Plan Review Details - Permit 11070469
Plan Review Stops For Permit 11070469
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2011-08-08 Cont ID  
Sent By jwitmer Date 2011-08-08 Time 08:55 Rev Time 0.77
Received By jwitmer Date 2011-08-08 Time 08:11 Sent To  
Notes
2011-08-08 08:56:00BUILDING PROVISO:
 11-7.2 AT LEAST ONE OF EACH TYPE SHALL HAVE A PORTION
 OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915 MM) IN
 LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915 MM)
 ABOVE THE FINISH FLOOR. IT SHALL BE ON AN ACCESSIBLE
 ROUTE COMPLYING WITH SECTION 11-4.3.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2011-08-19 Cont ID  
Sent By rlecky Date 2011-08-19 Time 15:51 Rev Time 0.00
Received By rlecky Date 2011-08-17 Time 15:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-13 Cont ID  
Sent By wjolin Date 2011-09-13 Time 14:14 Rev Time 0.00
Received By wjolin Date 2011-09-13 Time 14:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-08-19 Cont ID  
Sent By wjolin Date 2011-08-19 Time 15:36 Rev Time 0.00
Received By wjolin Date 2011-08-19 Time 07:59 Sent To  
Notes
2011-08-19 15:36:23777 SOUTH FLAGLER DRIVE - SUITE #1601W
 PERMIT #11070469
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FABRIC WRAPPED PANELS TO MEET THE FLAME SPREAD
 REQUIREMENTS FOR CLASS A, B OR C.
  
 ALL NEW OR EXISTING DOORS THAT ARE EQUIPPED WITH
 ELECTROMAGNETIC HARDWARE SHALL INTERLOCK WITH THE
 SPRINKLER AND FIRE ALARM SYSTEM AND SHALL BE NOTED ON
 THE LIFE SAFETY PLANS, FIRE ALARM PLANS AND ACCESS
 CONTROL PLANS. ACCESS CONTROLLED EGRESS DOORS SHALL
 COMPLY WITH ALL EIGHT REQUIREMENTS LISTED IN SECTION
 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2007. INTERLOCK
 WITH THE SPRINKLER AND FIRE ALARM SYSTEM SHALL BE
 REFERENCED ON THE LIFE SAFETY PLANS AND ELECTRICAL FIRE
 ALARM SYSTEM DRAWINGS.
  
 SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2007
 ALLOWS ACCESS CONTROLLED EGRESS DOORS PROVIDED THAT ALL
 EIGHT OF THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. MANUAL FIRE ALARM BOXES SHALL NOT BE REQUIRED TO
 UNLOCK THE DOORS.
 8. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 SHEET E1: FIRE ALARM NOTIFICATION APPLIANCE SYMBOL IS
 MISSING FROM SHEET.
  
 SHEET E2: NO FIRE ALARM NOTIFICATION APPLIANCE PROVIDED
 IN CONFERENCE ROOM 16-005 OR COPY ROOM 16-023.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 IN ADDITION TO THE ENGINEERING DOCUMENTS, SEPARATE
 PLANS AND PERMITS ARE REQUIRED FOR THE INSTALLATION OR
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2011-09-07 Time   Rev Time 0.00
Received By jgomez Date 2011-07-22 Time 14:48 Sent To  
Notes
2011-07-22 14:48:40SENT TO RON'S DESK FOR PROCESSING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-09-07 Cont ID  
Sent By rregueir Date 2011-09-07 Time 15:54 Rev Time 0.00
Received By rregueir Date 2011-09-07 Time 15:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2011-08-17 Cont ID  
Sent By lwagner Date 2011-08-17 Time 14:43 Rev Time 0.00
Received By lwagner Date 2011-08-17 Time 14:04 Sent To  
Notes
2011-08-17 14:44:25SINK COUNTER TOP TO BE MAX 34" AFF

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2011-09-16 Cont ID  
Sent By rregueir Date 2011-09-16 Time 12:55 Rev Time 0.00
Received By rregueir Date 2011-09-16 Time 12:55 Sent To  
Notes
***NONE***