Plan Review Details - Permit 11070467
Plan Review Stops For Permit 11070467
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2011-08-18 Cont ID  
Sent By shill Date 2011-08-18 Time 14:52 Rev Time 0.00
Received By shill Date 2011-08-18 Time 14:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2011-08-15 Cont ID  
Sent By shill Date 2011-08-15 Time 09:43 Rev Time 0.00
Received By shill Date 2011-08-15 Time 09:43 Sent To  
Notes
2011-08-15 09:50:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 ALL COMPONENTS & CLADDING, FAC9N-3. IT APPEARS THAT THE
 CONTRACTOR IS ATTEMPTING TO SUBMIT A LOCAL PRODUCT
 APPROVAL FOR THE IMPACT DOOR.
  
 IN ORDER TO SUBMIT A LOCAL PRODUCT APPROVAL
 APPLICATION, ORIGINAL SIGNED AND SEALED ENGINEERING IS
 REQUIRED PER FS471. YOU MAY USE THE FORM WHICH IS ON
 THE DCA WEBSITE.
  
 THE APPLICATION IS TO BE FILLED OUT COMPLETELY,
 INCLUDING HOW QUALITY ASSURANCE WILL BE ADDRESSED (AND
 EVIDENCE OF QUALITY ASSURANCE FOR THE SPECIFIC PRODUCT,
 IF APPLICABLE).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-08-02 Cont ID  
Sent By shill Date 2011-08-02 Time 11:26 Rev Time 0.00
Received By shill Date 2011-08-02 Time 11:26 Sent To  
Notes
2011-08-02 11:27:46****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE DOOR PRODUCT APPROVAL SUBMITTED IS FOR A NON
 IMPACT DOOR. IMPACT PROTECTION REQUIRED, FBC1609.1.4.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-26 Cont ID  
Sent By shill Date 2011-07-26 Time 10:00 Rev Time 0.00
Received By shill Date 2011-07-26 Time 10:00 Sent To  
Notes
2011-07-26 10:01:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALD, DATED ORIGINALS
 FS471. IT APPEARS THAT THESE DOCUMENTS (SHOPS) ARE NOT
 REQUIRED TO DEMONSTRATE CODE COMPLIANCE.
  
 2. SCOPE OF WORK INCLUDES A DOOR. PROVIDE DOOR PRODUCT
 APPROVAL FAC9N-3, FBC1609.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-08-15 Cont ID  
Sent By shill Date 2011-08-15 Time 09:50 Rev Time 0.00
Received By shill Date 2011-08-10 Time 14:48 Sent To  
Notes
2011-08-10 14:49:02SENT TO SAMANTHA'S DESK FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-02 Cont ID  
Sent By shill Date 2011-08-02 Time 11:27 Rev Time 0.00
Received By shill Date 2011-08-01 Time 14:10 Sent To  
Notes
2011-08-01 14:11:05SENT TO S HILL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-26 Cont ID  
Sent By shill Date 2011-07-26 Time 10:01 Rev Time 0.00
Received By shill Date 2011-07-22 Time 13:50 Sent To  
Notes
2011-07-22 13:51:32SENT TO MISCELLANEOUS SHELF #1 FOR REVIEW.