Plan Review Details - Permit 11070343
Plan Review Stops For Permit 11070343
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-10-13 Cont ID  
Sent By jwitmer Date 2011-10-13 Time 08:16 Rev Time 1.50
Received By jwitmer Date 2011-10-13 Time 08:16 Sent To  
Notes
2011-10-13 08:29:35BUILDING PLAN REVIEW
 PERMIT: 11070343
 ADD: 1015 N DIXIE HWY
 CONT: LS INVESTMENTS
 TEL: (561) 282-5692
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 10/13/2011
 ACTION: DENIED
  
 NOTE ONLY ONE SET OF PLANS!!!!
  
 1) THE PLANS SUBMITTED FROM PE JOHN GRIFFIN HAVE
 DISCREPANCIES BETWEEN THE CODE SUMMARY AND CODE
 TABULATION. THE CODE SUMMARY INDICATES THIS TO BE A
 BUSINESS OCCUPANCY WHERE AS THE CODE SUMMARY INDICATES
 THE USE AS A SINGLE STORY, CMU BUILDING USE GROUP A-3
 AMUSEMEENT ARCADE. 106.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. FOR THIS REVIEW THE OCCUPANCY TYPE WILL BE
 BUSINESS PROFESSIONAL SERVICES PHYSICAL THERAPY.
  
 COMMERCIAL BUILDINGS:
 2.SEMI COMPLIED WHICH TYPE OF OCCUPANCY SEE COMMENT# 1.
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 3.SEMI- COMPLIED. PLANS INDICATE A TYPE III BUILDING A
 OR B? PLANS INDICATE THE AREA IN THE TENANT SPACE NOT
 TTHE BUILDING FOOTPRINT WHICH WOULD NEED TO BE KNOWN
 FOR TABLE 503.
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 4A) FIRE-RESISTANT SEPARATIONS THE PLANS NOW INDICATE
 TENANT SEPERATION WALLS BUT NO TENANT SEPERATIONIS
 SHOWN.
  
 4B) FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 NOT KNOWN IF IT IS A TYPE III A OR B?
  
 5) PROTECTION OF OPENINGS AND PENETRATIONS OF RATED
 WALLS FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED
 FIRE RESISTANCE
  
 6. COMPLIED. LIFE SAFETY SYSTEMS SHALL BE DETERMINED
 AND SHALL INCLUDE THE FOLLOWING REQUIREMENTS: OCCUPANT
 LOAD AND EGRESS CAPACITIES.
  
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 7A) COMPLIED. OCCUPANCY LOAD
 7B) COMPLIED. GROSS/ NET
 7C)MEANS OF EGRESS:
 7C)(1) EXIT ACCESS
 7C)(2) EXIT -THE PLANS INDICATE A VERTICAL EXIT THAT
 ENDS WITHIN THE TENANT SPACE WITH NO ENCLOSURE, FBC-B
 1020.1 THE 2 EXCEPTIONS THAT POSSIBLY WOULD BE
 CONSIDERED ARE
 EXCEPTION #1 WHICH WOULD REQUIRE A OCCUPANT LOAD OF
 LESS THAN 10. THE SECOND EXCEPTION IS (8) WHICH WOULD
 ALLOW 50 % OF THE EGRESS STAIRS SERVING ONE ADJACENT
 FLOOR ARE NOT ENCLOSED, PROVIDED AT LEAST 2 MEANS OF
 EGRESS ARE PROVIDED FROM BOTH FLOORS SERVED BY THE
 UNENCLOSED STAIRWAY.
 7C)(3) STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION: SEE
 COMMENT ABOVE.
 7C)(4) EXIT DISCHARGE THE PLANS DO NOT INDICATE THE
 LOCATION OF EITHER STAIRWAYS EXIT DISCHARGE? FBC-B
 1024.
 7C)(5) DOORS PLANS INDICATE A DOOR DETAIL WITH A 2'-8"
 DOOR AND 32" CLEAR COMPLYING WITH A.D.A. REQUIREMENTS.
 PLEASE REVIEW FBC-B 1008.1.1 THE MINIMUM REQUIREMENT
 FOR A
 SWING DOOR WOULD BE 34" A CLEAR OPENING OF 32". ALSO
 SEE 11-4.13.5 CLEAR WIDTH AND 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS, 11-4.19.3 CLEAR FLOOR SPACE AND
 11-4.22.3 CLEAR FLOOR SPACE.
 7C)(6) EMERGENCY LIGHTING AND EXIT SIGNS FBC-B
 1006.1.6.
  
