Plan Review Details - Permit 11070321
Plan Review Stops For Permit 11070321
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2012-02-02 Cont ID  
Sent By jgomez Date 2012-02-02 Time 09:07 Rev Time 0.00
Received By jgomez Date 2012-02-02 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2012-01-26 Cont ID  
Sent By jgomez Date 2012-01-26 Time 08:59 Rev Time 0.00
Received By jgomez Date 2012-01-26 Time 08:59 Sent To  
Notes
2012-01-26 08:59:44RESIDENTIAL (R2) REPAIRS FOURTH BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PLEASE PROVIDE COMPLETE WALL SECTION DETAIL THRU THE
 BALCONY TO BE REPLACED. PROVIDE COMPLETE DETAIL/SECTION
 AND SPECIFICATIONS. SPECIFY ALL MATERIALS, FASTENING,
 ETC. SEC. 106.1.1 CITY AMENDMENTS TO FBC TO VERIFY
 COMPLIANCE WITH ALL THE LOADS REQUIRED BY SEC. 1603 FBC
 2007.
  
 *** ENGINEER OF RECORD RESPONDED "DECKING AS SELECTED
 BY OWNER". DECKING IS PART OF THE BALCONY ASSEMBLY.
 ENGINEER NEEDS TO SPECIFY MATERIAL TYPE, SIZE AND
 FASTENING METHOD TO SHOW COMPLIANCE WITH ALL THE DESIGN
 LOADS REQUIRED BY THE CODE SECTIONS LISTED ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER.
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-01-09 Cont ID  
Sent By jgomez Date 2012-01-09 Time 16:33 Rev Time 0.00
Received By jgomez Date 2012-01-09 Time 16:32 Sent To  
Notes
2012-01-09 16:33:41RESIDENTIAL (R2) REPAIRS THIRD BUILDING REVIEW
 COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEER DRAWINGS SUBMITTED ARE ONLY FOR CONDO UNIT
 #1 OF BUILDING A. THERE ARE 8 DIFFERENT PERMIT
 APPLICATIONS FOR WORK TO BE PERFORMED ON 8 DIFFERENT
 CONDO UNITS. PLEASE PROVIDE DRAWINGS IDENTIFYING THE
 SCOPE OF WORK TO BE PERFORMED ON EACH UNIT. REVISE ALL
 THE INFORMATION ON PLANS AS REQUIRED. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  
 *** SAME DRAWINGS WERE SUBMITTED WITHOUT IDENTIFYING
 ALL UNITS INVOLVED IN THESE REPAIRS.
  
 2- PLEASE REVISE THE BUILDING CODE INFORMATION SHOWN ON
 SHEET C-1: THE OCCUPANCY GROUP IS R2 NOT R3. REVISE AS
 REQUIRED.
  
 *** ENGINEER NEEDS TO REVISE ORIGINAL DRAWINGS. PLANS
 SUBMITTED ARE THE SAME ONES THAT WERE SUBMITTED ON
 PREVIOUS REVIEW. THEY HAVE HAND WRITTEN REVISIONS NOT
 DONE BY THE ENGINEER RESPONSIBLE FOR THE PLANS. ALSO,
 PLANS SUBMITTED ARE MISSING THE ENGINEER'S SEAL AND THE
 SIGNATURE MUST BE ORIGINAL NOT COPY. CHAPTER 471
 FLORIDA STATUTE.
  
 3- PLEASE PROVIDE COMPLETE WALL SECTION DETAIL THRU THE
 BALCONY TO BE REPLACED. PROVIDE COMPLETE DETAIL/SECTION
 AND SPECIFICATIONS. SPECIFY ALL MATERIALS, FASTENING,
 WATERPROOFING, ETC. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 *** ENGINEER OF RECORD DIDN'T PROVIDE ANY DRAWINGS.
  
 4- PLEASE PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR
 THE BALCONY GUARDRAIL TO BE REPLACED TO SHOW COMPLIANCE
 WITH SEC. 1013 AND SEC. 1607.7 FBC 2007.
  
 ***ENGINEER OF RECORD DIDN'T PROVIDE ANY DRAIWGNS
  
 5- ENTRY DOOR NOA 08-1015.05 SUBMITTED DOESN'T MATCH
 NOA 07--0618.10 SPECIFIED BY THE ENGINEER ON SHEET A-2.
 REVISE AS REQUIRED TO MATCH.
  
 *** ENGINEER DIDIN'T REVISE PLANS.
  
 6- NOTICE OF COMMENCEMENT SIGNATURE WAS CLARIFIED.
  
 7- PLEASE UPDATE VALUATION TO INCLUDE ALL SCOPE OF WORK
 SHOWN ON PLANS. INCLUDE THE DOORS/WINDOWS REPLACEMENT,
 NEW DECK AND GUARDRAIL AND PROFESSIONAL ENGINEER FEES
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC.
 PERMIT TYPE AND FEES TO BE ADJUSTED ACCORDINGLY.
  
