Plan Review Details - Permit 11070466
Plan Review Stops For Permit 11070466
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-08-30 Cont ID  
Sent By rmcdouga Date 2011-08-30 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2011-08-30 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-08-02 Cont ID  
Sent By rmcdouga Date 2011-08-02 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2011-08-02 Time 06:52 Sent To Z
Notes
2011-08-02 08:04:53REVISION DENIED BY BUILDING
  
 1) THE FLOOR TRUSS PLACEMENT PLAN AND TRUSS DRAWINGS
 FROM THE TRUSS COMPANY ARE NOT SIGNED AND SEALED BY THE
 TRUSS SYSTEM ENGINEER AS REQUIRED BY FAC 61G15-31.003.
  
 2) SHEET S-1 SHOWS A 4" STEP DOWN FROM THE KITCHEN AREA
 TO THE LAUNDRY ROOM. THIS IS NOT REFLECTED ON THE FLOOR
 PLAN ON SHEET A-1.1 OR THE TRUSS DRAWINGS. PLEASE
 CORRECT.
  
 3) SHEET S-1 SHOWS A 2-1/2" STEP AT THE REAR OF THE
 GARAGE WHICH IS NOT SHOWN ON SECTION 10 ON S-3. PLEASE
 CORRECT.
  
 4) SHOW COMPLIANCE WITH FBC R319.1(1) WHICH REQUIRES
 PROTECTION AGAINST DECAY OF FLOOR JOISTS OR THE BOTTOM
 OF A WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES
 OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES TO THE
 EXPOSED GROUND IN CRAWL SPACES.
  
 5) SPECIFY THE UNDER FLOOR INSULATION THAT WILL BE
 INSTALLED IN THE CRAWL SPACE AND SUBMIT TWO COPIES OF
 REVISED ENERGY CALCULATIONS AS REQUIRED BY FBC 11 SECT.
 N1100.
  
 6) THE SURFACE WATER DRAINAGE PLAN ON SHEET A-0.1 DOES
 NOT INDICATE HOW THE SURFACE DRAINAGE WILL BE DIVERTED
 TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION AS REQUIRED BY FBC R401.3. PLEASE CORRECT.
  
 7) PROVIDE A RESPONSE LETTER INDICATING HOW THE REVIEW
 COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-30 Cont ID  
Sent By rmcdouga Date 2011-08-30 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2011-08-23 Time 11:43 Sent To  
Notes
2011-08-23 11:44:49INCOMING SENT TO ROBERT MCDOUGAL DESK. JW
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-08 Cont ID  
Sent By rmcdouga Date 2011-08-08 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2011-07-22 Time 14:02 Sent To  
Notes
2011-07-22 14:02:31SENT TO MCDOUGAL'S DESK FOR REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2011-08-05 Cont ID  
Sent By jroach Date 2011-08-05 Time 16:31 Rev Time 0.00
Received By jroach Date 2011-08-05 Time 16:31 Sent To B
Notes
***NONE***