Plan Review Details - Permit 11070251
Plan Review Stops For Permit 11070251
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-13 Cont ID  
Sent By rmcdouga Date 2011-07-13 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2011-07-12 Time 18:14 Sent To  
Notes
2011-07-12 18:14:11TO RM DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2011-07-13 Cont ID  
Sent By rmcdouga Date 2011-07-13 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2011-07-13 Time 10:42 Sent To  
Notes
2011-07-13 11:09:462007 FBC W/2009 REVISIONS
  
 MECHANICAL REVISION DENIED
  
 1) SUBMIT TWO SETS OF REVISED ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS THAT CORRESPOND TO THE
 REVISED 13 SEER EQUIPMENT. THE PREVIOUSLY APPROVED
 EQUIPMENT CONSISTED OF TWO 5 TON AND A 1.5 TON SYSTEMS,
 ALL WERE 14 SEER.
  
 2) ON SHEET M-1, CU-2 IS SPECIFIED AS THE 2 TON UNIT
 AND IN THE EQUIPMENT SCHEDULE ON SHEET M-3, CU-3 IS
 SPECIFIED AS THE 2 TON UNIT. PLEASE CLARIFY.
  
 3) THE CFM IS NOT SPECIFIED AT TWO OF THE SUPPLY
 OUTLETS IN THE SECOND FLOOR SITTING/OFFICE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]