Plan Review Details - Permit 11070151
Plan Review Stops For Permit 11070151
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2011-08-04 Cont ID  
Sent By rlecky Date 2011-08-04 Time 10:33 Rev Time 0.00
Received By rlecky Date 2011-08-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2011-07-12 Cont ID  
Sent By rlecky Date 2011-07-12 Time 08:34 Rev Time 0.00
Received By rlecky Date 2011-07-12 Time 08:25 Sent To  
Notes
2011-07-12 08:43:28PROVIDE PANEL SCHEDULE AND LOAD CALCULATION. NEC 215.5
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE FRONT
 AND BACK. NEC 210.52
 PROVIDE A 20 AMP BRANCH CIRCUIT FOR THE BATHROOMS. NEC
 210.11 (C)(3)
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2011-08-04 Cont ID  
Sent By rlecky Date 2011-08-04 Time 10:34 Rev Time 0.00
Received By rlecky Date 2011-08-02 Time 15:53 Sent To  
Notes
2011-08-02 15:54:19TO ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2011-07-12 Cont ID  
Sent By rlecky Date 2011-07-12 Time 08:43 Rev Time 0.00
Received By rlecky Date 2011-07-08 Time 11:12 Sent To  
Notes
2011-07-11 11:12:27TO ELECTRICAL BOX