Plan Review Details - Permit 11070629
Plan Review Stops For Permit 11070629
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-11 Cont ID  
Sent By jwitmer Date 2011-08-11 Time 13:15 Rev Time 0.77
Received By jwitmer Date 2011-08-11 Time 13:12 Sent To  
Notes
2011-08-11 13:58:42BUILDING PLAN REVIEW
 PERMIT: 11070629
 ADD: 4200 N FLAGLER
 CONT: BENCHMARK III CORP.
 TEL: (561)722-5095
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 2) COUNTY IMPACT FEE OFFICE HAS AGREED TO ALLOW THE
 IMPACT FEE ASSESSMENT TO BE PAID AT TIME OF PERMIT FOR
 THE BUILDING BEFORE ISSUANCE OF THE BUILDING PERMIT.
  
 3) 2007 FBC-B 1802.4-6 QUESTIONABLE SOILS. AT THIS TIME
 NO SOILS REPORTS HAVE BEEN TURNED IN. IT WILL BE
 REQUIRED AT TIME OF THE FOUNDATION INSPECTION THE
 INSPECTOR TO RECEIVE A SIGNED & SEALED ORIGINAL REPORT
 FROM THE STUDY COMPLETED BY DUNKLEBERGER ENGINEERING &
 TESTING, INC.
  
 4) ) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-04 Cont ID  
Sent By jwitmer Date 2011-08-01 Time 11:59 Rev Time 0.77
Received By jwitmer Date 2011-08-01 Time 08:32 Sent To  
Notes
2011-08-01 08:32:30BUILDING PLAN REVIEW
 PERMIT: 11070629
 ADD: 4200 N FLAGLER
 CONT: BENCHMARK III CORP.
 TEL: (561)722-5095
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS PLAN IS FOR A NEW BUILDING PLEASE PROVIDE SOILS
 REPORT FOR THE SAFE MINIMUM SOIL BEARING VALUES.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN
 THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS
 OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 2) THIS BUILDING IS IN A A- 5 FLOOD ZONE. THE BASE
 FLOOD ELEVATION FOR FINISH FLOOR IS 7.5 NGVD. SHEET
 AS-101 INDICATES A FINISH FLOOR ELEVATION OF 100.00'
 BUT THERE IS NO REFERENCE TO WHAT
 100.00' IS EQUAL TO?
  
 3) THIS BUILDING (FOOTING) ALSO DOES NOT INDICATE TYPE
 OF OCCUPANCY AND MINIMUM BUILDING TYPE. 2007/09 FBC-B
 503. THIS INFORMATION IS REQUIRED TO VERIFY THE TYPE
 AND SIZE OF BUILDING IS DESIGN PER TABLE 503.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-08-02 Cont ID  
Sent By rlecky Date 2011-08-02 Time 13:34 Rev Time 0.00
Received By rlecky Date 2011-08-02 Time 12:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-08-12 Cont ID  
Sent By lmartine Date 2011-08-12 Time 16:24 Rev Time 0.00
Received By lmartine Date 2011-08-12 Time 16:24 Sent To  
Notes
2011-08-12 16:25:21SEE SHEET G-101 FOR WESLEY'S STAMP AND SIGNATURE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-02 Cont ID  
Sent By wjolin Date 2011-08-02 Time 14:27 Rev Time 0.00
Received By wjolin Date 2011-08-02 Time 14:02 Sent To  
Notes
2011-08-02 14:27:394050 NORTH FLAGLER DRIVE
 PERMIT #11070629
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING OCCUPANCY TYPE,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
 INDICATE IF ANY FIRE SPRINKLER SYSTEM OR FIRE ALARM
 SYSTEM WILL BE PROTECTING THIS BUILDING.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007. OCCUPANT LOADS EXCEEDING 100 PERSONS MAY
 REQUIRE PANIC HARDWARE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMITS REQUIRED FOR KITCHEN HOOD
 AND KITCHEN FIRE SUPPRESSION SYSTEM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF18'
 TO THE FRONT, 7?-6? TO THE SIDES AND 4? TO THE BACKSIDE
 PER SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION.
  
 PROVIDE ADDITIONAL DETAILS/INFORMATION FOR THE COVERED
 TERRACE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-12 Cont ID  
Sent By lmartine Date 2011-08-04 Time 16:25 Rev Time 0.00
Received By lmartine Date 2011-07-26 Time 08:40 Sent To  
Notes
2011-07-27 08:41:04C15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-08-11 Cont ID  
Sent By jwitmer Date 2011-08-11 Time 13:13 Rev Time 0.00
Received By jwitmer Date 2011-08-01 Time 08:32 Sent To  
Notes
2011-08-01 08:33:02BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 COUNTY IMPACT FEE OFFICE HAS AGREED TO ALLOW THE IMPACT
 FEE ASSESSMENT TO BE PAID AT TIME OF PERMIT FOR THE
 BUILDING. 8/11/11 JW
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-02 Cont ID  
Sent By hmoser Date 2011-08-02 Time 11:33 Rev Time 0.00
Received By hmoser Date 2011-08-02 Time 11:33 Sent To  
Notes
2011-08-02 11:46:34PASS PROVISO
 REFER TO SECTION 1107.2.1 PIPING INSTALLED IN OR
 BENEATH CONCRETE FLOORS SHALL BE ENCASED IN DUCT PIPE.
 2007 FBC (M)
 REFER TO SECTION 30702.1 CONDENSATE DISPOSAL.2007 FBC
 (M)
 REFER TO SECTION 90-125 ARTICLE 3 SEWERS & SEWAGE
 DISPOSAL. # 5
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-08-12 Cont ID  
Sent By lwagner Date 2011-08-12 Time 15:20 Rev Time 0.00
Received By lwagner Date 2011-08-12 Time 14:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-08-02 Cont ID  
Sent By lwagner Date 2011-08-02 Time 11:41 Rev Time 0.00
Received By lwagner Date 2011-08-02 Time 10:15 Sent To  
Notes
2011-08-02 10:40:27FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THIS BUILDING DOES NOT INDICATE TYPE OF OCCUPANCY
 AND NUMBER OF OCCUPANTS.
 403.1 MINIMUM NUMBER OF FIXTURES. PLUMBING FIXTURES
 SHALL BE PROVIDED FOR THE TYPE OF OCCUPANCY AND IN THE
 MINIMUM NUMBER SHOWN IN TABLE 403.1. TYPES OF
 OCCUPANCIES NOT SHOWN IN TABLE 403.1 SHALL BE
 CONSIDERED INDIVIDUALLY BY THE CODE OFFICIAL. THE
 NUMBER OF OCCUPANTS SHALL BE DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING. OCCUPANCY CLASSIFICATION SHALL
 BE DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 2. THE KITCHEN CAN WASH SHOULD BE INSTALLED ON THE
 GREASE LINE.
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR
 AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop Z ZONING
Rev No 1 Status P Date 2011-08-04 Cont ID  
Sent By jroach Date 2011-08-04 Time 11:19 Rev Time 0.00
Received By jroach Date 2011-08-04 Time 11:19 Sent To  
Notes
2011-08-04 11:20:30ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 08.04.2011
 PERMIT NO.: 11070629
 ADDRESS: 4050 NORTH FLAGLER DRIVE
 CONTRACTOR/CONTACT: GREGORY HALE
 TELEPHONE NO.: 772.320.0206
 SCOPE OF REVIEW: FOUNDATION FOR CAFETERIA.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PERMIT ISSUED FOR FOUNDATION WORK ONLY! AS THE
 REQUIRED MAJOR AMENDMENT TO THE RYBOVICH CMPD HAS NOT
 BEEN APPROVED BY THE CITY COMMISSION, WORK MAY PROCEED
 AT YOUR OWN RISK! ANY MODIFICATIONS, OR A DENIAL, BY
 THE CITY COMMISSION MAY REQUIRE THE REMOVAL OF ANY
 IMPROVEMENTS INSTALLED AS PART OF THIS PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM