Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-25 Cont ID  
Sent By rlecky Date 2011-07-25 Time 08:53 Rev Time 0.00
Received By rlecky Date 2011-07-25 Time 08:53 Sent To ENG
Notes
2011-07-25 09:09:30RISER PLAN NEEDS TO INCLUDE SERVICE FEEDER WIRE SIZE,
 CONDUIT TYPE AND BURIAL DEPTH IF NOT PROVIDED BY FPL.
 PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF UG
 CONDUCTORS AND CONDUIT. UG SERVICE MAY NOT CROSS
 UTILITY EASEMENTS WITHOUT AN EASEMENT AGREEMENT. NEC
 215.5
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER