| 2011-07-25 11:38:12 | BUILDING PLAN REVIEW |
| | PERMIT: 11070424 |
| | ADD: 8628 PLUM CAY |
| | CONT: O/B BOYCHUK, PATRICIA |
| | TEL: (561)714-0686 |
| | |
| | 2007 FLORIDA BUILDING CODE RESIDENTIAL W/ 2009 FBC |
| | SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE SEE SURVEY THIS BUILDING IS LOCATED WITHIN A |
| | A0 FLOOD ZONE, THE FINISH FLOOR OF THE SUN ROOM IS TO |
| | BE THE SAME HEIGHT AS THE FLOOR LEVEL OF 21.42 FEET |
| | NGVD. SECTION 94-546 WEST PALM BEACH MUNI CODE & R |
| | 323.1. PLEASE BE AWARE THIS MAY CHANGE YOUR BUILDING |
| | DESIGN OF CURB. |
| | |
| | 2) THE DESIGNER OF RECORD FOR THE PLANS SHALL PRINT AND |
| | SIGN THERE NAME ON ALL PRINTS TAKING OWNERSHIP OF |
| | PLANS. 106.1 ADMINISTRATIVE CODE. |
| | |
| | 3) THE DESIGNER OF RECORD WILL NEED TO INDICATE TO |
| | WHICH WIND DESIN CRITERIA THE SUNROOM WAS DESIGNED? |
| | 2007/09 FBC-R 301.2.1.1. |
| | |
| | 4) 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 4.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | |
| | 4.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| | |
| | 4.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | |
| | 4.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 5) 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| | THE OVERTURNING EFFECTS CAUSED BY LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND. |
| | THERE APPEARS TO BE A DISCREPANCY BETWEEN THE CUT |
| | SECTION OF PLANS AND WOOD STUD INFILL DETAILS. PLEASE |
| | NOTE THE CUT SECTION INDICATES A EXISTING DOUBLE |
| | 2X BUILT UP WOOD BEAM WHERE AS THE WOOD STUD INFILL |
| | DETAIL INDICATES THERE TO BE A CONCRETE BEAM WITH 4 |
| | INCH POWER CONCRETE SCREWS, PLEASE CLARIFY. |
| | THIS WALL WILL BECOME PART OF THE MAIN WIND FORCE |
| | RESISTING SYSTEM AND WILL NEED TO SHOW STRAPPING FROM |
| | THE WOOD INFILL WALL TO THE BEAM ABOVE. |
| | R601.2 A CONTINIOUS LOAD PATH BETWEEN FOUNDATIONS, |
| | WALLS AND ROOFS SHALL BE PROVIDED. |
| | |
| | 6) PLEASE PROVIDE COMPLIANCE WITH 2007/09 FBC-R SECTION |
| | 301.2.1.1.2. PROVIDE TO WHAT CATEGORY THIS SUN ROOM WAS |
| | DESIGNED. |
| | |
| | 7) DEPENDING ON THE RESULTS OF COMMENT# SIX THE PRODUCT |
| | APPROVAL FOR T.M. WINDOWS 747 HP SINGLE HUNG WINDOWS |
| | MAY OR MAY NO BE ACCEPTED. NOTE THIS NOA (10-0202.03) |
| | ONLY HAS SMALL MISSILE IMPACT TESTING, PLEASE REVIEW |
| | 2007/09 FBC-R R 301.2.1.2. |
| | |
| | 8) PLEASE REVIEW CUT SECTION OF WALL FOR CODE |
| | COMPLIANCE REQUIRING BOND BREAK: R703.6.3 WHERE CEMENT |
| | PLASTER (STUCCO) IS TO BE APPLIED TO LATH OVER FRAME |
| | CONSTRUCTION, MEASURES SHALL BE TAKEN TO PREVENT |
| | BONDING BETWEEN THE CEMENT PLASTER AND THE |
| | WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED |
| | BETWEEN THE WATER-RESISTIVE BARRIER AND THE CEMENT |
| | PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING: |
| | |
| | 8.1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER |
| | MATERIAL; OR |
| | |
| | 8.2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER |
| | OVER AN APPROVED PLASTIC HOUSE WRAP; OR |
| | |
| | 8.3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN |
| | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 9) PLANS DO NOT PROVIDE DETAILS OF WINDOW AND DOOR |
| | OPENINGS 2007/09 FBC-R TABLE R502.2.5.1 SEE NOTE (NJ) |
| | NUMBER OF JACKS. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |