Plan Review Details - Permit 11070536
Plan Review Stops For Permit 11070536
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-07-27 Cont ID  
Sent By rlecky Date 2011-07-27 Time 10:03 Rev Time 0.00
Received By rlecky Date 2011-07-27 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-12 Cont ID  
Sent By rlecky Date 2011-08-12 Time 11:46 Rev Time 0.00
Received By rlecky Date 2011-08-05 Time 16:29 Sent To  
Notes
2011-08-05 16:29:20TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-27 Cont ID  
Sent By rlecky Date 2011-07-27 Time 10:04 Rev Time 0.00
Received By rlecky Date 2011-07-22 Time 08:00 Sent To  
Notes
2011-07-22 08:01:14TO ZONING
 TRAVELLING W/11070537

Review Stop Z ZONING
Rev No 2 Status P Date 2011-08-11 Cont ID  
Sent By eschneid Date 2011-08-11 Time 13:18 Rev Time 0.25
Received By eschneid Date 2011-08-11 Time 13:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2011-07-26 Cont ID  
Sent By eschneid Date 2011-07-26 Time 16:23 Rev Time 0.15
Received By eschneid Date 2011-07-26 Time 16:23 Sent To E
Notes
2011-07-26 16:34:25FAILED
  
 1) THE GENERATOR AND PAD ARE REQUIRED TO BE SET BACK A
 MINIMUM OF 3 FEET FROM THE EAST PROPERTY LINE. THE
 DIMENSION FROM THE PAD TO THE EAST PROPERTY LINE SHALL
 CLEARLY BE SHOWN ON THE MARKED UP SURVEY.
  
 2) WHICH DIRECTION IS THE PAD ORIENTED? THE DIMENSION
 OF THE SETBACK TO THE PROPERTY LINE, THE WIDTH OF THE
 PAD, AND THE DIMENSION FROM THE PAD TO THE HOUSE SHALL
 BE SHOWN AND SHALL TOTAL 19.8 FEET.
  
 3) PLEASE VERIFY THAT THE PAD WILL NOT BE IN FRONT OF
 THE FRONT FACADE OF THE HOUSE.
  