Plan Review Details - Permit 11070562
Plan Review Stops For Permit 11070562
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-08-22 Cont ID  
Sent By shill Date 2011-08-22 Time 13:56 Rev Time 0.00
Received By shill Date 2011-08-22 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-08-03 Cont ID  
Sent By shill Date 2011-08-03 Time 15:49 Rev Time 0.00
Received By shill Date 2011-08-03 Time 15:49 Sent To  
Notes
2011-08-03 15:54:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR
 EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE
 CHANGED EFFECTIVE MARCH 1, 2009. RESUB SHEET STATES
 THAT PRESSURES WERE CHANGED. PRESSURES ARE TOO LOW,
 MINIMUM -46.2 FOR ZONE 4.
  
 2. SEE OPENING C, 123 1/4" SPAN STATED. THIS DOES NOT
 CORRELATE WITH THE HEIGHT. IF THIS IS THE SPAN, SEE
 SHEET 11 OF THE PRODUCT APPROVAL. 5" SPACING REQUIRED.
  
 3. TIM ELLIS HAS SIGNED THE PERMIT APPLICATION WHERE
 THE QUALIFIER'S SIGNATURE SHOULD BE. IT IS NOT CLEAR
 WHY THIS PERSON HAS REPRESENTED HIMSELF AS THE
 QUALIFIER. PROVIDE A NEW PROPERLY NOTARIZED PERMIT
 APPLICATION, NO WHITE OUT PERMITTED IN THE NOTARIZED
 SIGNATURE AREA.
  
 4. PRIOR TO RESUBMITTAL, HAVE THE QUALIFIER REVIEW THE
 INSTALLATION SCHEDULE AND PROPOSED DESIGN PRESSURES FOR
 CODE COMPLIANCE.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-26 Cont ID  
Sent By shill Date 2011-07-26 Time 10:20 Rev Time 0.00
Received By shill Date 2011-07-26 Time 10:20 Sent To  
Notes
2011-07-26 10:24:03****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE PRESSURES TO EXPOSURE C OR PROVIDE ENGINEERED
 RATIONAL ANALYSIS FOR USE OF REDUCED PRESSURES, SEE
 ASCE7-05 AND FBC R301.2.1.4.
  
 2. SEE SHEET 11 OF THE PRODUCT APPROVAL. 9" SPACING
 DOES NOT COMPLY. PLEASE ALSO CLARIFY WHICH TAPCON IS
 PROPOSED. INSTALLATION SCHEDULE SPECIFIES "ITW TAPCON"
 BUT SHEET 11 HAS TWO, ITW TAPCON 1/4" AND ITW BULIDEX
 5/8".
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rlecky Date 2011-08-16 Time 16:30 Sent To  
Notes
2011-08-16 16:30:51TO SH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-03 Cont ID  
Sent By shill Date 2011-08-03 Time 15:54 Rev Time 0.00
Received By shill Date 2011-07-29 Time 09:45 Sent To  
Notes
2011-07-29 09:45:37TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-26 Cont ID  
Sent By shill Date 2011-07-26 Time 10:24 Rev Time 0.00
Received By shill Date 2011-07-22 Time 12:26 Sent To  
Notes
2011-07-22 12:27:03TO MISC 1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved