| 2011-08-19 15:36:23 | 777 SOUTH FLAGLER DRIVE - SUITE #1601W |
| | PERMIT #11070469 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | FABRIC WRAPPED PANELS TO MEET THE FLAME SPREAD |
| | REQUIREMENTS FOR CLASS A, B OR C. |
| | |
| | ALL NEW OR EXISTING DOORS THAT ARE EQUIPPED WITH |
| | ELECTROMAGNETIC HARDWARE SHALL INTERLOCK WITH THE |
| | SPRINKLER AND FIRE ALARM SYSTEM AND SHALL BE NOTED ON |
| | THE LIFE SAFETY PLANS, FIRE ALARM PLANS AND ACCESS |
| | CONTROL PLANS. ACCESS CONTROLLED EGRESS DOORS SHALL |
| | COMPLY WITH ALL EIGHT REQUIREMENTS LISTED IN SECTION |
| | 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2007. INTERLOCK |
| | WITH THE SPRINKLER AND FIRE ALARM SYSTEM SHALL BE |
| | REFERENCED ON THE LIFE SAFETY PLANS AND ELECTRICAL FIRE |
| | ALARM SYSTEM DRAWINGS. |
| | |
| | SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2007 |
| | ALLOWS ACCESS CONTROLLED EGRESS DOORS PROVIDED THAT ALL |
| | EIGHT OF THE FOLLOWING CRITERIA ARE MET: |
| | 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| | ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT |
| | ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON |
| | DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER |
| | TO THE SENSOR. |
| | 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL |
| | SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| | THE DOORS IN THE DIRECTION OF EGRESS. |
| | 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE |
| | DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| | LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND |
| | WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS. |
| | 4. THE MANUAL RELEASE DEVICE SHALL BE READILY |
| | ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| | PUSH TO EXIT. |
| | 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| | RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK, |
| | INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS, |
| | AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| | 30 SECONDS. |
| | 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | 7. MANUAL FIRE ALARM BOXES SHALL NOT BE REQUIRED TO |
| | UNLOCK THE DOORS. |
| | 8. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER |
| | SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL |
| | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF |
| | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. |
| | |
| | SHEET E1: FIRE ALARM NOTIFICATION APPLIANCE SYMBOL IS |
| | MISSING FROM SHEET. |
| | |
| | SHEET E2: NO FIRE ALARM NOTIFICATION APPLIANCE PROVIDED |
| | IN CONFERENCE ROOM 16-005 OR COPY ROOM 16-023. |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE |
| | SPRINKLERS. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | IN ADDITION TO THE ENGINEERING DOCUMENTS, SEPARATE |
| | PLANS AND PERMITS ARE REQUIRED FOR THE INSTALLATION OR |
| | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |