| Plan Review Stops For Permit 11070649 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2012-01-11 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2012-01-11 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2012-01-11 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2012-01-11 15:01:14 | LETTER DATED 1/6/12 FROM MR. JORDY SOPOURN, ARCHITECT, | | | GIVING METHOD OF STOREFRONT ATTACHMENT TO THE HOST | | | STRUCTURE. | | | | | | DURING A TELEPHONE CONFERENCE CALL ON 1/11/12 WITH BEN | | | HERD, G.C., MR. JORDY SOPOURN, ARCHITECT, STATED THAT | | | HE WOULD SUBMIT A REVISED LETTER TO INCLUDE THE | | | INTRODUCTION OF WOOD BACKING INSIDE THE METAL STUDS FOR | | | THE BUCK ATTACHMENT. THIS WILL PROVIDE A BUCK | | | ATTACHMENT THAT IS EQUIVALENT TO OR BETTER THAN THE | | | ATTACHMENT REQUIRED BY MIAMI-DADE NOA# 06-1026.08 FOR | | | THE STOREFRONT WHEN ATTACHED DIRECT TO A METAL FRAME | | | STRUCTURE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | | | | TELEPHONE: (561) 805 6652 ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2011-08-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-08-23 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-08-23 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2011-08-24 12:05:58 | SEPARATE PERMIT REQUIRED FOR ENTRY DOOR | | | (NOA SUBMITTED DOES NOT INCLUDE PANIC DEVICE) | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2011-08-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-08-03 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-08-03 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2011-08-03 14:05:08 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE DOORS FROM OFFICE TO RESTROOM VESTIBULE. FBC | | | 11-4.13.7, TWO DOORS IN A SERIES TO HAVE 48" PLUS THE | | | WIDTH OF THE DOOR. SEE ALSO FBC FIGURE 11-25. | | | | | | 2. N/A. | | | | | | 3. PROVIDE ROOF STAND PRODUCT APPROVALS. INDICATE WHICH | | | OPTION IS TO BE USED. DESIGN PROFESSIONAL TO SPECIFY | | | DESIGN PRESSURES, FBC1603.1.4. | | | | | | 4. DETAIL 2-A400.1 SHOWS AN EXTERIOR DOOR DETAIL, | | | EXTERIOR WALL DETAIL (MARKED 11-A500.1, BUT SHOWN ON | | | A400.1). IF THIS IS INCLUDED IN THE SCOPE OF WORK, | | | PROVIDE PRODUCT APPROVALS, NOTE ON PLAN, AND INCLUDE IN | | | PERMIT VALUATION. | | | | | | 5. PERMIT VALUATION IS TO INCLUDE ALL LABOR AND | | | MATERIALS, INCLUDING ANY FIXED EQUIPMENT. PLEASE | | | INCLUDE ALL INSTALLED ITEMS PROVIDED BY OWNER. | | | | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2011-08-08 |
|
|
Cont ID |
|
| Sent By |
rlecky |
Date |
2011-08-08 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
rlecky |
Date |
2011-08-08 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2011-08-05 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2011-08-05 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2011-08-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2011-08-04 15:35:39 | 330 CLEMATIS STREET #107 | | | PERMIT #11070649 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | MAIN ENTRY IS PERMITTED TO BE EQUIPPED WITH PANIC | | | HARDWARE OR A KEYED LOCK WITH LOCK/UNLOCK INDICATOR | | | WINDOW AND SIGNAGE STATING THE DOOR IS TO REMAIN | | | UNLOCKED DURING BUSINESS HOURS. A THUMB TURN LOCK IS | | | NOT PERMITTED. | | | | | | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE | | | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE | | | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT | | | TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE | | | SURFACE. | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. TRASH AND DEBRIS IS TO BE REMOVED FROM THE | | | SITE DAILY. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF | | | THE FIRE MARSHAL. | | | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | | WWW.KNOXBOX.COM. | | | | | | NOTE: DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY | | | THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS | | | HAVE BEEN SATISFIED. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2011-08-04 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-08-04 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-08-04 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2011-08-04 09:52:14 | SEPERATE GAS PERMIT REQUIRED |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2011-08-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-08-23 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-08-19 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2011-08-23 12:59:01 | 8/23 ON SH DESK FOR PROCESSING (NEED TO SWAP SHEETS) | | | | | 2011-08-19 13:30:26 | GAVE TO SAMANTHA |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2011-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-08-09 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-07-27 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2011-07-27 09:44:40 | **************EXPEDITED************** | | | B--12 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2011-08-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-08-09 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-08-09 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2011-08-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-08-23 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2011-08-23 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2011-08-23 12:58:37 | PER HM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2011-08-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2011-08-01 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-08-01 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2011-08-01 15:20:19 | ****CORRECTIONS**** | | | | | | 1. SEPARATE PERMITS REQUIRED FOR THE HOOD, OOLERS AND | | | ANSUL SYSTEM (ADVISORY ONLY). | | | | | | 2. AHU 1, GRILL SIZES NOT PROVIDED FOR THE 10" DUCTS, | | | SHEET M1.1. | | | | | | 3. UNABLE TO LOCATE FRESH AIR FOR UNIT AHU1 ON SHEET | | | M1.1. AHU2 INCLUDES A NOTE REGARDING MOTORIZED DAMPER. | | | SHEET M1.2 SHOWS INTAKE ON ROOF, BUT NO OTHER | | | INFORMATION PROVIDED, PLEASE SHOW COMPLIANCE WITH FBC | | | 13.409.AB.3.3. | | | | | | 4. SHEET M1.1, NOTE 14 REQUIRES VEF TO OPERATE AT 78, | | | M2.3 STATES FANS WILL TURN ON AT 85. PLEASE CORRELATE. | | | FBC MECHANICAL 507, EVIDENCE THAT THE FANS WILL OPERATE | | | WITH THE EQUIPMENT WILL BE REQUIRED AT INSPECTION. | | | | | | 5. THERE ARE TWO UNITS MARKED AHU2, APPEARS THAT AHU1 | | | IS MISMARKED ON SHEET M1.1. | | | | | | 6. KEY NOTES HVAC, SHEET M1.1, INCLUDE TWO NOTE 8S, TWO | | | NOTE 12S. PLEASE REVISE SO EACH NOTE HAS A UNIQUE | | | NUMBER. | | | | | | 7. THE VALUE ON THE PERMIT APPLICATION IS TO INCLUDE | | | ALL LABOR AND MATERIALS. NOTES ON SHEET M2.2 MAKE | | | REFERENCE TO ITEMS SUPPLIED BY OWNER. PLEASE INCLUDE | | | ALL LABOR AND MATERIAL, INCLUDING MATERIAL PROVIDED BY | | | OWNER. | | | | | | HAROLD MOSER, MECHANICAL PLANS EXAMINER | | | 561-805-6732 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2011-08-04 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2011-08-04 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2011-08-03 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2011-08-08 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2011-08-08 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2011-08-08 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|