 7C)(7) SPECIFIC OCCUPANCY REQUIREMENTS PLEASE REVIEW 2
 STORY BUILDINGS, NOT FIRE SPRINKLERED, THAT WILL
 REQUIRE VERTICAL ACCESSIBILITY BECAUSE OF CHANGE IN
 OCCUPANCY AND THE REQUIREMENT FOR AREA OF RESCUE
 ASSISTANCE.
  
 2) CHANGE OF OCCUPANCY FOR A PORTION OF A BUILDING
 SHALL COMPLY WITH 2007/09 EXISTING BUILDING CODE
 CHAPTER 9, SECTION 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY.
  
 1. THE DESIGNER OF RECORD WILL NEED TO DETERMINE IF
 THIS BUILDING HAS CHANGE OF OCCUPANCY CLASSIFICATION
 WITH OR WITHOUT SEPERATION. 2007 EXST BLD 912.1.1.1/
 912.1.1.2
  
 2. 912.1.2 FIRE PROTECTION AND INTERIOR FINISH.
  
 3. 912.1.4 ACCESSIBILITY SHALL COMPLY WITH EXT BLD
 912.8. PLEASE ALSO REVIEW 2007 FBC-B 11-4.3.11 AREA OF
 RESCUE ASSISTANCE.
  
 4. EXT BLD 912.2.1 FIRE SPRINKLER SYSTEMS
  
 5. EXT BLD 912.2.2 FIRE ALARM & DETECTION
  
 6) EXT BLD 912.3 INTERIOR FINISHES
  
 7) 912.4.2 MEANS OF EGRESS FOR CHANGE OF USE TO EQUAL
 OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 CLASSIFICATION IS MADE TO AN EQUAL OR LESSER HAZARD
 CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE 912.4,
 EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 805 FOR THE NEW
 OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 EXCEPTION: ANY STAIRWAY REPLACING AN EXISTING STAIRWAY
 WITHIN A SPACE WHERE THE PITCH OR SLOPE CANNOT BE
 REDUCED BECAUSE OF EXISTING CONSTRUCTION SHALL BE
 PERMITTED FOR CONTINUED USE SUBJECT TO APPROVAL OF THE
 BUILDING CODE OFFICIAL. ALSO, SEE SECTION 1001.4 OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
 8) 912.4.3 EGRESS CAPACITY. EGRESS CAPACITY SHALL MEET
 OR EXCEED THE OCCUPANT LOAD AS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY.
  
 9) 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY
 WITH THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE
 AREA OF THE CHANGE OF OCCUPANCY CLASSIFICATION.
  
 10) 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH
 THE REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
  
  
 11) 912.7 ENCLOSURE OF VERTICAL SHAFTS. ENCLOSURE OF
 VERTICAL SHAFTS SHALL BE IN ACCORDANCE WITH SECTIONS
 912.7.1 THROUGH 912.7.4.
  
 12) 912.7.1 MINIMUM REQUIREMENTS. VERTICAL SHAFTS SHALL
 BE DESIGNED TO MEET THE FLORIDA BUILDING CODE, BUILDING
 REQUIREMENTS FOR ATRIUMS OR THE REQUIREMENTS OF THIS
 SECTION.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 14) A CONTRACTOR WILL NEED TO SIGN ONTO THE PERMIT, NO
 REALETOR CAN PULL A PERMIT FOR LIFE SAFETYT ISSUE AND
 BECAUSE OF THE DOLLAR AMOUNT THAT WILL BE EXCEEDED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-18 Cont ID  
Sent By jwitmer Date 2011-07-18 Time 16:52 Rev Time 1.00
Received By jwitmer Date 2011-07-18 Time 15:47 Sent To  
Notes
2011-07-18 16:32:02BUILDING PLAN REVIEW
 PERMIT: 11070343
 ADD: 1015 N DIXIE HWY
 CONT: LS INVESTMENTS
 TEL: (561) 282-5692
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES A CHANGE OF USE
 FROM ROOMING HOUSE(R-1 TRANSIENT OR R-2 NON-TRANSIENT)
 TO A BUSINESS OCCUPANCY. THE ONE SHEET PROVIDED IS
 CONCEPTUAL IN NATURE, 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).
  
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION PLAN;
 FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:
 106.3.5
 COMMERCIAL BUILDINGS:
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
 HORIZONTAL EXITS/EXIT PASSAGEWAYS
 FIRE SPRINKLERS
 TENANT SEPERATION WALLS
  
 2) CHANGE OF OCCUPANCY FOR A PORTION OF A BUILDING
 SHALL COMPLY WITH 2007/09 EXISTING BUILDING CODE
 CHAPTER 9, SECTION 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY.
  
 1. THE DESIGNER OF RECORD WILL NEED TO DETERMINE IF
 THIS BUILDING HAS CHANGE OF OCCUPANCY CLASSIFICATION
 WITH OR WITHOUT SEPERATION. 2007 EXST BLD 912.1.1.1/
 912.1.1.2
  
 2. 912.1.2 FIRE PROTECTION AND INTERIOR FINISH.
  
 3. 912.1.4 ACCESSIBILITY SHALL COMPLY WITH EXT BLD
 912.8. PLEASE ALSO REVIEW 2007 FBC-B 11-4.3.11 AREA OF
 RESCUE ASSISTANCE.
  
 4. EXT BLD 912.2.1 FIRE SPRINKLER SYSTEMS
  
 5. EXT BLD 912.2.2 FIRE ALARM & DETECTION
  
 6) EXT BLD 912.3 INTERIOR FINISHES
  
 7) 912.4.2 MEANS OF EGRESS FOR CHANGE OF USE TO EQUAL
 OR LOWER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 CLASSIFICATION IS MADE TO AN EQUAL OR LESSER HAZARD
 CATEGORY (HIGHER NUMBER) AS SHOWN IN TABLE 912.4,
 EXISTING ELEMENTS OF THE MEANS OF EGRESS SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 805 FOR THE NEW
 OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 EXCEPTION: ANY STAIRWAY REPLACING AN EXISTING STAIRWAY
 WITHIN A SPACE WHERE THE PITCH OR SLOPE CANNOT BE
 REDUCED BECAUSE OF EXISTING CONSTRUCTION SHALL BE
 PERMITTED FOR CONTINUED USE SUBJECT TO APPROVAL OF THE
 BUILDING CODE OFFICIAL. ALSO, SEE SECTION 1001.4 OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
 912.4.3 EGRESS CAPACITY. EGRESS CAPACITY SHALL MEET OR
 EXCEED THE OCCUPANT LOAD AS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY.
  
 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH
 THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA
 OF THE CHANGE OF OCCUPANCY CLASSIFICATION.
  
 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH THE
 REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 912.7 ENCLOSURE OF VERTICAL SHAFTS. ENCLOSURE OF
 VERTICAL SHAFTS SHALL BE IN ACCORDANCE WITH SECTIONS
 912.7.1 THROUGH 912.7.4.
  
 912.7.1 MINIMUM REQUIREMENTS. VERTICAL SHAFTS SHALL BE
 DESIGNED TO MEET THE FLORIDA BUILDING CODE, BUILDING
 REQUIREMENTS FOR ATRIUMS OR THE REQUIREMENTS OF THIS
 SECTION.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2011-10-13 Cont ID  
Sent By rlecky Date 2011-10-13 Time 17:48 Rev Time 0.00
Received By rlecky Date 2011-10-13 Time 17:48 Sent To  
Notes
2011-10-13 17:50:13PLANS DENIED. NO ELECTRICAL PLAN. SEE COMMENTS FROM
 EARLIER REVIEW.
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-18 Cont ID  
Sent By rlecky Date 2011-07-18 Time 14:54 Rev Time 0.00
Received By rlecky Date 2011-07-18 Time 14:44 Sent To  
Notes
2011-07-18 14:54:09ELECTRICAL PLAN REQUIRED. PLEASE PROVIDE THE FOLLOWING:
  
 INDICATE THE SIZE, RATING, VOLTAGE, LOCATION OF THE
 EXISTING SERVICE, MAIN DISCONNECTS AND PANELBOARD.
 PROVIDE PANEL SCHEDULES AND LOAD CALCULATION. PROVIDE
 AN ELECTRICAL RISER DIAGRAM. INCLUDE NEW AND EXISTING
 LOADS. SHOW NEW AND EXISTING ELECTRICAL OUTLETS. NEC
 215.5
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 FBC 13-415 ABC.1.2. SPACE CONTROL; 13412.ABC.1.3
 ADDITIONAL CONTROLS
 SHOW EXIT SIGNS AND EMERGENCY LIGHTING. FBC 1006
 SHOW GFCI PROTECTION ON APPROPRIATE OUTLETS. NEC 210.8
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-10-20 Cont ID  
Sent By wjolin Date 2011-10-20 Time 10:54 Rev Time 0.00
Received By wjolin Date 2011-10-20 Time 10:18 Sent To  
Notes
2011-10-20 10:53:001011 NORTH DIXIE HIGHWAY
 PERMIT #11070343
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET 1 INDICATES BOTH A BUSINESS AND ASSEMBLY
 OCCUPANCY.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2006. INDICATE THE ADJACENT
 OCCUPANCY TYPES.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 INDICATE IF THE EXISTING FIRE SPRINKLER OR EXISTING
 FIRE ALARM SYSTEM IS BEING UTILIZED IN THIS SPACE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-07-20 Cont ID  
Sent By wjolin Date 2011-07-20 Time 14:17 Rev Time 0.00
Received By wjolin Date 2011-07-20 Time 13:55 Sent To  
Notes
2011-07-20 14:17:281011 NORTH DIXIE HIGHWAY
 PERMIT #11070343
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION: NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANT LOADS,
 FIRE RATED WALLS, EXIT SIGNS, EMERGENCY LIGHTING,
 TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2006. INDICATE THE ADJACENT
 OCCUPANCY TYPES.
  
 INDICATE THE EGRESS ROUTES FOR THE ADJACENT TENANT
 SPACES THAT SHARE THE SECOND FLOOR.
  
 INDICATE ON THE PLANS IF THE REAR PATIO AND REAR STAIR
 ARE ENCLOSED OR OPEN.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 INDICATE IF THE EXISTING FIRE SPRINKLER OR EXISTING
 FIRE ALARM SYSTEM IS BEING UTILIZED IN THIS SPACE.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2011-11-01 Time   Rev Time 0.00
Received By shill Date 2011-10-12 Time 14:22 Sent To  
Notes
2011-10-12 14:23:04* * * * * EXPEDITED * * * * *
 B21
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-10-12 Cont ID  
Sent By shill Date 2011-08-08 Time 14:05 Rev Time 0.00
Received By shill Date 2011-07-14 Time 15:48 Sent To  
Notes
2011-07-14 15:52:58*****************EXPEDITED********************
 B--9

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2011-10-13 Time 09:02 Sent To  
Notes
2011-10-13 09:02:13BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2011-11-01 Cont ID  
Sent By rregueir Date 2011-11-01 Time 11:28 Rev Time 0.00
Received By rregueir Date 2011-10-26 Time 15:14 Sent To  
Notes
2011-11-01 11:33:57REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PREVIOUS REVIEW COMMENT NOT ADDRESSED.
  
 THIS IS A PROPOSED CHANGE OF OCCUPANCY. NO INFORMATION
 WAS PROVIDED REGARDING EXISTING OR PROPOSED NEW
 VENTILATION SYSTEM. SHOW HOW THE VENTILATION
 REQUIREMENTS FOR THE NEW OCCUPANCY ARE TO BE PROVIDED
 IN ACCORDANCE WITH FBC-EB SECTION 909.1 AND FBC-M
 SECTION 403. IF THE VENTILATION REQUIREMENTS FOR THE
 NEW OCCUPANCY ARE LESS OR EQUAL TO THE PREVIOUS
 OCCUPANCY, PROVIDE AN ANLYSIS BASED ON THE REQUIREMENTS
 OF FBC-M SECTION 403.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-07-20 Cont ID  
Sent By hmoser Date 2011-07-20 Time 08:13 Rev Time 0.00
Received By hmoser Date 2011-07-20 Time 08:13 Sent To  
Notes
2011-07-20 08:17:15PLANS DENIED
 CHANGE OF OCCUPANCY , NO MECHANICAL PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2011-10-21 Cont ID  
Sent By lwagner Date 2011-10-21 Time 14:51 Rev Time 0.00
Received By lwagner Date 2011-10-21 Time 14:25 Sent To  
Notes
2011-10-21 14:34:08FBC 2007 PLUMBING REVIEW #2
 DENIED:
  
 1. 403.1 MINIMUM REQUIRED FIXTURES. ALL COMMERCIAL
 OCCUPANCY TYPES REQUIRE A DRINKING FOUNTAIN. (SEE TABLE
 403.1).
  
 2. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 PLUMBING
  
 1. MINIMUM PLUMBING FACILITIES
  
 2. FIXTURE REQUIREMENTS
  
 3. WATER SUPPLY PIPING
  
 4. SANITARY DRAINAGE
  
 5. WATER HEATERS
  
 6. VENTS.......
  
 13. PLUMBING RISER
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-07-22 Cont ID  
Sent By lwagner Date 2011-07-22 Time 07:37 Rev Time 0.00
Received By lwagner Date 2011-07-21 Time 14:33 Sent To  
Notes
2011-07-22 07:37:06FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 NOT ENOUGH INFORMATION TO DO A PLUMBING REVIEW.
 NO PLUMBING PLANS WERE SUBMITTED.
 SEE BUILDING REVIEW.
  
 ***NOTE****
 403.1 BUSINESS OCCUPANCIES REQUIRE A DRINKING FOUNTAIN

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By astelly Date   Time 17:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2011-08-08 Cont ID  
Sent By lmartine Date 2011-08-08 Time 14:42 Rev Time 0.00
Received By lmartine Date 2011-08-08 Time 14:42 Sent To  
Notes
2011-08-08 14:43:20REVIEW NOT REQUIRED PER ANA