Plan Review Details - Permit 11070279
Plan Review Stops For Permit 11070279
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2011-08-29 Cont ID  
Sent By jwitmer Date 2011-08-29 Time 08:08 Rev Time 0.33
Received By jwitmer Date 2011-08-29 Time 08:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2011-08-10 Cont ID  
Sent By jwitmer Date 2011-08-10 Time 14:54 Rev Time 0.22
Received By jwitmer Date 2011-08-10 Time 14:54 Sent To  
Notes
2011-08-10 14:56:48BUILDING PLAN REVIEW
 PERMIT: 11070279
 ADD: 1009 N DIXIE HWY.
 CONT: PAUL BENNETT BUILDING
 CONTRACTOR # 685-5050
 CONTACT: BOB CARTER
 TEL: (561) 301-2588 CELL
 833-7529 BUS.
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW REVIEW
 ACTION: DENIED
  
 ONLY CHANGE IN PLANS IS THE ADDRESS, OTHER COMMENTS NOT
 ADDRESSED.
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) THE DESIGNER OF RECORD WILL NEED TO DECIDE IF THIS
 PROJECT IS TO BE DESIGNED AS A MIXED USE BUILDING USING
 THE NON-SEPERATION METHOD OR SEPERATION METHOD:
  
 NONSEPARATED OCCUPANCIES:
 508.3.2 NONSEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS
 OF BUILDINGS THAT COMPLY WITH THE PROVISIONS OF THIS
 SECTION SHALL QUALIFY AS NONSEPARATED OCCUPANCIES.
  
 508.3.2.1 OCCUPANCY CLASSIFICATION. NONSEPARATED
 OCCUPANCIES SHALL BE INDIVIDUALLY CLASSIFIED IN
 ACCORDANCE WITH SECTION 302.1. CODE REQUIREMENTS SHALL
 APPLY TO EACH PORTION OF THE BUILDING BASED ON THE
 OCCUPANCY CLASSIFICATION OF THAT SPACE EXCEPT THAT THE
 MOST RESTRICTIVE APPLICABLE PROVISIONS OF SECTION 403
 AND CHAPTER 9 SHALL APPLY TO THE ENTIRE BUILDING OR
 PORTION THEREOF.
  
 508.3.2.2 ALLOWABLE AREA AND HEIGHT. THE ALLOWABLE AREA
 AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE
 BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE
 OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION
 503.1.
  
 508.3.2.3 SEPARATION. NO SEPARATION IS REQUIRED BETWEEN
 OCCUPANCIES.
  
 EXCEPTION: GROUP H-2, H-3, H-4 OR H-5 OCCUPANCIES SHALL
 BE SEPARATED FROM ALL OTHER OCCUPANCIES IN ACCORDANCE
 WITH SECTION 508.3.3.
  
  
 OR
  
 2007/09 FBC-B 508.3.3 SEPERATION
 508.3.3 SEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS OF
 BUILDINGS THAT COMPLY WITH THE PROVISIONS OF THIS
 SECTION SHALL QUALIFY AS SEPARATED OCCUPANCIES.
  
 508.3.3.1 OCCUPANCY CLASSIFICATION. SEPARATED
 OCCUPANCIES SHALL BE INDIVIDUALLY CLASSIFIED IN
 ACCORDANCE WITH SECTION 302.1. EACH FIRE AREA SHALL
 COMPLY WITH THIS CODE BASED ON THE OCCUPANCY
 CLASSIFICATION OF THAT PORTION OF THE BUILDING.
  
 508.3.3.2 ALLOWABLE AREA. IN EACH STORY, THE BUILDING
 AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS OF THE
 ACTUAL FLOOR AREA OF EACH OCCUPANCY DIVIDED BY THE
 ALLOWABLE AREA OF EACH OCCUPANCY SHALL NOT EXCEED ONE.
  
 508.3.3.3 ALLOWABLE HEIGHT. EACH OCCUPANCY SHALL COMPLY
 WITH THE HEIGHT LIMITATIONS BASED ON THE TYPE OF
 CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION
 503.1. THE HEIGHT, IN BOTH FEET AND STORIES, OF EACH
 FIRE AREA SHALL BE MEASURED FROM GRADE PLANE. THIS
 MEASUREMENT SHALL INCLUDE THE HEIGHT, IN BOTH FEET AND
 STORIES, OF INTERVENING FIRE AREAS.
  
 EXCEPTION: SPECIAL PROVISIONS PERMITTED BY SECTION 509.
  
 508.3.3.4 SEPARATION. INDIVIDUAL OCCUPANCIES SHALL BE
 SEPARATED FROM ADJACENT OCCUPANCIES IN ACCORDANCE WITH
 TABLE 508.3.3.
  
  
 IF THTE DESIGNER OF RECORD DECIDES TO USE THE
 NON-SEPERATED METHOD THE FOLLOWING WILL NEED TO BE
 DEMONSTRATED.
 STEP 1. DETERMINE WHICH OCCUPANCY GROUPS
 CLASSIFICATIONS ARE IN THE BUILDING.
  
 STEP 2. DETERMINE THE MINIMUM BUILDING TYPE OF
 CONSTRUCTION BASED ON THE HEIGHT & AREA OF THE BUILDING
 FOR EACH OCCUPANCY GROUP IN ACCORDANCE WITH THIS
 CHAPTER AND TABLE 503. APPLY THE REQUIREMENTS FOR THE
 MOST STRINGENT TO THE ENTIRE BUILDING.
  
 STEP 3. APPLY THE MOST RESTRICTIVE PROVISIONS CONTAINED
 IN SECTION 403 ( NOT APPLICABLE) AND CHAPTER 9
 THROUGHOUT ALL NONSEPARATED USES (SECTION 508.3.2.1).
  
 STEP 4. APPLY ALL OTHER REQUIREMENTS OF THE CODE TO
 EACH OCCUPANCY INDIVIDUALLY BASED ON THE SPECIFIC
 OCCUPANCY OF EACH SPACE( E.G. MEANS OF EGRESS) (SECTION
 508.3.2.1).
  
 4) ELEVATED PLATFORMS SHALL COMPLY WITH:
 4A) 1003.5 ELEVATION CHANGE. CHANGE IN LEVEL IN THE
 MEANS OF EGRESS SHALL BE EITHER BY A RAMP OR A STAIR.
 THE PRESENCE AND LOCATION OF RAMPED WALKWAYS SHALL BE
 READILY APPARENT.
  
 4B) 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF EGRESS
 NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY A
 STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT. NOT SHOWN ON
 PLANS.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-20 Cont ID  
Sent By jwitmer Date 2011-07-20 Time 14:07 Rev Time 0.66
Received By jwitmer Date 2011-07-20 Time 14:07 Sent To  
Notes
2011-07-20 14:29:11BUILDING PLAN REVIEW
 PERMIT: 11070279
 ADD: 1009 N DIXIE HWY.
 CONT: TO BE DETERMINED
 CONTACT: BOB CARTER
 TEL: (561)301-2588 CELL
 833-7529 BUS.
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) A CONTRACTOR EITHER CGC OR CBC MUST SIGN ON TO THE
 PERMIT APPLICATION AND TAKE RESPONSIBILITY FOR THE
 PERMIT.
  
 2) PLEASE VERIFY WHICH OF THE ADDRESSES ARE CORRECT THE
 PERMIT APPLICATION OR THE PLANS. DISCREPANCY.
  
 3) THE DESIGNER OF RECORD WILL NEED TO DECIDE IF THIS
 PROJECT IS TO BE DESIGNED AS A MIXED USE BUILDING USING
 THE NON-SEPERATION METHOD OR SEPERATION METHOD:
  
 NONSEPARATED OCCUPANCIES:
 508.3.2 NONSEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS
 OF BUILDINGS THAT COMPLY WITH THE PROVISIONS OF THIS
 SECTION SHALL QUALIFY AS NONSEPARATED OCCUPANCIES.
  
 508.3.2.1 OCCUPANCY CLASSIFICATION. NONSEPARATED
 OCCUPANCIES SHALL BE INDIVIDUALLY CLASSIFIED IN
 ACCORDANCE WITH SECTION 302.1. CODE REQUIREMENTS SHALL
 APPLY TO EACH PORTION OF THE BUILDING BASED ON THE
 OCCUPANCY CLASSIFICATION OF THAT SPACE EXCEPT THAT THE
 MOST RESTRICTIVE APPLICABLE PROVISIONS OF SECTION 403
 AND CHAPTER 9 SHALL APPLY TO THE ENTIRE BUILDING OR
 PORTION THEREOF.
  
 508.3.2.2 ALLOWABLE AREA AND HEIGHT. THE ALLOWABLE AREA
 AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE
 BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE
 OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION
 503.1.
  
 508.3.2.3 SEPARATION. NO SEPARATION IS REQUIRED BETWEEN
 OCCUPANCIES.
  
 EXCEPTION: GROUP H-2, H-3, H-4 OR H-5 OCCUPANCIES SHALL
 BE SEPARATED FROM ALL OTHER OCCUPANCIES IN ACCORDANCE
 WITH SECTION 508.3.3.
  
  
 OR
  
 2007/09 FBC-B 508.3.3 SEPERATION
 508.3.3 SEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS OF
 BUILDINGS THAT COMPLY WITH THE PROVISIONS OF THIS
 SECTION SHALL QUALIFY AS SEPARATED OCCUPANCIES.
  
 508.3.3.1 OCCUPANCY CLASSIFICATION. SEPARATED
 OCCUPANCIES SHALL BE INDIVIDUALLY CLASSIFIED IN
 ACCORDANCE WITH SECTION 302.1. EACH FIRE AREA SHALL
 COMPLY WITH THIS CODE BASED ON THE OCCUPANCY
 CLASSIFICATION OF THAT PORTION OF THE BUILDING.
  
 508.3.3.2 ALLOWABLE AREA. IN EACH STORY, THE BUILDING
 AREA SHALL BE SUCH THAT THE SUM OF THE RATIOS OF THE
 ACTUAL FLOOR AREA OF EACH OCCUPANCY DIVIDED BY THE
 ALLOWABLE AREA OF EACH OCCUPANCY SHALL NOT EXCEED ONE.
  
 508.3.3.3 ALLOWABLE HEIGHT. EACH OCCUPANCY SHALL COMPLY
 WITH THE HEIGHT LIMITATIONS BASED ON THE TYPE OF
 CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION
 503.1. THE HEIGHT, IN BOTH FEET AND STORIES, OF EACH
 FIRE AREA SHALL BE MEASURED FROM GRADE PLANE. THIS
 MEASUREMENT SHALL INCLUDE THE HEIGHT, IN BOTH FEET AND
 STORIES, OF INTERVENING FIRE AREAS.
  
 EXCEPTION: SPECIAL PROVISIONS PERMITTED BY SECTION 509.
  
 508.3.3.4 SEPARATION. INDIVIDUAL OCCUPANCIES SHALL BE
 SEPARATED FROM ADJACENT OCCUPANCIES IN ACCORDANCE WITH
 TABLE 508.3.3.
  
  
 IF THTE DESIGNER OF RECORD DECIDES TO USE THE
 NON-SEPERATED METHOD THE FOLLOWING WILL NEED TO BE
 DEMONSTRATED.
 STEP 1. DETERMINE WHICH OCCUPANCY GROUPS
 CLASSIFICATIONS ARE IN THE BUILDING.
  
 STEP 2. DETERMINE THE MINIMUM BUILDING TYPE OF
 CONSTRUCTION BASED ON THE HEIGHT & AREA OF THE BUILDING
 FOR EACH OCCUPANCY GROUP IN ACCORDANCE WITH THIS
 CHAPTER AND TABLE 503. APPLY THE REQUIREMENTS FOR THE
 MOST STRINGENT TO THE ENTIRE BUILDING.
  
 STEP 3. APPLY THE MOST RESTRICTIVE PROVISIONS CONTAINED
 IN SECTION 403 ( NOT APPLICABLE) AND CHAPTER 9
 THROUGHOUT ALL NONSEPARATED USES (SECTION 508.3.2.1).
  
 STEP 4. APPLY ALL OTHER REQUIREMENTS OF THE CODE TO
 EACH OCCUPANCY INDIVIDUALLY BASED ON THE SPECIFIC
 OCCUPANCY OF EACH SPACE( E.G. MEANS OF EGRESS) (SECTION
 508.3.2.1).
  
 4) ELEVATED PLATFORMS SHALL COMPLY WITH:
 4A) 1003.5 ELEVATION CHANGE. CHANGE IN LEVEL IN THE
 MEANS OF EGRESS SHALL BE EITHER BY A RAMP OR A STAIR.
 THE PRESENCE AND LOCATION OF RAMPED WALKWAYS SHALL BE
 READILY APPARENT.
  
 4B) 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF EGRESS
 NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY A
 STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT. NOT SHOWN ON
 PLANS.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2011-08-25 Cont ID  
Sent By wjolin Date 2011-08-25 Time 15:33 Rev Time 0.00
Received By wjolin Date 2011-08-25 Time 15:33 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2011-08-11 Cont ID  
Sent By wjolin Date 2011-08-11 Time 12:30 Rev Time 0.00
Received By wjolin Date 2011-08-11 Time 12:20 Sent To  
Notes
2011-08-11 12:30:45REVIEW #2:
 FIRST ROUND OF COMMENTS NOT ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2011-07-19 Cont ID  
Sent By wjolin Date 2011-07-19 Time 15:41 Rev Time 0.00
Received By wjolin Date 2011-07-19 Time 14:54 Sent To  
Notes
2011-07-19 15:41:361009 NORTH DIXIE HIGHWAY
 PERMIT #11070279
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO NFPA 101 LIFE SAFETY CODE
 FLORIDA 2006 EDITION. THE FLOOR PLAN SHOWS MIXED USE OF
 THE OCCUPANCIES BUT VERY LIMITED INFORMATION IS
 PROVIDED FOR THE AREA AROUND THE THEATER SPACE.
  
 THIS SPACE APPEARS TO BE A CHANGE OF OCCUPANCY FROM
 MERCANTILE TO ASSEMBLY. PROVIDE A LIFE SAFETY PLAN
 SHOWING ALL OCCUPANT LOADS, FIRE RATED WALLS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 STORAGE AREAS ARE REQUIRED TO BE SEPARATED FROM THE
 ASSEMBLY AREA WITH A ONE-HOUR FIRE RATED WALL OR SHALL
 BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
  
 INDICATE HOW THE THEATER SPACE IS SEGREGATED FROM THE
 LOBBY SPACE.
  
 SHOW ALL PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE
 DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE PER SECTION 7.2.1.5.9 OF NFPA 101 FLORIDA
 EDITION 2006.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE AT LEAST SIX-INCHES IN HEIGHT AND
 SHALL CONTRAST THE BACKGROUND.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE APPROVED AND SUBMITTED IN WRITING TO THE OFFICE OF
 THE FIRE MARSHAL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2011-08-29 Cont ID  
Sent By jwitmer Date 2011-08-29 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2011-08-25 Time 15:02 Sent To  
Notes
2011-08-25 15:02:53GAVE TO WESLEY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-19 Cont ID  
Sent By lmartine Date 2011-08-11 Time 16:15 Rev Time 0.00
Received By lmartine Date 2011-08-04 Time 17:42 Sent To  
Notes
2011-08-04 17:43:58B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-26 Cont ID  
Sent By lmartine Date 2011-07-25 Time 09:05 Rev Time 0.00
Received By lmartine Date 2011-07-18 Time 16:10 Sent To  
Notes
2011-07-18 16:11:30SENT TO B14 SHELF FOR BUILDING AND FIRE REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2011-08-23 Cont ID  
Sent By jwitmer Date 2011-08-23 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2011-08-10 Time 14:57 Sent To  
Notes
2011-08-10 14:57:48BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 8/19/11 PB COUNTY IMPACT FEES- PLANS STAMPED NO FEES
 DUE. JW
  

Review Stop Z ZONING
Rev No 1 Status P Date 2011-07-25 Cont ID  
Sent By aaponte Date 2011-07-25 Time 14:08 Rev Time 0.15
Received By aaponte Date 2011-07-25 Time 14:08 Sent To  
Notes
2011-07-25 14:09:58INTERIOR WORK ONLY.