Plan Review Details - Permit 11070634
Plan Review Stops For Permit 11070634
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-12 Cont ID  
Sent By shill Date 2011-08-12 Time 14:43 Rev Time 0.00
Received By shill Date 2011-08-12 Time 14:43 Sent To  
Notes
2011-08-12 15:07:57PROVISO
 EITHER: REVISION REQUIRED (SUBMIT INSTALLATION
 SCHEDULE) OR SUBMIT SEPARATE PERMIT FOR SHUTTERS WITH
 ALL REQUIRED INFORMATION (PRODUCT APPROVAL, PLAN,
 INSTALLATION SCHEDULE)
  
  
 SUBMIT AN INSTALLATION SCHEDULE CORRECTED AS FOLLOWS:
  
 1. SEE OPENINGS 1 AND 2, SEE SHEET 4 OF PRODUCT
 APPROVAL FOR SHUTTER TO GLASS SEPARATION REQUIRED.
  
 2. SEE SHEET 5 OF PRODUCT APPROVAL, 3 1/2" EDGE
 DISTANCE REQUIRED FOR BLOCK SUBSTRATE.
  
 3. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHARTS ON SHEET 5 (FOR INSTANCE, 1 TOP,
 2 BOTTOM, ETC.). CODE COMPLIANCE CANNOT BE DETERMINED
 BASED ON THE INFORMATION PROVIDED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-28 Cont ID  
Sent By shill Date 2011-07-28 Time 07:52 Rev Time 0.00
Received By shill Date 2011-07-28 Time 07:52 Sent To  
Notes
2011-07-28 08:07:25****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A FLOOR PLAN SHOWING LOCATION OF PROPOSED
 NEW WINDOWS AND DOORS WITH SIZES, FBC301. PROVIDE ROOM
 DESIGNATIONS (BATHROOMS PER APPLICATION) ON THE FLOOR
 PLAN.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
 3. FOR THE KITCHEN AND BATH RENOVATIONS, PLEASE CLARIFY
 SCOPE. ARE YOU PROPOSING TO REPLACE CABINETRY IN THE
 SAME SIZE, CONFIGURATION, AND LOCATION?
  
 IF THE FLOOR PLAN IS TO BE ALTERED, PLEASE PROVIDE A
 DEMO PLAN OF THE EXISTING CONDITIONS AND A PROPOSED
 FLOOR PLAN SHOWING THE NEW LAYOUT PROPOSED.
  
 IF THE FLOOR PLAN IS NOT TO BE ALTERED, PLEASE NOTE
 LOCATION ON PLAN AND INCLUDE A NOTE WHICH STATES THAT
 EXISTING CABINETS, COUNTERS, ETC. WILL BE REPLACED IN
 SAME SIZE AND CONFIGURATION.
  
 4. FENCING WORK REQUIRES A SEPARATE PERMIT. THIS WILL
 BE REMOVED FROM THE SCOPE OF WORK ON THIS PERMIT.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-12 Cont ID  
Sent By shill Date 2011-08-12 Time 15:08 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2011-08-09 10:54:44INCOMING SENT TO SAMANTHA HILL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-28 Cont ID  
Sent By shill Date 2011-07-28 Time 08:07 Rev Time 0.00
Received By shill Date 2011-07-26 Time 16:16 Sent To  
Notes
2011-07-26 16:18:47TO MISC 1