Plan Review Details - Permit 11070239
Plan Review Stops For Permit 11070239
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2011-07-22 Cont ID  
Sent By jgomez Date 2011-07-22 Time 09:43 Rev Time 0.00
Received By jgomez Date 2011-07-22 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2011-07-18 Cont ID  
Sent By jgomez Date 2011-07-18 Time 17:03 Rev Time 0.00
Received By jgomez Date 2011-07-18 Time 17:03 Sent To  
Notes
2011-07-18 17:07:06RESIDENTIAL (R2) WINDOWS REPLACEMENT BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- COMPONENT AND CLADDING DESIGN PRESSURES CALCULATIONS
 DONE BY SPECIALTY ENGINEERING NEED TO BE REVISED.
 ACCORDING TO 2009 REVISIONS SEC. 1609.4.3 FBC THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". REVISE
 CALCULATIONS AS REQUIRED.
  
 2- ENGINEER TO REVISE CALCULATIONS/LETTER FOR THE
 INSTALLATION OF 3"X3"X1/4" ALUMINUM MULLION. NEED TO
 USE EXPOSURE "C" FOR CALCULATIONS. SEC. 1609.4.3 FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-07-22 Cont ID  
Sent By jgomez Date 2011-07-22 Time 09:44 Rev Time 0.00
Received By jgomez Date 2011-07-21 Time 14:36 Sent To  
Notes
2011-07-21 14:37:08GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-18 Cont ID  
Sent By jgomez Date 2011-07-18 Time 17:07 Rev Time 0.00
Received By jgomez Date 2011-07-12 Time 15:24 Sent To  
Notes
2011-07-12 15:24:25TO MISC 1
  