 *** VALUATION WAS NOT UPDATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-11-29 Cont ID  
Sent By jgomez Date 2011-11-29 Time 15:54 Rev Time 0.00
Received By jgomez Date 2011-11-29 Time 15:54 Sent To  
Notes
2011-11-29 15:55:05RESIDENTIAL (R2) REPAIRS BUILDING REVIEW COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEER DRAWINGS SUBMITTED ARE ONLY FOR CONDO UNIT
 #1 OF BUILDING A. THERE ARE 8 DIFFERENT PERMIT
 APPLICATIONS FOR WORK TO BE PERFORMED ON 8 DIFFERENT
 CONDO UNITS. PLEASE PROVIDE DRAWINGS IDENTIFYING THE
 SCOPE OF WORK TO BE PERFORMED ON EACH UNIT. REVISE ALL
 THE INFORMATION ON PLANS AS REQUIRED. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  
 2- PLEASE REVISE THE BUILDING CODE INFORMATION SHOWN ON
 SHEET C-1: THE OCCUPANCY GROUP IS R2 NOT R3. REVISE AS
 REQUIRED.
  
 3- PLEASE PROVIDE COMPLETE WALL SECTION DETAIL THRU THE
 BALCONY TO BE REPLACED. PROVIDE COMPLETE DETAIL/SECTION
 AND SPECIFICATIONS. SPECIFY ALL MATERIALS, FASTENING,
 WATERPROOFING, ETC. SEC. 106.1.1 CITY AMENDMENTS TO FBC
  
 4- PLEASE PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR
 THE BALCONY GUARDRAIL TO BE REPLACED TO SHOW COMPLIANCE
 WITH SEC. 1013 AND SEC. 1607.7 FBC 2007.
  
 5- ENTRY DOOR NOA 08-1015.05 SUBMITTED DOESN'T MATCH
 NOA 07--0618.10 SPECIFIED BY THE ENGINEER ON SHEET A-2.
 REVISE AS REQUIRED TO MATCH.
  
 6- PLEASE CLARIFY IF THE CONTRACTOR IS ALSO THE
 PRESIDENT OF THE CONDO ASSOCIATION AND IS THE ONE
 AUTHORIZED TO SIGN THE NOTICE OF COMMENCEMENT. PLEASE
 PROVIDE DOCUMENTATION.
  
 7- PLEASE UPDATE VALUATION TO INCLUDE ALL SCOPE OF WORK
 SHOWN ON PLANS. INCLUDE THE DOORS/WINDOWS REPLACEMENT,
 NEW DECK AND GUARDRAIL AND PROFESSIONAL ENGINEER FEES
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC.
 PERMIT TYPE AND FEES TO BE ADJUSTED ACCORDINGLY
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-20 Cont ID  
Sent By jgomez Date 2011-07-20 Time 17:05 Rev Time 0.00
Received By jgomez Date 2011-07-20 Time 17:05 Sent To  
Notes
2011-07-20 17:06:14RESIDENTIAL (R2) WINDOW/DOOR REPLACEMENT BUILDING
 REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- MISSING PLANS SPECIFIED ON THE PERMIT APPLICATION.
 PROVIDE PLANS SHOWING THE WINDOWS AND DOORS TO BE
 REPLACED AND THE DETAILS/SPECIFICATIONS FOR FRAME
 SUPPORT STRUCTURAL REPAIRS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC.
  
 2- SPECIFY TYPE AND SIZE OF EXISTING BEDROOM WINDOWS
 AND TYPE AND SIZE OF NEW WINDOWS TO VERIFY COMPLIANCE
 WITH THE EMERGENCY EGRESS REQUIREMENTS.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
  
 A) HORIZONTAL ROLLING WINDOW. NOA 09-0105.02 SUBMITTED
 WAS SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE
 WEBSITE AND DOWNLOAD CURRENT NOA.
  
 B) SLIDING GLASS DOOR. NOA 09-0324.16 SUBMITTED WAS
 SUPERSEDED ALSO BY MIAMI-DADE. NEED CURRENT NOA.
  
 C) FIXED WINDOW. NOA 10-0930.04 SUBMITTED IS FOR
 NON-IMPACT GLASS. NEED TO PROVIDE GLASS PROTECTION AS
 REQUIRED BY SEC. 1609.1.2 FBC. PROVIDE NOA WITH IMPACT
 GLASS OR PROVIDE INFORMATION FOR SHUTTERS.
  
 D) HURRICANE SHUTTERS IF FIXED WINDOW HAS NO IMPACT
 GLASS. IN ADDITION PROVIDE COMPLETE SHUTTERS
 INSTALLATION SCHEDULE AND MARK ON SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITION (EX: WALL MOUNTED) AND
 ANCHOR TYPE AND SPACING TO BE USED. SEE CITY POLICY FOR
 SHUTTERS INSTALLATION.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2012-02-02 Cont ID  
Sent By jgomez Date 2012-02-02 Time 09:06 Rev Time 0.00
Received By jgomez Date 2012-02-02 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-01-26 Cont ID  
Sent By jgomez Date 2012-01-26 Time 08:59 Rev Time 0.00
Received By jgomez Date 2012-01-26 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-01-09 Cont ID  
Sent By jgomez Date 2012-01-09 Time 16:33 Rev Time 0.00
Received By jgomez Date 2012-01-09 Time 16:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-29 Cont ID  
Sent By jgomez Date 2011-11-29 Time 15:54 Rev Time 0.00
Received By jgomez Date 2011-11-29 Time 15:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-20 Cont ID  
Sent By jgomez Date 2011-07-20 Time 17:06 Rev Time 0.00
Received By jgomez Date 2011-07-20 Time 17:06 Sent To  
Notes
***NONE***