| 2011-08-01 09:47:24 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- CONVERTING EXISTING GARAGE TO LIVABLE AREA. NEED TO |
| | BRING PLANS TO THE PALM BEACH COUNTY BUILDING (2300 N. |
| | JOG RD) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | THIS IS REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- CHANGING USE FROM GARAGE TO LIVABLE AREA. NEED TO |
| | PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED BY |
| | SEC. N1100.0. PLEASE MAKE SURE CORRECT UPDATED FORM IS |
| | USED AND FORM IS SIGNED AND DATED BY ALL THE REQUIRED |
| | PEOPLE. |
| | |
| | 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE PLANS. SEC. 106.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 4- PLANS ARE MISSING THE FOLLOWING INFORMATION: |
| | A) BUILDING CODE USED (2007 FLORIDA RESIDENTIAL CODE |
| | WITH 2009 REVISIONS). |
| | |
| | B) DESIGN PRESSURES FOR EXTERIOR DOOR AND WINDOWS. |
| | NOTE: DESIGNER DOING THE CALCULATIONS TO TAKE INTO |
| | CONSIDERATION THAT ACCORDING TO SEC. R301.2.1.4.3 THIS |
| | BUILDING IS LOCATED IN EXPOSURE "C" AND THE BASIC WIND |
| | SPEED FOR THE CITY OF WEST PALM BEACH IS 140MPH. |
| | |
| | C) COMPLETE WALL SECTION SHOWING CONSTRUCTION OF NEW |
| | WALL TO ENCLOSE GARAGE DOOR OPENING. SHOW HOW THE |
| | CONSTRUCTION WILL RESIST THE DESIGN PRESSURES OF SEC. |
| | R301. NOTE: TAKE INTO CONSIDERATION THAT GARAGE DOOR |
| | WILL REMAIN AS SHOWN ON THE FRONT ELEVATION. SPECIFY |
| | ALL FRAMING MEMBERS, STRUCTURAL CONNECTORS AND ALL THE |
| | FINISHES ON BOTH SIDES OF THE WALL. DETAIL W-1 SHOWN ON |
| | THE PLANS IS INCOMPLETE AND DOESN'T PROVIDE THIS |
| | INFORMATION. |
| | |
| | D) COORDINATE INSULATION SHOWN ON THE WALL DETAIL W-1 |
| | WITH THE INSULATION SPECIFIED ON THE ENERGY |
| | CALCULATIONS. NOTE: R31 DOESN'T FIT ON A 2X6 WALL. |
| | REVISE AS REQUIRED. |
| | |
| | E) SPECIFY ATTIC INSULATION AS REQUIRED BY SEC. R806. |
| | COORDINATE WITH ENERGY CALCULATIONS. |
| | |
| | F) SPECIFY SIZE OF WINDOWS TO VERIFY COMPLIANCE WITH |
| | EGRESS REQUIREMENTS OF SEC. R310. |
| | |
| | G) COMPLETE DETAILS AND SPECIFICATIONS FOR STRUCTURAL |
| | FRAMING OF NEW WINDOWS AND NEW ENTRY DOOR TO SHOW |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. |
| | |
| | H) GARAGE FINISH FLOOR IS USUALLY LOWER THAN THE FINISH |
| | FLOOR OF THE EXISTING HOUSE. SPECIFY NEW BEDROOM AND |
| | BATHROOM FINISH FLOOR TO VERIFY COMPLIANCE WITH THE |
| | MIN. FINISH FLOOR REQUIREMENTS OF SEC. R404.1.6. NEED |
| | MIN. 4" OR 6" FINISH FLOOR ELEVATION ABOVE GRADE |
| | DEPENDING ON THE CONSTRUCTION TYPE. SHOW HOW GETTING |
| | THE REQUIRED FINISH FLOOR ELEVATION IF CURRENT |
| | ELEVATION IS LOWER THAN THE MIN. REQUIRED. |
| | |
| | 5- OWNER TO SIGN PERMIT APPLICATION FOR BUILDING AND |
| | ELECTRICAL PERMITS. AND, CLARIFY IF ANY A/C WORK IS |
| | GOING TO TAKE PLACE. IF SO, THEN PROVIDE COMPLETE A/C |
| | INFORMATION AND SIGN PERMIT APPLICATION FOR A/C PERMIT |
| | AS WELL. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR THE STRUCTURAL CONNECTORS SPECIFIED |
| | ON THE WALL SECTIONS AND DETAILS. OR PERSON RESPONSIBLE |
| | FOR THE DESIGN MAY WRITE THE CURRENT CONNECTOR FLORIDA |
| | PRODUCT APPROVAL ON THE DRAWINGS. |
| | |
| | 7- DESIGNER RESPONSIBLE FOR THE PLANS TO APPROVE IN |
| | WRITING ALL PRODUCT APPROVALS (DOORS AND WINDOWS) AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION WAS UPDATED AS REQUIRED BY SEC. 108.3 |
| | CITY AMENDMENTS TO FBC. PERMIT FEE BALANCE IS $259.82. |
| | |
| | 9- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |