Plan Review Details - Permit 11070653
Plan Review Stops For Permit 11070653
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-08-31 Cont ID  
Sent By jwitmer Date 2011-08-31 Time 11:53 Rev Time 0.77
Received By jwitmer Date 2011-08-31 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-08-10 Cont ID  
Sent By jwitmer Date 2011-08-10 Time 15:45 Rev Time 0.77
Received By jwitmer Date 2011-08-10 Time 15:00 Sent To  
Notes
2011-08-16 14:18:56BUILDING PLAN REVIEW
 PERMIT: 11070653
 ADD: 1701 PRESIDENTIAL WAY # 101
 CONT: SUNSHINE ALUMINUM
 TEL: (561)842-3643
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
 1) COMPLIED.
  
 2A) COMPLIED.
  
 2B) COMPLIED.
  
  
 3) THE DESIGNER OF RECORD SHALL PROVIDE THE WIND DESIGN
 CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 3.1) COMPLIED.
  
 3.2) COMPLIED.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. PLANS INDICATE AN B EXPOSURE,
 THIS UNIT BACKS UP AGAINST A GOLF COURSE SEE 2007/09
 1609.4.3 EXPOSURE C. THIS EXPOSURE SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN
 WHERE THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN
 ANY DIRECTION OF OPEN AREAS OF EXPOSURE C-TYPE TERRAIN
 THAT EXTENDS MORE THAN 600 FEET (182.9 M) AND WIDTH
 GREATER THAN 150 FT. IN THE UPWIND DIRECTION.
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 3.5) POSITVE AND NEGATIVE PRESSURES FOR OPENINGS. WILL
 NEED TO BE RECALCULATED FOR C EXPOSURE.
  
 4) THE ELEVATION SHEET SUBMITTED INDICATES VERTICAL AND
 HORIZONTAL BANDS, PLEASE PROVIDE WHAT THESE ELEMENTS
 ARE, STUCCO MOLDINGS OR ARE THEY INFILL FRAMING
 MEMBERS? 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) NON-HABITAL SPACE, EXISTING SLIDING GLASS DOORS ARE
 REQUIRED TO STAY IN PLACE!!!
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-29 Cont ID  
Sent By jwitmer Date 2011-07-29 Time 13:40 Rev Time 0.25
Received By jwitmer Date 2011-07-29 Time 13:40 Sent To  
Notes
2011-07-29 14:06:12BUILDING PLAN REVIEW
 PERMIT: 11070653
 ADD: 1701 PRESIDENTIAL WAY # 101
 CONT: SUNSHINE ALUMINUM
 TEL: (561)842-3643
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
 1) COMPLIED.
  
 2A) COMPLIED.
  
 2B) WILL THE EXISTING SLIDING GLASS DOORS FROM TTHE
 BEDROOM AND LIVING ROOM BE REMOVED, CREATING HABITABLE
 SPACE? INDICATE ON THE PLANS WHAT LEVEL OF SUN ROOM
 THIS DESIGNED TOO?
 THIS IS INFORMATION REQUIRED FOR BUILDING REVIEW AND
 IMPACT FEE OFFICE? @007/09 R301.2.1.1.2 SUNROOMS
  
  
 3) THE DESIGNER OF RECORD SHALL PROVIDE THE WIND DESIGN
 CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 3.1) COMPLIED.
  
 3.2) COMPLIED.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. PLANS INDICATE AN B EXPOSURE,
 THIS UNIT BACKS UP AGAINST A GOLF COURSE SEE 2007/09
 1609.4.3 EXPOSURE C. THIS EXPOSURE SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN
 WHERE THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN
 ANY DIRECTION OF OPEN AREAS OF EXPOSURE C-TYPE TERRAIN
 THAT EXTENDS MORE THAN 600 FEET (182.9 M) AND WIDTH
 GREATER THAN 150 FT. IN THE UPWIND DIRECTION.
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 3.5) POSITVE AND NEGATIVE PRESSURES FOR OPENINGS. WILL
 NEED TO BE RECALCULATED FOR C EXPOSURE.
  
 4) THE ELEVATION SHEET SUBMITTED INDICATES VERTICAL AND
 HORIZONTAL BANDS, PLEASE PROVIDE WHAT THESE ELEMENTS
 ARE, STUCCO MOLDINGS OR ARE THEY INFILL FRAMING
 MEMBERS? 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2011-09-01 Cont ID  
Sent By rlecky Date 2011-09-01 Time 15:16 Rev Time 0.00
Received By rlecky Date 2011-09-01 Time 15:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-08-15 Cont ID  
Sent By rlecky Date 2011-08-15 Time 11:42 Rev Time 0.00
Received By rlecky Date 2011-08-15 Time 11:42 Sent To  
Notes
2011-08-15 11:51:35 
 PLEASE PROVIDE AN ELECTRICAL LAY OUT SHOWING
 RECEPTACLE. THE NATIONAL ELECTRIC CODE DOES NOT
 DISTINGUISH BETWEEN HABITABLE OR NON HABITABLE. ALL
 ROOMS ARE REQURED TO HAVE RECEPTACLES. NEC 210.52(A).
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-08-08 Cont ID  
Sent By rlecky Date 2011-08-08 Time 08:22 Rev Time 0.00
Received By rlecky Date 2011-08-08 Time 08:00 Sent To  
Notes
2011-08-08 08:23:42NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. THE NEW LIVING AREA REQUIRES A
 SWITCHED RECEPTACLE OR LIGHT. AT LEAST ONE GFCI
 PROTECTED RECEPTACLE IS REQUIRED OUTSIDE. NEC 210.70
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-09-08 Cont ID  
Sent By shill Date 2011-09-08 Time 08:57 Rev Time 0.00
Received By shill Date 2011-08-29 Time 09:48 Sent To  
Notes
2011-08-10 11:12:47SENT TO B3 SHELF FOR ZONING, BUILDING AND ELECTRICAL
 REVIEWS. JG.
  
 8/29/11 SENT TO B15 SHELF FOR ZONING, BUILDING AND
 ELECTRICAL REVIEWS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-10 Cont ID  
Sent By jgomez Date 2011-08-10 Time 11:05 Rev Time 0.00
Received By jgomez Date 2011-07-26 Time 12:43 Sent To  
Notes
2011-08-10 11:05:56LAST REVIEW DONE ON 8/9/11 BY ZONING. JG.
2011-07-26 13:38:56B18
  
2011-07-26 12:43:20TO MISC 3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2011-08-31 Cont ID  
Sent By jwitmer Date 2011-08-31 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2011-08-16 Time 14:22 Sent To  
Notes
2011-08-16 14:23:18TYPE III SUNROOM, CONSIDERED NON-HABITAL SPACE,
 EXISTING SLIDDING GLASS DOORS NOT TO BE REMOVED!!!!!

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-08-05 Cont ID  
Sent By jwitmer Date 2011-07-29 Time 14:06 Rev Time 0.00
Received By jwitmer Date 2011-07-29 Time 14:06 Sent To  
Notes
2011-07-29 14:06:59BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2011-09-05 Cont ID  
Sent By jroach Date 2011-09-05 Time 17:14 Rev Time 0.00
Received By jroach Date 2011-09-05 Time 17:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-08-09 Cont ID  
Sent By jroach Date 2011-08-09 Time 08:52 Rev Time 0.00
Received By jroach Date 2011-08-09 Time 08:52 Sent To  
Notes
2011-08-09 08:52:25ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.09.2011
 PERMIT NO.: 11070653
 ADDRESS: 1701 PRESIDENTIAL WAY #101
 CONTRACTOR/CONTACT: SUNSHINE ALUMINUM
 TELEPHONE NO.: 561.842.3643
 SCOPE OF REVIEW: RAISE SLAB, ENCLOSE PATIO USING
 SLIDING GLASS DOORS & INSTALL ACCORDION SHUTTERS ON THE
 OUTSIDE OF THE NEW ENCLOSURE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE CLARIFY THE SCOPE OF THE WORK. IS THIS AN
 EXISTING COVERED (ROOFED) PATIO THAT IS BEING ENCLOSED?
 A SITE PLAN OR SURVEY, AND FLOOR PLAN, SHALL BE
 PROVIDED SHOWING THE LOCATION OF THE PROPOSED WORK AND
 WHAT IS PROPOSED. STAFF IS UNABLE TO DETERMINE IF THERE
 ARE ANY ISSUES WITH COMPLIANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS UNTIL THIS INFORMATION HAS BEEN
 PROVIDED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH