| 2011-08-04 09:40:05 | BUILDING PLAN REVIEW |
| | PERMIT: 11070370 |
| | ADD: 420 COLUMBIA # 111 |
| | CONT: AUTOBUILDERS |
| | TEL: (561)622-3515 |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW COVER SHEET CODE RESEARCH MEANS OF |
| | EGRESS WITH TRAVEL LESS THAN 75'-0". SHEET A-1.0 PLEASE |
| | TAKE THE TRAVEL DISTANCE FROM ONE FOOT OFF OF THE |
| | NORTH-EAST CORNER OF THE LOUNGE WALL, STAY 1'-0" OFF OF |
| | WALLS FOR TRAVEL DISTANCE UNTIL YOU REACH THE FRONT |
| | DOORS, THE LEAST AMOUNT OF TRAVEL DISTANCE THAT I |
| | MEASURED IS APPROXIMATELY 78'. IF YOU CAN ILLUSTRATE |
| | YOUR TRAVEL DISTANCE LESS THAN 75'-0" THEN ONLY ONE |
| | MEANS OF EGRESS IS REQUIRED. IT APPEARS THAT THE LOUNGE |
| | DOOR LEADING TO THE EXTERIOR (DOOR 107A) WILL BE |
| | REQUIRED AS A SECOND EXIT SINCE THIS IS A UNSPRINKERED |
| | BUILDING THE 100 FOOT EXCEPTION CAN NOT BE APPLIED. |
| | 2007/09 FBC-B 1014.3, SEE COMMENTARY WHERE YOU CAN NOT |
| | TAKE DIAGONAL ROUTES ACROSS ROOMS. THE REASONING IS IF |
| | THE BUILDING IS FILLED WITH SMOKE YOU WILL NEED TO |
| | TOUCH THE WALLS TO FIND YOUR WAY TO AN EXIT, IF |
| | FURNITURE IS IN THE WAY YOU WILL ALSO NEED TO GO AROUND |
| | SUCH OBSTRUCTIONS. |
| | |
| | 2) PLEASE REVIEW SHEET A-2.0 DETAILS 1 & 2 RECEPTION |
| | DESK MUSST MEET TTHE REQUIREMENTS OF 11-7.2 SERVICE |
| | COUNTERS AND OR INFORMATION COUNTERS. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |