:33 Rev Time 0.50
Received By eschneid Date 2011-09-05 Time 09:33 Sent To  
Notes
2011-09-05 09:58:08PASSED
  
 1) THE FOLLOWING PERMITS ARE REQUIRED TO BE APPROVED,
 INSTALLED AND PASS FINAL INSPECTION PRIOR TO C.O. OF
 THE BUILDING:
  
 A. A LANDSCAPE PERMIT THROUGH THE CONSTRUCTION SERVICES
 DEPARTMENT.
 B. A PARKING LOT/STRIPPING PERMIT THROUGH THE
 ENGINEERING SERVICES DEPARTMENT.
 C. A RIGHT-OF-WAY PERMIT FROM FDOT FOR MODIFICATIONS TO
 THE SOUTH DIXIE HIGHWAY DRIVEWAYS AND A RIGHT-OF-WAY
 PERMIT FROM THE CITY FOR THE CLOSURE OF THE BREVARD
 AVENUE DRIVEWAYS.
 D. A FENCE PERMIT FOR THE DUMPSTER ENCLOSURE THROUGH
 THE CONSTRUCTION SERVICES DEPARTMENT.
 E. A SIGN(S) PERMIT, INCLUDING THE MENU BOARD THROUGH
 THE CONSTRUCTION SERVICES DEPARTMENT.
 F. A SITE LIGHTING PERMIT THROUGH THE CONSTRUCTION
 SERVICES DEPARTMENT.
 G. A TREE ALTERATION PERMIT FOR ANY REMOVED AND
 RELOCATED TREES THROUGH THE PLANNING AND ZONING
 DEPARTMENT.
 H. AN IRRIGATION PERMIT IS THROUGH THE CONSTRUCTION
 SERVICES DEPARTMENT.
 I. AN AWNING PERMIT THROUGH THE CONSTRUCTION SERVICES
 DEPARTMENT
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2011-08-17 Cont ID  
Sent By eschneid Date 2011-08-17 Time 16:32 Rev Time 8.00
Received By eschneid Date 2011-08-17 Time 16:32 Sent To  
Notes
2011-08-17 16:45:21FAILED
  
 PLEASE PROVIDE COMMENT RESPONSES IN WRITING.
  
 PLEASE NOTE THAT THE PROVISION OF THE REQUIRED
 ADDITIONAL INFORMATION AND UPDATED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 1) A RECENT SURVEY, LESS THAN ONE YEAR OLD, IS
 REQUIRED. THE SURVEY SHALL SHOW EXISTING UTILITIES,
 INCLUDING THE POWER POLES AND THE BACK FLOW PREVENTER;
 THE EXISTING ON-SITE TREES; THE OFF-SITE LIGHT POSTS ON
 SOUTH DIXIE HIGHWAY, BREVARD AVENUE AND THE PROPERTY TO
 THE SOUTH; THE NEIGHBORING RETAINING WALL; THE SOUTH
 WALL OF THE BUILDING TO THE NORTH, INCLUDING THE ROOF
 DRAINS; AND OFF-SITE UTILITIES ADJACENT TO THE PROPERTY
 (EX. OVERHEAD WIRES).
  
 2) THE FOLLOWING ADDITIONAL PERMITS REQUIRING ZONING
 REVIEW ARE NEEDED:
  
 A. A LANDSCAPE PERMIT THROUGH THE CONSTRUCTION SERVICES
 DEPARTMENT.
 B. A PARKING LOT/STRIPPING PERMIT THROUGH THE
 ENGINEERING SERVICES DEPARTMENT.
 C. A RIGHT-OF-WAY PERMIT FROM FDOT FOR MODIFICATIONS TO
 THE SOUTH DIXIE HIGHWAY DRIVEWAYS AND A RIGHT-OF-WAY
 PERMIT FROM THE CITY FOR THE CLOSURE OF THE BREVARD
 AVENUE DRIVEWAYS.
 D. A FENCE PERMIT FOR THE DUMPSTER ENCLOSURE THROUGH
 THE CONSTRUCTION SERVICES DEPARTMENT.
 E. A SIGN(S) PERMIT, INCLUDING THE MENU BOARD THROUGH
 THE CONSTRUCTION SERVICES DEPARTMENT.
 F. A SITE LIGHTING PERMIT THROUGH THE CONSTRUCTION
 SERVICES DEPARTMENT.
 G. A TREE ALTERATION PERMIT FOR ANY REMOVED AND
 RELOCATED TREES THROUGH THE PLANNING AND ZONING
 DEPARTMENT.
  
 3) THE LANDSCAPE AND PARKING LOT/STRIPING PERMITS SHALL
 BE SUBMITTED PRIOR TO ZONING APPROVAL OF THE RENOVATION
 PERMIT.
  
 4) THERE ARE A NUMBER OF DISCREPANCIES AMONG THE
 VARIOUS PLAN SHEETS. ALL PLANS SHALL SHOW THE SAME
 CONDITIONS. SOME EXAMPLES ARE LISTED BELOW:
  
 A. SHEET C-1 SHOWS THE SOUTHERN DRIVEWAY AS 19 FEET 10
 INCHES WIDE WITH A 7 FEET 3 INCH WIDE SIDEWALK, WHILE
 SHEET A-1 SHOWS THE RESPECTIVE DIMENSIONS AT 20 FEET 2
 INCHES AND 7 FEET.
 B. SHEET C-1 SHOWS A DIFFERENT ENTRY DRIVE CONDITION
 THAN SHEETS A-1 AND LP-1.
 C. SHEET C-1 SHOWS DIFFERENT DIMENSIONS NORTH OF THE
 BUILDING THAN SHEETS A-1 AND L-1.
 D. SHEET LP-1 SHOWS A DIFFERENT SOUTH LANDSCAPE BUFFER
 CONDITION THAN SHEETS A-1 AND C-1.
 E. SHEET A-4 SHOWS A DIFFERENT PARKING SPACE/BIKE
 RACK/WALKWAY CONDITION THEN SHEETS A-1, C-1 AND LP-1.
 F. SHEET C-1 SHOWS A DIFFERENT RAMP WIDTH AT THE COOLER
 THAN SHEETS A-1, A-4 AND LP-1.
 G. SHEETS A-3 AND A-4 SHOW A BOLLARD ADJACENT TO THE
 DRIVE THRU WINDOW WHICH IS NOT SHOWN ON SHEETS A-1, C-1
 AND LP-1.
  
 5) NO PARKING DETAIL WAS PROVIDED FOR THE 90 DEGREE
 PARKING SPACES.
  
 6) SHOW THE ROOFTOP EQUIPMENT ON THE ELEVATIONS.
  
 7) CLARIFY ON THE PLANS WHAT THE FINAL DISPOSITION OF
 THE 2 EXISTING LIGHT POLES AND THE EXISTING LIGHT POLE
 BASE WILL BE. ARE THEY BEING REPLACED, REMOVED, OR
 RELOCATED? ALL SIGHT LIGHTING SHALL BE SHOWN ON THE
 SITE, CIVIL AND LANDSCAPE PLANS. PLEASE NOTE THAT SIGHT
 LIGHTING SHALL NOT INTERFERE WITH LANDSCAPE. THE LIGHTS
 POST AND LIGHT POST BASE WOULD CONFLICT WITH THE
 PROPOSED TREES.
  
 8) A FULL REVIEW OF THE LANDSCAPE PLANS WILL BE
 COMPLETED AT THE TIME OF LANDSCAPE PERMIT SUBMITTAL.
 STAFF BEGAN A COMPLIMENTARY REVIEW OF THE SUBMITTED
 LANDSCAPE PLAN, BUT DUE TO THE AMOUNT OF INITIAL
 COMMENTS, STAFF SUGGESTS A MEETING WITH THE LANDSCAPE
 ARCHITECT TO DISCUSS. PLEASE SEE THE INITIAL COMMENTS
 LISTED BELOW:
  
 A. THE SOUTH BUFFER DOES NOT HAVE 5 FEET BETWEEN THE
 ADA PARKING SPACES AND THE SOUTH PROPERTY LINE. THE 5
 FOOT DIMENSION IS TAKEN FROM THE FRONT OF THE REGULAR
 PARKING SPACES.
 B. THE LANDSCAPE PLAN SHALL SHOW OFF-SITE TREES TO
 VERIFY THAT THERE ARE NO CONFLICTS WITH THE PROPOSED
 TREES.
 C. THE PROPOSED TREES SHALL BE SIZED TO THE PROPOSED
 PLANTING AREAS FOR ADEQUATE LONG TERM GROWTH. THE
 MAJORITY OF THE LIVE OAK TREES SHALL BE REPLACES WITH A
 SPECIES THAT IS APPROPRIATE WITH THE 5 FOOT WIDE
 PLANTING AREAS. POSSIBILITIES ARE CRAPE MYRTLE,
 TIBOUCHINA, SILVER BUTTONWOOD, PINK TAB, CASSIA, OR
 ORANGE GEIGER.
 D. THERE IS ONE TOO MANY DOTS SHOWN TO REPRESENT THE
 LISTED NUMBER OF SABAL PALM TREES ON THE PLAN.
 E. THE WEST PROPERTY LINE CONTAINS 125 FEET OF
 FRONTAGE, WHICH REQUIRES 5 TREES NOT 4 AS SHOWN.
 F. PER TABLE XIV-1, TREES SHALL BE PLANTED AT 30 FOOT
 INTERVALS IN THE EAST, SOUTH AND WEST LANDSCAPE BUFFERS
 AND HEDGES SHALL BE PLANTED AT 2 FOOT INTERVALS. THE
 ALL TREES, EXCEPT THE 2 TREES CREATING A GATEWAY FOR
 THE PEDESTRIAN PATH ARE PLANTED TOO FAR APART. NO
 DETAILS ARE PROVIDED FOR THE SHRUBS, BUT THERE ARE
 AREAS ALONG THE WEST PROPERTY LINE WHERE NO HEDGE IS
 SHOWN WITHIN THE REQUIRED 5 FOOT BUFFER.
 G. A TERMINAL ISLAND TREE IS NOT BEING PROVIDED FOR THE
 2 ANGLED SPACES BY THE DRIVE THRU.
 H. THE XERISCAPE TABLE IS NOT ACCURATELY TABULATED. FOR
 EXAMPLE, THE ST. AUGUSTINE GRASS PROPOSED IS NOT A
 DROUGHT TOLERANT AND THUS MAY NOT COUNT AS MEETING 51+
 % OF DROUGHT TOLERANT GRASS.
 I. THERE IS NO TURF ALONG SOUTH DIXIE HIGHWAY AS SHOWN
 ON THE LANDSCAPE PLANS.
 J. THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRE
 THAT SOD AND IRRIGATION BE PROVIDED IN ADJACENT
 RIGHTS-OF-WAY. THE TURF AREA ADJACENT TO THE SITE
 WITHIN THE BREVARD AVENUE RIGHT-OF-WAY SHALL HAVE
 IRRIGATION PROVIDED AND SHALL BE REPLACED WITH NEW SOD
 IF THE EXISTING TURF IS DEAD OR WEED INFESTED. A NOTE
 STATING THAT SOD AND IRRIGATION IS TO BE PROVIDED SHALL
 BE ON THE LANDSCAPE PLANS.
 K. THE HEIGHT OF THE SABAL PALMS ALONG THE NORTH
 PROPERTY LINE SHALL BE SPECIFIED SO THAT THE CROWN
 EXCEEDS THE DRIPLINE OF THE EXISTING BUILDING -
 POSSIBLY 12-14 FEET AT INSTALLATION.
 L. THE TREE SPECIFICATION (HEIGHT TO CALIPER) DOES NOT
 SEEM TO BE REALISTIC AS A FLORIDA GRADE NO. 1.
 M. THE NUMBER OF SHRUBS AND TREES FOR A SITE ARE
 CALCULATED USING OPEN SPACE NOT LANDSCAPE AREA. THE
 LANDSCAPE REQUIREMENT TABLE SHALL BE REVISED WITH THE
 CORRECT BASE INFORMATION AND THE CALCULATIONS FOR EACH
 REQUIREMENT SHALL BE SHOWN. EX. OPEN SPACE/1,600 = X
 REQUIRED TREES.
 N. THE INTERIOR PARKING AREA LANDSCAPE REQUIREMENTS ARE
 NOT SHOWN.
 O. COMPLIANCE WITH THE REQUIRED 30% FOUNDATION PLANTING
 IS NOT SHOWN.
 P. STAFF SUGGESTS INCORPORATING VERTICAL ELEMENTS INTO
 THE FOUNDATION PLANTING.
 Q. THE BASE OF THE SIGN SHOULD INCLUDE GROUND COVER.
  
 9) THE PLANS SHALL STATE THAT THE PARKING SPACES ARE AT
 A 45% ANGLE.
  
 10) BICYCLE RACK DETAILS ARE REQUIRED. THIS INCLUDES
 THE STYLE OF BICYCLE RACK AND ITS LOCATION ON THE PAD,
 WITH DIMENSIONS. PLEASE NOTE THAT THE WAVE STYLE RACK
 IS NOT PERMITTED IN THE CITY.
  
 11) THE BICYCLE RACK SHALL BE ORIENTED SO THAT BICYCLES
 PARK IN A NORTH/SOUTH ORIENTATION, NOT EAST WEST AS
 SHOWN ON THE PLAN.
  
 12) IN ORDER TO PROVIDE VISIBILITY AND EASE OF USE FOR
 THE BICYCLE RACK, THE 6 FOOT X 4 FOOT PAD SHALL START
 ON THE NORTH SIDE OF THE PEDESTRIAN WALK AND 1 FOOT
 EAST OF THE BUILDING WALL (IN EFFECT A 6 FOOT X 5 FOOT
 PAD).
  
 13) THE CIVIL PLANS INCORRECTLY SHOW WHEEL STOPS ALONG
 THE NORTHERN PARKING ROW.
  
 14) AN IRRIGATION PERMIT IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.


Account Summary | Usage Policy | Privacy Policy