Plan Review Details - Permit 11070290
Plan Review Stops For Permit 11070290
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-09-19 Cont ID  
Sent By jwitmer Date 2011-09-19 Time 14:01 Rev Time 0.55
Received By jwitmer Date 2011-09-19 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-18 Cont ID  
Sent By jwitmer Date 2011-07-18 Time 10:09 Rev Time 1.33
Received By jwitmer Date 2011-07-15 Time 10:49 Sent To  
Notes
2011-07-18 10:32:16BUILDING PLAN REVIEW
 PERMIT: 11070290
 ADD: 1120 13TH ST
 CONT: GENERAL ENGINEERING & DEVELOPMENT
 TEL: (561)509-4000
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
  
 1) COVER SHEET INDICATES A MIXED USE OCCUPANCY AS
 BUSINESS/ DAYCARE PLEASE INDICATE WHERE THE BUSINESS
 PORTION OF THE MIXED USE OCCUPANCY IS LOCATED. THE
 PLANS APPEAR TO BE A DAYCARE OCCUPANCY PER 2007/ 09
 FBC-B 202 DEFINITIONS AND SECTION 436 OF THE FBC-B.
  
 2) PLEASE REVIEW THE OCCUPANT LOADS VERSES SQ FT, COVER
 SHEET SEE FBC-B TABLE 1004.1.1DAYCARE 20 NET
  
 3) OF THE OCCUPANT LOAD FOR THE DAYCARE OCCUPANCY HOW
 MANY OF THE OCCUPANTS (CLIENTS) WILL BE 24 MONTHS OLD
 OR LESS IN AGE ? 2007/09 FBC-B 436.2.
  
 4) PLEASE UPDATE PLANS TO COMPLY WITH :
 4A) 436.2 CLOSET DOORS. EVERY CLOSET DOOR LATCH SHALL
 BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE
 CLOSET.
  
 4B) 436.3 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE
 SHALL BE READILY ACCESSIBLE TO THE STAFF.
  
 4C) 436.4 DOOR CLOSURE. ANY EXIT DOOR DESIGNED TO BE
 NORMALLY CLOSED SHALL BE KEPT CLOSED AND SHALL COMPLY
 WITH SECTION 715.3.
  
 5) 2007/09 FBC-B 436.1 & 436.2 PLEASE PROVIDE
 INFORMATION ON ROOMS OR AREAS OF CONCERN SINCE THEY ARE
 NOT INDICATED ON THE PLANS:
 5A) 436.1(3.) ROOMS OR SPACES USED FOR THE STORAGE OF
 HAZARDOUS MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS
 IN QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS.
  
 5B) 436.1(4) JANITOR CLOSETS.
  
 5C) 436.6.2 ( 1.) LAUNDRIES.
  
 5D) 436.2 (4.) ROOMS OR SPACES USED FOR PROCESSING OR
 USE OF HAZARDOUS MATERIALS (CLEANING PRODUCTS) OR
 FLAMMABLE OR COMBUSTIBLE LIQUIDS IN QUANTITIES DEEMED
 HAZARDOUS BY RECOGNIZED STANDARDS.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-09-13 Cont ID  
Sent By rlecky Date 2011-09-13 Time 15:10 Rev Time 0.00
Received By rlecky Date 2011-09-13 Time 15:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-20 Cont ID  
Sent By rlecky Date 2011-07-20 Time 09:24 Rev Time 0.00
Received By rlecky Date 2011-07-19 Time 11:00 Sent To  
Notes
2011-07-20 09:25:46PROVIDE AN ELECTRICAL PLAN. NEC 215.5
 MAXIMUM OVERCURRENT PROTECTION FOR #3 SERVICE
 CONDUCTORS AT MAIN DISCONNECT IS 100 AMPERES. NEC T.
 310.16
 ALL RECEPTACLES SHALL BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES IN BATHROOMS, KITCHEN AREAS AND OUTDOORS
 SHALL BE GFCI PROTECTED. NEC 210. 8
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-09-14 Cont ID  
Sent By mgonzale Date 2012-09-14 Time 15:30 Rev Time 0.00
Received By mgonzale Date 2012-09-14 Time 15:30 Sent To  
Notes
2012-09-14 15:31:25PLAN DOES NOT CONFLICT WITH CITY OF WPB PUBLIC
 UTILITIES.
  
 PLAN WILL REQUIRE A ROW PERMIT FOR OFF-SITE PARKING AND
 USE OF 15' ALLEYWAY.
  
 CONTACT CITY OF WEST PALM BEACH ENGINEERING SERVICES
 DEPARTMENT.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2011-09-06 Cont ID  
Sent By wjolin Date 2011-09-06 Time 08:42 Rev Time 0.00
Received By wjolin Date 2011-09-06 Time 08:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-07-21 Cont ID  
Sent By wjolin Date 2011-07-21 Time 13:56 Rev Time 0.00
Received By wjolin Date 2011-07-20 Time 16:45 Sent To  
Notes
2011-07-20 16:57:281120 13TH STREET
 PERMIT #11070290
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
  
 STRUCTURES WITH LIGHT FRAME ROOF TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING
 OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE
 EXTINGUISHER COMPANY.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2007.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B.
  
 JANITOR CLOSETS SHALL BE SEPARATED FROM THE REST OF THE
 BUILDING WITH A ONE-HOUR FIRE RESISTANCE RATING.
  
 EMERGENCY PLAN (EXIT LOCATIONS, EMERGENCY PHONE
 NUMBERS, ETC) TO BE DEVELOPED AND POSTED IN BUILDING
 PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-09-05 Cont ID  
Sent By jwitmer Date 2012-09-05 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2012-09-04 Time 14:53 Sent To  
Notes
2012-09-04 14:53:17GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-02-06 Cont ID  
Sent By astelly Date 2012-02-06 Time 08:22 Rev Time 0.00
Received By astelly Date 2011-12-22 Time 10:21 Sent To  
Notes
2011-12-22 10:21:40INCOMING SENT TO AMEY S. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-11-17 Cont ID  
Sent By shill Date 2011-10-01 Time 14:28 Rev Time 0.00
Received By shill Date 2011-08-30 Time 10:49 Sent To  
Notes
2011-08-30 10:49:57INCOMING SENT TO B-3 .JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-08-08 Cont ID  
Sent By lmartine Date 2011-08-08 Time 11:59 Rev Time 0.00
Received By lmartine Date 2011-07-14 Time 13:38 Sent To  
Notes
2011-07-14 13:38:57SENT TO SHELF B13 FOR ALL TRADES REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2012-09-05 Cont ID  
Sent By jwitmer Date 2012-09-05 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2012-09-05 Time 09:54 Sent To  
Notes
2012-09-05 09:57:04IMPACT FEES:
 RECEIPT # 2012-0803-115
 TRACKING# MU-2012-014194-0000
 FEES: $477.13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2011-07-18 Cont ID  
Sent By jwitmer Date 2011-07-18 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2011-07-18 Time 10:32 Sent To  
Notes
2011-07-18 10:32:54BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2011-09-07 Cont ID  
Sent By hmoser Date 2011-09-07 Time 11:39 Rev Time 0.00
Received By hmoser Date 2011-09-07 Time 11:12 Sent To  
Notes
2011-09-07 11:39:04REFER TO SECTION 602.2.1 MATERIALS EXPOSED WITHIN
 PLENUMS 2007 FBC(M) .
 IF MORE MECHANICAL WORK IS BEING DONE BESIDE BATH
 EXHAUST THE MECHANICAL CONTRACTOR MUST
 SUBMIT PLANS TO BE REVIEWED BY THE CITY.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2011-08-08 Cont ID  
Sent By hmoser Date 2011-08-08 Time 13:04 Rev Time 0.00
Received By hmoser Date 2011-08-08 Time 12:18 Sent To  
Notes
2011-08-08 13:03:25PLAN SUBMITTED IS FOR BATH EXHAUST ONLY.
 AIR CONDITIONING SHOWS EXISTING.
 REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2011-09-08 Cont ID  
Sent By lwagner Date 2011-09-08 Time 14:24 Rev Time 0.00
Received By lwagner Date 2011-09-08 Time 14:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2011-07-22 Cont ID  
Sent By lwagner Date 2011-07-22 Time 07:51 Rev Time 0.00
Received By lwagner Date 2011-07-21 Time 13:01 Sent To  
Notes
2011-07-21 13:16:06FBC 2007 PLUNBING REVIEW # 1
 DENIED:
  
 1. ONE SET OF PLANS THE DESIGNER OF RECORD IS A COPIED
 SIGNATURE AND MISSING THE ARCHITECT'S SEAL. SANDRA
 PUERTA, AR 95385. FL ADMINISTRATIVE RULE 61G-16.003
  
 2. COVER-SHEET PLUMBING FIXTURE CALULATIONS:
  
 2A) WILL NEED TO BE BASED ON THE CORRECT BUILDING CODE
 CLASSIFICATION OF DAYCARE OCCUPANCY, PLUMBING FIXTURE
 COUNT IS BASED ON A BUSINESS OCCUPANCY.
  
 2B) THE PLUMBING FIXTURE CALCULATIONS WILL NEED TO BE
 BASED ON THE CORRECTED OCCUPANCY LOAD OF 20 OCCUPANTS
 PER 2007/09 FBC-B TABLE 1004.1.1. INDICATE THE REQUIRED
 FIXTURES FOR A DAYCARE OCCUPANCY PER 2007/09 FBC-P
 TABLE 403.1(3)
 EDUCATIONAL/ DAYCARE.
  
 3) THE FLOOR PLAN ONLY SHOWS ONE RESTROOM THAT IS
 ACCESSIBLE, IN REVIEWING FBC-P
 TABLE 403.1(3) FOR BOTH MALE AND FEMALES 1/50 FOR BOTH
 WATER CLOSETS AND LAVS SO TWO ACCESSIBLE RESTROOMS WILL
 BE REQUIRED PER 403.2. 403.2 SEPARATE FACILITIES. WHERE
 PLUMBING FIXTURES ARE REQUIRED, SEPARATE FACILITIES
 SHALL BE PROVIDED FOR EACH SEX.
 THE BUSINESS EXCEPTION DOES NOT MEET THE CRITERIA, NO
 BUSINESS OCCUPANCY WAS INDICATED ON THE PLANS.
  
 4) PLANS ARE MISSING THE WATER SUPPLY PIPING ISOMETRIC
 PER 2007/09 106.5.1.3.
  
 5) PLANS FAIL TO INDICATE COMPLIANCE WITH 2007/09 FBC-P
 608.13 BACKFLOW PROTECTION. MEANS OF PROTECTION AGAINST
 BACKFLOW SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 608.13.1 THROUGH 608.13.9.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-02-06 Cont ID  
Sent By astelly Date 2012-02-06 Time 08:22 Rev Time 0.00
Received By astelly Date 2012-02-06 Time 08:22 Sent To  
Notes
2012-02-06 12:00:51AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PASSED W/ PROVISO
 DRIVE AISLE SHALL BE MEASURED AT 24 FT. FROM EDGE OF
 UTILITY POLE. 15.5 FT. OF PROVATE PROPERTY SHALL BE
 DEVOTED TO PAVED DRIVE AISLE. OUTDOOR PLAY AREA AND
 STUDENT CAPACITY MUST BE RE-CALCULATED.

Review Stop Z ZONING
Rev No 2 Status F Date 2011-10-01 Cont ID  
Sent By astelly Date 2011-10-01 Time 10:09 Rev Time 0.00
Received By astelly Date 2011-10-01 Time 10:09 Sent To  
Notes
2011-10-01 10:15:11AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 REPEAT COMMENTS:
  
 PLEASE PROVIDE A SURVEY OF THE PROPERTY.
  
 CIRCULATION TO PARKING SPACES THROUGH AN UN-PAVED ALLEY
 IS NOT ALLOWED.
  
 THE REQUIRED PARKING FOR DAYCARES IS ONE (1) SPACE PER
 EMPLOYEE PLUS FIVE (5) VISITOR SPACES. A MINIMUM OF
 SEVEN (7) SPACES IS REQUIRED.
  
 LANDSCAPING MUST BE INSTALLED PER SEC. 94-443
  
 A SIGNED AND SEALED LANDSCAPE PLAN MUST BE SUBMITTED
 PER SEC. 94-448
  
 LANDSCAPED TERMINAL ISLANDS ARE REQUIRED AT THE ENDS OF
 EACH PARKING ROW.
  
 THE GATE SHOWN ALONG CARVER AVE. IS NOT PERMITTED TO
 SWING INTO THE RIGHT-OF-WAY.
  
 THE CIRCULATION /PICK-UP AREA SHOWN ON THE PLAN
 INDICATES THAT GRASS WILL BE INSTALLED IN THE PAVEMENT
 AREA OF THE RIGHT-OF-WAY. THIS IS NOT ALLOWED. PLEASE
 SHOW PAVEMENT AREA AS IT EXISTS IN THE REVISED
 DRAWINGS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2011-07-29 Cont ID  
Sent By astelly Date 2011-07-29 Time 16:31 Rev Time 0.00
Received By astelly Date 2011-07-29 Time 16:31 Sent To  
Notes
2011-07-29 16:41:33AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 CIRCULATION TO PARKING SPACES THROUGH AN UN-PAVED ALLEY
 IS NOT ALLOWED.
 THE REQUIRED PARKING FOR DAYCARES IS ONE (1) SPACE PER
 EMPLOYEE PLUS FIVE (5) VISITOR SPACES. A MINIMUM OF
 SEVEN (7) SPACES IS REQUIRED.
 LANDSCAPING MUST BE INSTALLED PER SEC. 94-443
 A SIGNED AND SEALED LANDSCAPE PLAN MUST BE SUBMITTED
 PER SEC. 94-448
 LANDSCAPED TERMINAL ISLANDS ARE REQUIRED AT THE ENDS OF
 EACH PARKING ROW.
 THE CIRCULATION /PICK-UP AREA MUST ALSO BE SHOWN ON THE
 PLAN IN ACCORDANCE WITH TABLE XV-6 IN SEC. 94-486 OF
 THE ZONING CODE.
 THE GATE SHOWN ALONG CARVER AVE. IS NOT PERMITTED TO
 SWING INTO THE RIGHT-OF-WAY.